3 Mounting
3.1 Safety
The MultiPipe steam distribution system must only be installed by
adequately
qualified personnel
.
Observe and comply with all safety instructions in the installation and
operating instructions of the steam humidifier.
3.2 Delivery
The MultiPipe steam distribution system will be delivered either premounted or
as single components. Observe the corresponding mounting instructions.
3.3
Mounting positions
The MultiPipe steam distribution system can be installed in
horizontal
or
vertical ducts
. When mounting in a vertical duct the nozzle pipes must
have a minimum declination of 20° and the end pieces of the collector pipes
must be turned, so that the vertical condensate connection directs straight
downwards (see figure below).
Note: Before mounting the MultiPipe system check the type designation
and steam capacity on the data plate to ensure that the correct MultiPipe
system is installed in the right place.
In addition to this installation and operating instructions please observe and
comply with the instructions regarding the steam installation (positioning,
max. length of steam pipe, etc.) in the installation and operating instructions
of the steam humidifier.
20°
1x
+70°
–70°