background image

9

Figure 3. Proper Belt Tension

1/4 inch

1 f

oot

Pulley Alignment
Inspect the pulley alignment between the motor sheave 
and blower pulley. If a misalignment occurs, adjust the 
location of the motor sheave by loosening the set-screw 
in the stationary face of the motor sheave. Relocate the 
sheave assembly on the motor shaft to ensure the belt will 
be straight and aligned (Figure 2). Tighten the set-screw 
and then reinstall the fan belt. Tighten the tensioning bolts 
as described below.

Belt Tensioning
Proper belt tension can be determined by testing the 
belt defl ection at the midpoint of the pulleys. The belt 
should defl ect ¼” per foot of span between the centers 
of the pulleys (Figure 3). After the proper tension has 
been applied, tighten the motor mount bolts to secure 
the assembly, and visually inspect the area to ensure all 
tools have been removed. Inspect all wire harness and 
routings in the vicinity and make sure there is adequate 
clearance for the wire harness.

Blower Adjustments - 3 phase units only
If blower is turning opposite of arrow direction, disconnect 
all power to unit and allow all rotating equipment to stop, 
then interchange any two fi eld wired leads at the terminal 
block OR disconnect connections. 

The blower speed has been preset at the factory. For 
optimum system performance and comfort, it may be 

necessary to change the factory set speed. Adjustment 
of the blower speed is made through varying the pitch of 
the motor pulley, this adjustment allows for a wide range 
of installation applications. Refer to Table 4 (page 12) for 
blower performance data.

 WARNING:

Never perform maintenance on energized or rotating 
equipment. Always disconnect electrical power and 
allow all rotating equipment to stop before servicing 
the unit. Failure to do so may result in personal 
injury, loss of limb, or death from electrical shock 
or entanglement in moving parts. 

UNIT MAINTENANCE

The maintenance information listed below should be 
performed in accordance with the Maintenance Schedule 
shown in Figure 9 (page 16).

Filters
To clean permanent fi lters, remove the fi lters and wash 
gently with mild soap and water. Rinse in clean, hot water 
and allow to drain & dry thoroughly before reinstalling.

Drain Pan
The drain pan and the drain lines should be cleaned to allow 
condensate to drain properly. Remove any accumulation 
of residue or sludge from the drain pan. Inspect in and 
around the drain pan for rust, holes, and leaks.

V-Belts
Inspect for cracks, tears, and excessive or abnormal wear. 
V-belts tend to elongate over time with normal application 
and use. Ensure the belt always maintains adequate 
tension without over tightening. Belts which have been 
over tightened will wear out rapidly and may cause motor 
and blower bearings to receive undue strain and wear. 
As a result the unit could experience excessive vibration 
and noise problems.

Blower Bearings
The blower assembly incorporates sealed bearings. Under 
normal operating conditions, no maintenance is necessary 
for the life of the equipment.

Blower Fan Wheel
Inspect the blower wheel blades for accumulations of dirt 
and clean if necessary. Inspect mounting nut for tightness 
when done.

Blower Motor and Assembly
Inspect the blower assembly and motor mounting 
brackets for tightness and corrosion. Correct defi ciencies 
if neccessary. The blower motor contains sealed bearings 
and under normal operating conditions, no maintenance 
is necessary for the life of the equipment.

Figure 2. Proper Belt Alignment

Summary of Contents for B5SM -090 Series

Page 1: ...ss to it in the future If a problem occurs check the instructions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor These instructions a...

Page 2: ...6 Electrical Wiring 7 Pre Electrical Checklist 7 Line Voltage 7 Thermostat Connections 7 Electrical Wiring with a Duct Heater 7 Unbalanced 3 Phase Supply Voltage 8 Grounding 8 Startup Adjustments 8 Pr...

Page 3: ...type equipment All electrical wiring must be completed in accordance with local state and national codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Canadian Ele...

Page 4: ...be given to availability of electric power service access noise and shade Field Connections for Electrical Power Supply All wiring must comply with current provisions of the National Electrical Code...

Page 5: ...hes Note It is recommended that a secondary drain pan be used when the unit is hung above an enclosed ceiling Connecting Refrigerant Tubing WARNING Evaporator Coils are factory shipped with a nitrogen...

Page 6: ...Z bracket See Figure 1 5 Secure the filter slide assembly together with the four screws Table 2 Electrical Rating Data MODEL VOLTAGE PHASE Hz FLA HP MCA MOP 090 120 J 208 230 460 3 60 6 6 6 6 3 3 2 8...

Page 7: ...re making any electrical connections to the unit See Figure 6 page 13 These air handlers can be purchased in both single and three phase power configurations all single phase equipment is shipped from...

Page 8: ...d verify the moveable face is properly secured Grounding WARNING The unit cabinet must have an uninterrupted or unbrokenelectricalgroundtominimizepersonal injury if an electrical fault should occur Do...

Page 9: ...zedorrotating equipment Always disconnect electrical power and allowallrotatingequipmenttostopbeforeservicing the unit Failure to do so may result in personal injury loss of limb or death from electri...

Page 10: ...57 Filter Rack Frame 60 1 4 Cabinet Width 1 5 8 1 5 8 25 1 16 Filter Rack 16 1 4 Electrical Knock outs Condensate Drain Figure 4 B5SM Physical Dimensions for Horizontal Installations 47 5 8 Center to...

Page 11: ...er Rack Frame 60 1 4 Cabinet Width 18 13 16 Supply Duct Opening 22 1 16 19 3 8 27 3 8 Cabinet Depth without Filter Rack 2 16 1 4 Supply Duct Opening 9 1 8 29 5 16 Depth with Filter Rack 25 1 16 Filter...

Page 12: ...8 0 9 1 0 CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw B5SM 120 2HP 60 Hz Fully Closed 4789 868 2 12 4640 868 2 00 4442 870 1 95 4208 873 1 87 40...

Page 13: ...ONLY NOTES 1 Disconnect all power before servicing 2 If wiring must be replaced use only 105 C copper wire of the same gauge 3 For economizer application remove black wire from low voltage board Y te...

Page 14: ...0 GRN GRY YEL BLK ORN RED RED WHITE BLUE VIO 14 GRN 18 GRN 18 RED 12 GRY 12 BLK 12 BLU 12 BLK 12 NOTES 1 C W2 to be connected to electric heat 2 Remove BLACK wire from air handler low voltage terminal...

Page 15: ...ANGE RED RED WHITE BLUE VIO 14 GRN 18 GRN 18 RED 12 GRY 12 BLK 12 BLU 12 BLK 12 BLACK BLACK GREEN BROWN SINGLE STAGE HEAT PUMP THERMOSTAT NOTE 1 NOTE 2 NOTE 4 NOTE 5 NOTE 3 G Y E R O B W2 C NOTES 1 Ju...

Page 16: ...all coil connections for leaks x Air Handler Assm Inspect Mounting Hardware for security and corrosion x Inspect Filter Rack mounting hardware for security x Inspect panel assemblies for proper insta...

Reviews: