background image

7

Burner Operation

Perform the startup instructions on page 7. The igniter 
should ignite the closest burner and the fl ames  should 
quickly carryover to the other burners. The fl ames should 
be bright blue, with occasional yellow streaks.

New Construction

The operation of gas furnaces in a construction environment 
can cause a variety of problems with the furnace. Before 
occupying the residence, homeowners should have these 
safety inspections performed by a licensed technician:

• The 

fi lter must be replaced or cleaned and the furnace 

must be inspected by a licensed HVAC technician. 
The furnace must be cleaned and/or repaired if found 
to be dirty, damaged, or malfunctioning in any way. 
Before occupancy, the furnace shall be inspected 
and approved by applicable local authority even if 
this results in redundant inspections. 

•  The duct work must be inspected and cleaned if 

found to contain any construction debris.

If the furnace fails to operate check the following:

1.  Is the thermostat operating properly?

2.  Are the blower compartment door(s) in place?

3.  Has the circuit breaker tripped or the control board 

fuse burned open?

4.  Is the gas turned on at the manual shutoff?

5.  Is the fi lter dirty or clogged?

If the furnace continues to not operate, contact a licensed 
HVAC technician 

MAINTENANCE ITEM

FREQUENCY OF MAINTENANCE

BEGINNING OF EACH 

HEATING SEASON

END OF EACH 

HEATING SEASON

MONTHLY

Verify furnace area is free of 
combustible materials.

X

X

X

Verify combustion and 
ventilation air is not restricted.

X

X

X

Verify no signs of physical 
deterioration of the furnace.

X

X

X

Verify no obstructions or 
restrictions in vent or chimney.

X

X

Verify no holes or cracks in 
vent pipe.

X

X

Verify no corrosion in vent 
pipe.

X

X

Verify the horizontal vent 
pipes slope upwards away 
from furnace.

X

X

Verify burner fl ame.

X

Clean or replace fi lter(s).

X

Clean blower compartment.

X

Clean burner assembly.

X

Clean condensate collection 
and disposal system (if ap-
plicable).

X

Table 1. Maintenance Table

TROUBLESHOOTING

Summary of Contents for M4RC 92.1% AFUE Upflow

Page 1: ...ITION 65 WARNING This product contains chemicals known to the state of California to cause cancer birth defects or other reproductive harm Gas Furnaces USER MANUAL Congratulations on the purchase on y...

Page 2: ...Furnace 5 Furnaces Components 5 Venting System 5 Category IV Furnaces 5 Combustion Air Requirements 5 Sources of Corrosion 5 Furnace in Small Room or Closet 5 Startup and Shutdown 6 Starting the Furn...

Page 3: ...n propertydamage carbonmonoxidepoisoning personal injury or death WARNING The safety information listed throughout this manualmustbefollowedduringtheinstallation service and operation of this furnace...

Page 4: ...ng Down the Furnace Should you ever need to shut down your furnace for service or maintenance shut off the gas at the gas valve first by moving the switch to the OFF Position Figure 1 If your installa...

Page 5: ...ers has occurred and must be corrected immediately Only a licensed HVAC technician can reset this switch Here is a problem that should be avoided Sometimes a furnace is properly installed and located...

Page 6: ...y by a licensed HVAC technician Homeowners should perform frequent visual inspections Table 1 on page 9 contains suggested inspections and frequency of maintenance Venting System Existing vent pipes s...

Page 7: ...s If the furnace fails to operate check the following 1 Is the thermostat operating properly 2 Are the blower compartment door s in place 3 Has the circuit breaker tripped or the control board fuse bu...

Page 8: ...pecifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 05 08 O Fallon MO 7088750 1 Blower Assembly 2 Blower Door Switch 3 Burner Assembly 4...

Reviews: