3. Safety distances
Firewall
Ensure that the minimum safety distances are fullfiled
(
FIG 1
).
When connecting a steel chimney to the top outlet use
the security distances required by the manufacturer.
Important! When placing the insert on
a combustible floor, a steel plate of at least
0.7mm must cover the entire floor surface inside
the surround. Any flooring made of combustible
material, such as linoleum, carpets etc. must be
removed from underneath the steel plate.
4. Assembly
FIG 3 - to FIG 12
Assembling and adjusting the legs FIG 3
The insert is delivered with adjustable legs. The legs
are mounted on to the insert using the added bolts and
washers.
Fasten the screws on to the insert with a 13 mm
wrench.
Adjust legs to the desired height before returning the
insert to an upright position
(do not tilt the insert)
.
The height varries according to the surround.
Air inlet FIG 4
Assemble air inlet connector to the insert body with pro-
vided fasteners and tool, as shown on the drawing.
Flue colar FIG 5
The insert is equipped in connector which enable top
flue chimney connection.
Assemble connector with provided fasteners and tools.
Attention! Our inserts are prepared for connecting
the smoke pipe on the outside of the flue collar
Ø150.
*
Alternative versions of the flue collar exist due to
National requirements. For the flue connection to the
chimney, follow the recomenndations from the chimney
manufacturer.
The insert expands when in use, and for
this reason the surround must NEVER rest
on the insert, but have a gap of about 3 mm.
The insert must neither rest on the bench plate or
against the sides. It is recommended to dry stack
the surround in order to adjust the insert prior
to perforating the chimney for the flue connection.
Technical TABLE
Insert
N-20T
Material
Steel
Surface treatment
Heat resistant varnish
Weight of insert (kg)
99 kg
Draught system
Ignition air vent control
and air vent control
Combustion system
Clean burning
(Secondary combu-
stion)
Combustion air consumption (m³/h) 8-22,5
Maximum fuel length (cm)
40
Flue outlet
Top
Flue collar (Ø mm)
Outer 150
*alternate versions exists due to nationa requirements
Flue gas temperature at flue
connector (°C)
313
Flue gas mass flow [g/s]
8,0
Draft at flue connector
recommended (Pa)
12-25
Data according to EN 13 229
Area of convection air vent under
insert (cm2)
300
Area of convection air vent over
insert (cm2)
450
Minimum distance conv. air outlet
to ceiling (mm)
700
Nominal heat output (kW)
6,8
Efficiency (%)
78
CO @ 13% O2 (%)
0,08
Flue gas temperature (°C)
261
Draft (Pa)
>12
Fuel recommended:
Wood logs
Fuel length recommended (cm)
25-30
Fuel charge (kg)
1,55
Refueling interval (minutes)
45
Opening of the air vent control (%) 40-50
Operation*
Intermittent*
* Intermitent combustion refers to normal use of a fireplace,
i.e. new wood is inserted when the previous load has burned
down to ember
Warning: If the requirements for ventilation are
NOT complied with, the cooling airflow around the
product will be considerably reduced and
the product can overheat.
This can cause a fire.
4
GB
Summary of Contents for N-20 T
Page 29: ...N 20T mm 29 ...
Page 31: ...Tools 4 mm 2 5 mm 13 mm TORX 2 mm 3 mm 31 ...
Page 36: ...FIG 10 Heat shield Hitzeschutzbleche FIG 11 21 30011 408 x4 a b c a b c 60 60 36 ...
Page 39: ...FIG 16 Back door handle Mehrzweckschlüssel FIG 17 Handle front door 39 ...
Page 40: ...FIG 18 FIG 19 Operation handle ignition valve usage Operation handle secondary valve usage 40 ...
Page 42: ...FIG 22 22 0N20T 080 x2 FIG 23 42 ...
Page 43: ...FIG 24 FIG 24a 43 ...
Page 44: ...FIG 24b 44 ...
Page 45: ...POSITION OF THE SERIAL NUMBER POSITION DER SERIENNUMMER POSITION DU NUMÉRO DE SÉRIE 45 ...