Model Number JT5BD-
018K
024KA
030KA
036K
042K
048K
060K
Electrical
Data
Volts-Cycles-Phase (1)
208/230-60-1
Total Amps
9.9
11.8
14.6
15.7
17.5
19.7
26.4
Delay Fuse Max. (2)
20
25
30
30
35
40
50
Min. Circuit Ampacity
12.1
14.5
18.0
19.4
21.6
24.3
32.6
Component
Data
Coil
Area
15.17
15.17
22.88
25.42
22.88
25.42
25.42
Rows-FPI
1 - 18
1 - 18
1 - 20
1 - 20
2 - 16
2 - 16
2 - 16
Tube Dia
3/8” O.D.
Fan Motor
Type
PSC
Amps
0.91
0.91
1.00
1.00
1.00
1.4
1.4
HP
1/8
1/8
1/4
1/4
1/4
1/4
1/4
Fan Blade
Dia-#
Blades
24” - 3
SCFM
2370
2370
3000
3000
3000
4000
4000
Compressor Data
RLA
8.3
10.8
13.4
15.3
19.2
19.8
25.3
LRA
40.3
56
68
87
112
105
146
Refrigerant suction line:
Length/
O.
Liquid Line:
All Lengths - 3/8” O.D.
0-24 ft.
3/4”
3/4”
3/4”
3/4”
7/8”
7/8”
7/8”
25-39 ft.
3/4”
3/4”
3/4”
7/8” (3)
7/8”
7/8”
1-1/8” (4)
40-75 ft.
3/4”
3/4”
7/8” (3)
7/8” (3)
7/8”
1-1/8” (4)
1-1/8” (4)
R-22 Refrigerant charge (in ounces):
(Outdoor unit, Indoor Unit 15’ Line Set)
93
96
144
155
248
248
268
Approximate Weight (lbs.)
Net
166
171
190
204
252
276
285
Ship
175
180
200
215
265
290
300
(1) Operating Voltage Range: 198v min. - 253v max.
(2) HACR type circuit breakers may be used.
(3) Requires 7/8" to 3/4" reducer from line to unit.
(4) Requires 1 1/8" to 7/8" reducer from line to unit.