27
FAN4
DS80
KS10
Steam line
– as short as possible (length: min. 1 m and max. 4 m)
– adequate upslope/downslope min. 20 %
– no restrictions
– condensate trap at the lowest point
– hose or fixed pipe (with same inner diameter as steam
outlet)
Fan unit
(mounted separated from the steam humidifier)
Condsensate line
– min. downslope 20 %
– no restrictions
– condensate trap ømin 200 mm
to drain
to cylinder
Fig. 9: Overview steam for room humidification
ømin : 200 mm