background image

38

AIRFLOW DATA

Model

Number

Heating

Input

(Btuh)

Motor

Speed

External Static Pressure (Inches Water Column)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

UPFLO

W FURNA

CES

RC054-24B

Bottom Retur

n

54,000

High*

1550

30

1520

30

1485

31

1450

32

1410

33

1360

34

1300

35

1255

37

Med-High

1250

37

1220

38

1200

38

1170

39

1140

40

1105

42

1065

43

1010

46

Med-Low**

935

49

910

51

880

52

850

54

815

56

785

59

735

63

680

68

Low

720

64

690

67

655

70

620

74

585

79

550

84

520

88

485

95

RC054D-24B

Side Retur

n

54,000

High*

1630

28

1595

29

1560

29

1525

30

1480

31

1430

32

1365

34

1320

35

Med-High

1315

35

1280

36

1260

37

1230

37

1200

38

1160

40

1120

41

1060

43

Med-Low**

980

47

955

48

925

50

890

52

855

54

825

56

775

59

715

64

Low

755

61

725

63

690

67

650

71

615

75

580

79

545

84

510

90

RC072D-35C

Bottom Retur

n

72,000

High*

1895

32

1790

34

1720

36

1630

38

1550

40

1445

42

1330

46

1225

50

Med-High**

1775

35

1710

36

1650

37

1550

40

1470

42

1385

44

1290

48

1180

52

Med-Low

1255

49

1200

51

1155

53

1105

56

1050

58

1000

61

925

66

830

74

Low

1140

54

1100

56

1065

58

1025

60

980

63

930

66

870

70

805

76

RC072D-35C

Side Retur

n

72,000

High*

1970

31

1865

33

1780

34

1695

36

1615

38

1505

41

1385

44

1275

48

Med-High**

1845

33

1780

34

1715

36

1615

38

1530

40

1440

43

1340

46

1230

50

Med-Low

1305

47

1250

49

1200

51

1150

53

1090

56

1040

59

965

64

865

71

Low

1185

52

1145

54

1110

55

1065

58

1020

60

965

64

905

68

840

73

RC072D-35C

Side + Bottom

or 2 Sides

72,000

High*

1990

31

1880

33

1805

34

1710

36

1630

38

1510

41

1400

44

1285

48

Med-High**

1865

33

1795

34

1735

35

1630

38

1545

40

1455

42

1355

45

1240

49

Med-Low

1320

46

1260

49

1215

50

1160

53

1105

56

1050

58

970

63

875

70

Low

1200

51

1155

53

1120

55

1075

57

1030

60

975

63

915

67

845

73

RC090D-35C

Bottom Retur

n

90,000

High*

2155

36

2090

37

2015

38

1960

39

1910

40

1835

42

1755

44

1660

46

Med-High**

2015

38

1960

39

1920

40

1860

41

1805

42

1755

44

1695

45

1615

47

Med-Low

1705

45

1675

46

1640

47

1590

48

1555

49

1495

51

1435

53

1340

57

Low

1410

54

1390

55

1365

56

1330

58

1310

59

1275

60

1235

62

1210

63

RC090D-35C

Side Retur

n

90,000

High*

2240

34

2175

35

2100

37

2040

38

1985

39

1910

40

1825

42

1725

44

Med-High**

2095

37

2040

38

2000

38

1935

40

1875

41

1825

42

1765

43

1680

46

Med-Low

1775

43

1740

44

1705

45

1655

46

1615

47

1555

49

1490

51

1335

57

Low

1465

52

1445

53

1420

54

1385

55

1360

56

1325

58

1285

60

1260

61

RC090D-35C

Side + Bottom

or 2 Sides

90,000

High*

2265

34

2195

35

2115

36

2060

37

2005

38

1930

40

1845

42

1745

44

Med-High**

2115

36

2060

37

2015

38

1955

39

1895

40

1845

42

1780

43

1695

45

Med-Low

1790

43

1760

44

1725

44

1670

46

1635

47

1570

49

1510

51

1410

54

Low

1480

52

1460

53

1435

53

1400

55

1375

56

1340

57

1300

59

1270

60

RC108D-45D

Bottom only

or 2 openings

108,000

High*

2135

43

2095

44

2040

45

1975

47

1910

48

1840

50

1735

53

1675

55

Med-High**

2000

46

1955

47

1900

48

1845

50

1800

51

1735

53

1665

55

1570

59

Med-Low

1665

55

1660

55

1625

57

1590

58

1530

60

1500

61

1415

65

1340

69

Low

1385

66

1360

68

1310

70

1300

71

1275

72

1250

74

1200

77

1150

80

RC108D-45D

Side Retur

n

108,000

High*

2115

43

2075

44

2020

46

1955

47

1890

49

1822

50

1720

53

1660

55

Med-High**

1980

46

1935

48

1880

49

1830

50

1780

52

1720

53

1650

56

1555

59

Med-Low

1650

56

1645

56

1610

57

1575

58

1515

61

1485

62

1400

66

1330

69

Low

1370

67

1345

68

1300

71

1290

71

1260

73

1240

74

1190

77

1140

81

DO

WNFLO

FURNA

CES

RL090-35C

90,000

High*

1,955

39

1,905

40

1,835

42

1,795

43

1,730

44

1,620

47

1,545

50

1,450

53

Med-High**

1,845

42

1,790

43

1,750

44

1,680

46

1,515

51

1,540

50

1,475

52

1,410

54

Med-Low

1,320

58

1,290

59

1,250

61

1,215

63

1,180

65

1,120

68

1,050

73

970

79

Low

1,190

64

1,165

66

1,125

68

1,080

71

1,055

73

1,000

77

945

81

875

88

NOTES:

* Factory Set Cooling Speed
** Factory Set Heating Speed
1. Two openings are recommended for airfl ows above 1,600 CFM if fi lter(s) is(are) adjacent to furnace.
2. Temperature rises in the table are approximate. Actual temperature rises may vary.
3. Temperature rises shaded in gray are for reference only. These conditions are not recommended.

Table 8. Blower Performance

Summary of Contents for M4RC

Page 1: ...tarting the installation Return these instructions to the customer s package for future reference GAS FURNACES Installation Instructions 92 1 AFUE PROPOSITION 65 WARNING This product contains chemicals known to the state of California to cause cancer birth defects or other reproductive harm WARNING DO NOT DESTROY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE FIRE OR EXPLOSION HAZARD Failure to follow ...

Page 2: ...w Furnace Installation 16 Downflow Furnace Installation 16 Alternate Attachment Method 18 Bottom Panel Removal 19 Alternate Bottom Panel Removal 19 Pressure Switch Relocation 19 Inducer Assembly Rotation 20 Direct Vent 2 Pipe Applications 20 Vent and Inducer Assembly Options 20 Accessories 21 Finish Flange 21 Rubber Grommets 21 Inline Drain Assembly 21 PVC TEE Reducer and Hose Barbs 21 Condensate ...

Page 3: ...rnace Failuretofollowsafety recommendations could result in possible damage to the equipment serious personal injury or death Use only with type of gas approved for this furnace Refer to the furnace rating plate Install this furnace in accordance to the minimum clearances to combustible materials listed in Table 1 page 9 Provide adequate combustion and ventilation air to the furnace space as speci...

Page 4: ... of eight feet away and read Gas Vent Directly Below 2 For direct vent appliances mechanical vent heating appliances or domestic hot water equipment where the bottom of the vent terminal and the air intake is installed above four feet above grade the following requirements must be satisfied a A CO detector and alarm shall be placed on each floor level where there are bedrooms The detector shall co...

Page 5: ...source of combustion air is to use outdoor air However the use of indoor air in most applications is acceptable except as listed If the furnace is a single pipe installation and installed in a confined space it is required that the necessary combustion air come from the outdoors by way of attic crawl space air duct or direct opening See pages 6 9 for combustion air requirements Installations in th...

Page 6: ... area with volume less than 50 cubic feet per 1 000 Btuh of the combined input rates of all appliances drawing combustion air from that space COMBUSTION AIR REQUIREMENTS General Information Provisions must be made during the installation of this furnace that provide an adequate supply of air for combustion NORDYNE condensing furnaces must be installed with outdoor combustion air piped directly to ...

Page 7: ...l equipment in the enclosure Alternate Air Inlet Outlet Air Outdoor Air Using Vertical Ducts If combustion air is taken from outdoors through vertical ducts the openings and ducts must have a minimum free area of one square inch per 4 000 Btuh of total appliance input Attics or crawl spaces must connect freely with the outdoors if they are the source of air for combustion and ventilation See Figur...

Page 8: ...wl or attic space that connects with the out of doors 2 The opening must have a minimum free area of 1 sq in per 3 000 Btu per hour of the total input rating of all equipment located in the enclosure 3 The free area must not be less than the sum of all the areas of the vent connectors in the enclosure Installation in Unconfined Spaces An unconfined space is an area including all rooms not separate...

Page 9: ... operate a summer exhaust fan 6 Follow the lighting instructions Place the appliance being inspected into operation Adjust the thermostat so appliance is operating continuously 7 Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle 8 If improper venting is observed during any of the above ...

Page 10: ... their venting and can allow combustion gases to escape through such appliances or vents Do not vent the furnace to a fireplace chimney or building chase Upon completion of the furnace installation carefully inspect the entire flue system both inside and outside the furnace to assure it is properly sealed Leaks in the flue system can result in serious personal injury or death due to exposure of fl...

Page 11: ...at there are no sagging sections that can trap condensate Outdoor Terminations Horizontal Venting Vent and combustion air intake terminations shall be installed as depicted in Figures 6 7 page 12 and in accordance with these instructions Vent termination clearances must be consistent with the NFGC ANSI 2223 1 NFPA 54 and or the CSA B149 1 Natural Gas and Propane Installation Code All minimum clear...

Page 12: ...ing may be installed in an existing chimney which is not in use provided that Both the exhaust vent and air intake run the length of the chimney The top of the chimney is sealed and weatherproofed The termination clearances shown in Figure 9 are maintained No other gas fired or fuel burning equipment is vented through the chimney Vent Freezing Protection When the vent pipe is exposed to temperatur...

Page 13: ...tion Existing Installations When an existing furnace is removed from a vent system serving other appliances the existing vent system may not be sized properly to vent the remaining appliances Example water heater An improperly sized venting systemcanresultintheformationofcondensate leakage or spillage The existing vent system should be checked to make sure it is in compliance with NFGC ANSI Z223 1...

Page 14: ...n air applications When a cooling system is installed which uses the furnace blower to provide airflow over the indoor coil the coil must be installed downstream on the outlet side of the furnace or in parallel with the furnace If a cooling system is installed in parallel with the furnace a damper must be installed to prevent chilled air from entering the furnace and condensing on the heat exchang...

Page 15: ...hlocalcodes for special requirements For best sound performance install all the needed gaskets and grommets around penetrations into the furnace such as for electrical wiring FURNACE INSTALLATION RC series gas furnaces are shipped ready for installation in the upflow position with upflow return air RL series gas furnaces may only be used for downflow operation See Table 1 page 9 for the required c...

Page 16: ...re in place using the provided attachment brackets To install the brackets position one bracket on side of furnace and using the provided self drilling screws secure the bracket to the A C coil box and the furnace Repeat for other side of furnace 5 Position the plenum on top of the coil box and secure together with sheet metal screws The screws must penetrate the sheet metal casing and coil box fl...

Page 17: ...k the cut out area on the supply air duct by tracing around the connector tabs Figure 11 page 16 of the duct connector c Remove the duct connector and cut out the marked area of the supply air duct 1 4 larger the actual cutout drawn d Install the duct connector back in the floor opening with the bottom tabs extending into the supply air duct e Installthemountingplate Figure14 undertheback side of ...

Page 18: ...tthetopofthesupplyairductasindicated in Option 1 or Option 2 Figure 20 With Option 1 choice cut out the metal from the shaded area 2 Fold the two flaps Options 1 or 2 up to form the opening for the duct connector 3 Install the duct connector with the bottom tabs extending into the supply air duct 4 Bend the tabs on the bottom of the duct connector upwards and as tight as possible against the suppl...

Page 19: ...lide bottom panel 6 out through front of furnace 7 Reinstall the blower assembly 4 in reverse order 6 7 5 1 2 3 4 Figure 22 Bottom Panel Removal Pressure Switch Relocation In some inducer orientations the inducer pressure switch may interfere with gas pipe installation Check the side of the cabinet the gas pipe will enter and determine if the inducer pressure switch needs to be moved If the switch...

Page 20: ... HIGH EAC L1 XFMR HUM 24V L1A NEUTRALS 2 7 8 9 2 FAN 5 2 1 3 6 4 Direct Vent 2 Pipe Applications It is important that Direct Vent 2 pipe systems maintain an airtight flow path from the air inlet to the flue gas outlet The furnace ships from the factory with two holes in the cabinet for the air inlet and flue gas outlet In certain configurations it is necessary to remove and relocate a plastic cap ...

Page 21: ...ecommended you dry fit them first to ensure proper fit and alignment with other vent pipes 1 Install the 1 2 x 1 2 hose barb on the 2 PVC reducer with an adequate amount of approved sealant on the threads Do not over tighten the hose barb 2 Install the tee on the 2 vent pipe that is extending out the side of the cabinet Use appropriate primer and cement to permanently bond the tee to the 2 PVC pip...

Page 22: ...ake care that this drain tube does not sag in the middle Sometimes the lowest point in the vent system is where it connects to the inducer Options 3 6 9 12 If the distance between the exhaust pipe and the cabinet is 6 inches or less one drain at this location is sufficient If the distance is more than 6 inches then another drain will need to be added to the bottom of the tee IMPORTANT NOTE If the ...

Page 23: ... box Upflow Furnaces Combustion air and exhaust vent piping must have removable connections between the furnace flanges and vent pipes when installed vertically in front of the coil box NOTE Both vent pipes must be long enough to clear the height of the coil box when installed This allows for future servicing or maintenance of the coil Position the 2 x 3 neoprene coupling between the top of the 2 ...

Page 24: ...nnected to the furnace This includes connections at the main gas valve emergency shutoff valve and flexible gas connectors if applicable The soap and water solution can be applied on each joint or union using a small paintbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeatthetighteningandsoapcheckprocess until bubbling ceases IMPORTANTNOTE Whenp...

Page 25: ...o use the properconversionkitcancausefire explosion propertydamage carbonmonoxidepoisoning personal injury or death This furnace can be converted from factory equipped natural gas to Liquid Propane gas Conversion of this valve requires replacement of the burner orifices on the manifold assembly The orifices required for conversion are supplied with the furnace For altitudes between 0 and 1 999 fee...

Page 26: ...assembly 6 Make sure the center of the orifices are aligned with center of the burners q Secure the manifold assembly 5 to the burner assembly 6 with the four screws 4 removed in step 1 h r Reconnect the gas piping to the gas valve inlet 3 ON OFF IN N A T N A T L P L P Other side of cap Pressure Regulator Cap Manifold Pressure Plug Inlet Pressure Plug ON OFF Knob OR Figure 35 Gas Valve Top View s ...

Page 27: ...ially available soap solution A fire or explosion may result causing property damage personal injury or loss of life Failure to follow the safety warnings exactly could result in serious injury death or property damage a Turn the main gas supply valve on the outside of the furnace to the ON position b Check all gas connections for leaks with a soap and water solution If the solution bubbles there ...

Page 28: ... utilities require Shut Off Valve to be 4 to 5 feet above floor B Inducer assembly omitted for clarity of pipe installation Figure 36 Typical Gas Connections 4 7 5 3 6 UPFLOW MODELS DOWNFLOW MODELS 9 2 See Note B 1 3 See Note B Right Side Entry Left Side Entry Right Side Entry Left Side Entry See Note B See Note B 7 2 9 4 6 1 5 8 4 9 9 4 See Note A See Note A 6 6 5 1 2 3 7 5 3 7 1 2 See Note A See...

Page 29: ... proper cooling mode operation Connect R W For Heating Only 2 ELECTRONIC AIR CLEANER MOTOR SPEED TAPS NOT USED HUMIDIFIER TAP NEUTRAL LEADS 6 3 4 1 7 8 9 5 2 6 3 4 1 FAN IMPORTANTNOTE Settheheatanticipatoraccording to the instructions supplied by the thermostat manufacturer To determine the heat anticipator setting 1 Add the current draw of the system components or 2 Measurethecurrentflowonthether...

Page 30: ...ite Field Line Voltage Wiring Factory Line Voltage Wiring Ground Ground Junction Box may be int or ext to the furnace These connections can be made in the field supplied disconnect at the furnace Ground Furnace Model Number RC RL Furnace Input Btuh Cabinet Width in Nominal Electrical Supply Maximum Operating Voltage Minimum Operating Voltage Maximum Furnace Amperes Minimum Wire Gauge Maximum Fuse ...

Page 31: ...tment door 2 Setthethermostat5degreesaboveroomtemperature and observe the ignition sequence START UP AND ADJUSTMENTS Pre Start Check List Verify the polarity of the connections are correct the line voltage power leads are securely connected and the furnace is properly grounded Verify the thermostat wires R W Y and G are securely connected to the correct leads on the terminal strip of the circuit b...

Page 32: ...goff curling orfloating The flames should be blue without yellow tips 3 After validating the flame change thermostat setting to below room temperature 4 Verify the burner flame is completely extinguished 5 Replace the burner compartment door Verifying Operation of the Supply Air Limit Switch A properly functioning limit switch should turn off the gas valve when the return is blocked time depends o...

Page 33: ... potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death Air Filter s WARNING Never operate the furnace without a filter in place Dust and lint can build up on internal components resulting in loss of efficiency equipment damage and possible fire NOTE An air filter is supplied with the furnace as shipped from the factory It is recommended ...

Page 34: ...ressure Switch Open Fault Flash On Open Limit Switch Fault Flash Off Motor Fault On Off Diagnostic Description Yellow LED Low Flame Sensor Signal Continuous Flash Flame Present On Table 7 Control Board Fault Codes DESCRIPTION OF COMPONENTS Thedescriptionsbelowarevariousfunctionalcomponents that affect the operation and shutting down of this furnace Some of these components and their locations are ...

Page 35: ... des foyers 5 Mettre en service les sécheuses et tout autre appareil qui n est pas raccordé à la systéme d évacuation Faire fonctionner à régime maximal tout ventilateur d évacuation tel que les hottes de cuisinière et les ventilateurs de salles de bains Ne pas mettre en service les ventilateurs d été 6 Respecter les instructions d allumage Mettre en service l appareil à l essai Régler le thermost...

Page 36: ...allateur qualifié un organisme de service ou le fournisseur de gazstaller service agency or the gas supplier Ne pas entreposer ni utiliser de l essence ni d autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ni de tout autre appareil QUE FAIRE S IL Y A UNE ODEUR DE GAZ Ne pas tenter d allumer aucun appareil Ne toucher à aucun interrupteur électrique n utiliser aucun téléphon...

Page 37: ...om Return Opening Bottom Return Opening RC Upflow Furnace RC Model s Dim A Dim B Dim C 054D 24B 17 15 16 072D 35C 21 19 19 090D 35C 108D 45D 24 22 23 NOTES Dimensions shown in inches A 34 28 10 22 22 2 22 Ø HOLE FOR ELECTRIC 22 25 17 7 16 29 17 22 25 Ø 1 HOLE FOR GAS Ø HOLE FOR THERMOSTAT LEFT SIDE RIGHT SIDE Ø HOLE FOR ELECTRIC CONDENSATE CONDENSATE 25 22 1 X 3 HOLE FOR GAS Ø 3 HOLE FOR VENT PIPE...

Page 38: ... 47 Med Low 1705 45 1675 46 1640 47 1590 48 1555 49 1495 51 1435 53 1340 57 Low 1410 54 1390 55 1365 56 1330 58 1310 59 1275 60 1235 62 1210 63 RC090D 35C Side Return 90 000 High 2240 34 2175 35 2100 37 2040 38 1985 39 1910 40 1825 42 1725 44 Med High 2095 37 2040 38 2000 38 1935 40 1875 41 1825 42 1765 43 1680 46 Med Low 1775 43 1740 44 1705 45 1655 46 1615 47 1555 49 1490 51 1335 57 Low 1465 52 ...

Page 39: ...ion Yellow LED Continuous Flash On Alternating Flash IGNITOR INDUCER FLAME SENSOR C BLOWER LIMIT SWITCH DOOR SWITCH R 4 SPEED MOTOR WHITE RED BLUE ORANGE BLACK BLOWER LIMIT SWITCH GAS VALVE H MH ML L C FLAME ROLLOUT SUPPLY AIR LIMIT PRESSURE SWITCH R C Y G W LOW ML MH HIGH EAC L1 XFMR HUM 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 COM GREEN YELLOW RED 3 AMP FUSE 24V 1 2 3 4 24 V 120 V WHITE BLACK WHITE W BLK S...

Page 40: ... 375 750 104 35 173 346 50 72 360 720 106 34 170 340 52 69 346 692 108 33 167 333 54 67 333 667 110 33 164 327 56 64 321 643 112 32 161 321 58 62 310 621 114 32 158 316 60 60 300 600 116 31 155 310 62 58 290 581 118 31 153 305 64 56 281 563 120 30 150 300 CAPACITY OF BLACK IRON GAS PIPE CU FT PER HOUR FOR NATURAL GAS SPECIFIC GRAVITY 0 60 NOMINAL BLACK IRON PIPE DIAMETER IN LENGTH OF PIPE RUN FT 1...

Page 41: ...HIGH HIGH 10 000 FT LOW LOW HIGH HIGH HIGH HIGH HIGH HIGH HIGH Table 12 Natural Gas Heating Values Table 11 High Altitude Deration Chart for Propane Gas PROPANE GAS ALTITUDE ABOVE SEA LEVEL INPUT BTU 54 000 72 000 90 000 108 000 0 to 1 999 FT 56 56 56 56 ORIFICE SIZE 10 0 10 0 10 0 10 0 MANIFOLD PRESSURE 2 000 to 2 999 FT 56 56 56 56 ORIFICE SIZE 9 0 9 0 9 0 9 0 MANIFOLD PRESSURE 3 000 to 4 999 FT...

Page 42: ... 3 0 3 0 MANIFOLD PRESSURE 9 000 to 9 999 FT 49 49 49 49 ORIFICE SIZE 2 8 2 8 2 8 2 8 MANIFOLD PRESSURE NATURAL GAS LOW HEATING VALUE ALTITUDE ABOVE SEA LEVEL INPUT BTU 54 000 72 000 90 000 108 000 0 to 1 999 FT 47 47 47 47 ORIFICE SIZE 3 5 3 5 3 5 3 5 MANIFOLD PRESSURE 2 000 to 2 999 FT 47 47 47 47 ORIFICE SIZE 3 5 3 5 3 5 3 5 MANIFOLD PRESSURE 3 000 to 3 999 FT 47 47 47 47 ORIFICE SIZE 3 3 3 3 3...

Page 43: ...pply inlet to building or the combustion air inlet to any other appliance 6 inches 15cm for appliances 10 000 Btuh 3kW 6 inches 15cm for appliances 10 000 Btuh 3kW 4 ft 1 2m below or to side of opening 1 ft 300mm above opening 12 inches 30cm for appliances 10 000 Btuh 100 000 Btuh 30kW 9 inches 23cm for appliances 10 000 Btuh 50 000 Btuh 30kW 36 inches 91cm for appliances 100 000 Btuh 30Kw 12 inch...

Page 44: ...se to Furnace as Possible 2 x 3 Neoprene Couplings with 2 Hose Clamps Upward Pitch 1 4 Per Foot Exhaust Vent 5 3 Combustion Air Vent Pipe 7 3 x 90 Elbows 3 x 90 Elbow Exhaust Vent 3 Exhaust Vent Straps or Other Suitable Supports at minimum 5 ft Intervals 3 Combustion Air Vent Pipe 3 Exhaust Vent 3 x 90 Elbows Upward Pitch 1 4 Per Foot Exhaust Vent First Support as Close to Furnace as Possible See ...

Page 45: ...lug X See View C Header Box Drain Inline Drain This drain not needed if X is less than 6 Header Box Drain 1 All drain lines must be trapped with J Trap or field supplied loop 2 Drain line traps may be positioned inside or outside the cabinet 3 PVC Cap is required for options 5 and 6 NOTES Exhaust Vent Exhaust Vent Exhaust Vent Exhaust Vent Inlet Air Exhaust Vent Inlet Air Inlet Air Tubing is route...

Page 46: ... Plug See View F See View E See View F See View E Plug Plug See View D See View D See View L See View M See View M See View L 1 All drain lines must be trapped with J Trap or field supplied loop 2 Drain line traps may be positioned inside or outside the cabinet NOTES Exhaust Vent Exhaust Vent Exhaust Vent Exhaust Vent Exhaust Vent Exhaust Vent Inlet Air Inlet Air Inlet Air PVC TEE Reducer and 1 2 ...

Page 47: ...h 13 Pressure Switch s B C D cabinets only 14 Roll Out Switch s 15 Transformer 9 4 10 12 15 14 2 6 3 7 8 1 11 13 5 Figure 46 Downflow Gas Furnace Components 9 1 2 12 13 12 3 14 6 7 8 11 10 15 4 5 ITEM COMPONENT NAME 1 Blower Assembly 2 Blower Door Switch behind blower panel 3 Burner Assembly 4 Control Board 5 Finish Flange 6 Flame Sensor 7 Gas Manifold 8 Gas Valve 9 Igniter 10 Inducer Assembly 11 ...

Page 48: ...ion and ventilation YES NO Installation Altitude ____________________ FT Deration Percentage ___________________ Furnace Input _______________________ Btuh Supply Air Temperature ________________ F Return Air Temperature ________________ F Temperature Rise ____________________ F VENTING SYSTEM Vent free from restrictions YES NO Filter s secured in place YES NO Filter s clean YES NO Flue connection...

Reviews: