11
3.5
Mounting the different parts of the MultiPipe system
1. Remove the protection covers.
2. Affix the installation templates on the duct wall at the designed place with
the correct distance of the collector pipes (permissible variation ±3 mm).
Cut out the openings.
3. Slip the flange, O-ring and steam hose connections onto the tube and fix
them by the four screws. From outside of the duct, insert the premounted
collector pipes through the prepared openings.
4. Put one half tube clip with O-ring onto both ends of the nozzle pipes.
Slide the nozzle pipes into the holes of the collectors to the limit stop and
so that the nozzles are situated one against the others. With a suitable
clamp press both halves of the clips together until they will be fixed by
a “click”.
5. Starting with the lowest collector pipe fix the steam hose connections
with the 4 screws at the duct wall.
6. Align the collector pipes with a down-slope of 2° against the steam con-
nector. Then, fasten the pipe ends on the duct using M8 threaded rod
or the specially designed support available as accessory (see mounting
drawing in chapter 3.6).
7. Connect the steam hose and the condensate hose to each collector pipe
according to the instructions in the installation and operating instructions
of the humidifier.
Note: with the system 1 connect the steam hose ø35/46 mm to the lower
steam connector DV71 and close the upper steam connector with the
sealing cap supplied.
4
5
6
M8
M8
7
2
3
1
ø64 mm
ø3.6 mm
2°
2°