background image

11

Blower configurations
Selecting Minimum Electric Heat Airflow
The minimum electric heat airflow setting controls the 
minimum air flow that will be produced whenever electric 
heater kits are used. When the electric heater kit is 
energized along with a heat pump, the airflow may be higher 
depending on the basic cooling/heat-pump airflow setting. 
The minimum electric heat airflow is selected by the red 
blower wire on 3-speed models or setting switches 1,2,3 
& 4 on B7EM models. B7VM models automatically set the 
heating speed based on the amount of installed heat. The 
A/B switch must be set appropriately for the unit cabinet 
size. For C-sized cabinets, the A/B switch can be set in 
either position. The remaining 3 HEAT switches have no 
function. Switch settings are listed in Tables 6 or 9 (pages 
20 & 22). note: For B7EM Models,

 

the minimum electric 

heat airflow setting may be set higher, but must never be 
set lower than the setting shown in Table 6 (page 18).

Determining Nominal System Capacity
To select the appropriate airflows for the air handler, the 
nominal system capacity must be known. The nominal 
system capacity is always the nominal capacity of the 
outdoor unit. However, in some situations the nominal 
system capacity may not be the same as the nominal 
capacity of the air handler. Always refer to the nominal 
capacity of the outdoor unit to determine the nominal 
system capacity.

note: The CFM values listed in Table 8 (page 19) are 
not dependent on duct static pressure. The VSHE motor 
automatically compensates for changes in duct static 
pressure (within the limits of the motor).

3-Speed Units
The blower speed is preset at the factory for operation 
at the same speed for heating and cooling, by using the 
jumping terminal on the blower motor and connecting it 
to the desired speed with both the red and black wires 
connected to the jumping terminal. note: The control 
board is programmed with a 40 second off delay in the 
cooling mode for optimum system performance and 
efficiency.

 caution:

to avoid personal injury or property damage, 
make sure the motor leads do not come into 
contact with any uninsulated metal components 
of the unit.

For optimum system performance and comfort, it may be 
necessary to change the factory set speed. See Table 4 
(page 16) for airflow data. To change the blower speed:
1. Disconnect all electrical power to the unit and remove 

the upper door.

2. Remove the black and red wires from the blower motor 

jumping terminal. Discard the blower motor jumping 
terminal.

StartuP & adjuStMentS

Before You Start the air Handler
Prior to start-up, complete the following inspections:

  Verify the unit is level and properly located with adequate 

clearances for servicing the unit. See Table 1 (page 4).

 Check condensate drain line(s) for proper drainage.

 Verify the surrounding area and top of the unit is free 

from obstructions and debris.

 Check all duct connections. Make sure the duct work 

is adequately sealed to prevent air leakage.

 Check all coil connections for leaks.

 Verify that the line voltage power leads are securely 

connected and the unit is properly grounded. Make sure 
all doors are installed before restoring power to the unit

  Verify the thermostat is wired correctly. Make sure all 

low voltage wires are securely connected.

 Verify the power supply branch circuit overcurrent 

protection is sized properly.

 Verify filter is properly and securely installed.

air circulation check
Running the Blower Continuously
Set the thermostat’s system mode to oFF and the 
thermostat’s fan mode to on. The blower motor should 
run continuously. Check for air delivery at the register(s). 
Make sure that there are no obstructions at the registers 
or in the ducts.

System Cooling
1. Set the thermostat’s system mode to cool and fan 

mode to auto. Lower the thermostat’s temperature 
mode below room temperature and observe that the 
blower energizes. Check the air being discharged at 
the register is cooler than room temperature. Verify 
unit refrigerant pressures are in order. Blower should 
be turning in direction indicated by arrow.

 note: DO NOT alter unit wiring. Listen for any unusual 

noises. Locate the source and correct as needed.

2. Allow the unit to run for several minutes and then set 

the thermostat’s temperature above room temperature. 
Verify the blower cycles off with the thermostat.

System Heating
1. Set the thermostat’s system mode to Heat and the fan 

mode to auto. Increase the thermostat’s temperature 
above room temperature and observe that the blower 
energizes. Check the air being discharged at the register 
is warmer than room temperature.

2. Allow the unit to run for several minutes and then set 

the thermostat’s temperature below room temperature. 
Verify the blower cycles off with the thermostat.

Turning the Blower Off
Set thermostat’s fan mode to auto, the blower will shut 
down immediately.

Summary of Contents for MB7BM Series

Page 1: ...nt role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in ser...

Page 2: ...ing 11 Turning the Blower Off 11 Blower Configurations 11 Selecting minimum Electric Heat Airflow 11 Determining Nominal System Capacity 11 3 speed Units 11 High Efficiency Units 12 Selecting Basic He...

Page 3: ...ment Do not store any of the following on or in contact with the unit Rags brooms vacuum cleaners or other cleaning tools spray or aerosol cans soap powders bleaches waxes cleaning compounds plastics...

Page 4: ...dbesetintopositionbeforerouting the refrigerant tubing Operation of an Air Handler During Construction CAUTION Failure to follow these instructions will void the factory warranty and may significantly...

Page 5: ...tments must be constructed and installed in accordance with NFPA and SMACNA construction standards Consult with local codes for special requirements For best sound performance be sure to install all t...

Page 6: ...nts air handler INSTALLATION The MB7 Series air handler is shipped ready for vertical upflow installation and is approved for attic basement alcove closetorcrawlspaceinstallationwithzeroclearance to c...

Page 7: ...ne gasket tape to the top of the air handler NOTE The blowers flanged surface is now beneath the air handler and will connect with the supply air duct 4 Carefully place the cased coil on top of the mo...

Page 8: ...ion of the unit in a suspended horizontal application is shown in Figure 5 When mating the blower and coil for horizontal left or right applications reference the upflow instructions on page 6 Make su...

Page 9: ...gures 14 16 Use only copper wire for the line voltage power supply to this unit Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit Aluminum suppl...

Page 10: ...erkitforyour unit by referring to the list below or the units rating label A Size Cabinet 15Kw max B Size Cabinet 20Kw max C Size Cabinet 20Kw max 1 Connect the 2 wire plug of the air handler to the m...

Page 11: ...Disconnect all electrical power to the unit and remove the upper door 2 Remove the black and red wires from the blower motor jumping terminal Discard the blower motor jumping terminal Startup Adjustme...

Page 12: ...ch nominal system capacity When operating in the heat pump mode a higher basic airflow setting will increase the energy efficiency and capacitybutwillalsodecreasethesupplyairtemperature For maximum ca...

Page 13: ...eate excessive loads on the motor resulting in higher than normal operating temperatures and shortened service life It is recommended that the blower compartment be cleaned of dirt or lint that may ha...

Page 14: ...mension B Dimension C A 12 3 4 24 3 4 14 1 4 B 12 3 4 24 3 4 17 1 2 C 18 1 4 27 1 2 21 B A 12 7 8 3 4 TYP 1 3 4 1 7 8 K O 3 1 4 1 1 4 C 22 1 1 7 8 3 1 2 5 1 2 2 5 8 1 1 8 K O TYP 1 1 4 2 7 8 TOP VIEW...

Page 15: ...ount Kit Blower Motor Blower Wheel Blower Housing Transformer Control Board Coil Assembly Outlet Heater Box Lower Front Bracket Blower Door Motor Control Board Rear Bracket Front Joining Bracket Figur...

Page 16: ...0 845 780 705 610 530 Corrected ESP1 0 08 0 19 0 31 0 42 0 54 0 65 0 76 Med 1335 1290 1235 1175 1100 1015 925 805 Corrected ESP1 0 10 0 22 0 34 0 46 0 59 0 71 High 1470 1425 1360 1300 1225 1135 1050 9...

Page 17: ...685 0 1 1 0 1095 1040 995 950 900 850 805 750 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0 1 1330 12...

Page 18: ...0 1 0 650 0 0 1 1 2 TON 1300 0 0 1 1 4 TON 700 0 1 0 0 1350 0 1 0 0 750 0 1 0 1 1400 0 1 0 1 800 0 1 1 0 2 5 TON 1450 0 1 1 0 850 0 1 1 1 1500 0 1 1 1 875 1 0 0 0 1550 1 0 0 0 950 1 0 0 1 1600 1 0 0 1...

Page 19: ...0 1 0 0 700 1 15 1300 1 0 1 0 1 750 1 20 1500 1 0 1 1 0 800 1 25 N A 1 0 1 1 1 850 1 30 N A 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 1400 1 1 1...

Page 20: ...1 7 68 1 50 25 70 020H XX 53 1 103 1 60 110 46 5 43 3 89 8 50 45 90 C 2000CFM None 5 5 15 15 5 5 15 15 005H XX 30 30 35 35 26 7 26 7 30 30 008H XX 44 6 44 6 45 45 39 3 39 3 40 40 010H XX 55 55 60 60 4...

Page 21: ...Thermostat Y1 C Y1 W2 Typical 2 Stage Air Conditioner with Variable Speed Air Handler Typical 2 Stage Heat Pump with Variable Speed Air Handler Y2 Y2 Y2 Y2 OUT W E R Air Conditioner Air Handler Air C...

Page 22: ...age Control Board MB7BM Models Figure 11 Two Stage Control Board MB7EM VM Models LED 1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2...

Page 23: ...W C EXPANSION PORT R RED GREEN TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTPUTS STATUS LIGHTS 2 3 4 5 6 7 8 OFF ON A B GREEN RED STATUS NOT USED TEST PORT BLOWER MOTOR R C Y1 TWIN DEHUM...

Page 24: ...PLUG HOUSING WHEN HEATER KIT NOT INSTALLED BLACK RED WHITE BROWN BROWN BLACK WHITE RED GRAY YELLOW WHITE GREEN GRAY RED NOTES 1 The blower motor speed tap connection may not be as shown See the Insta...

Page 25: ...2 3 4 5 6 9 PIN HOUSING 9 PIN PLUG 6 PIN PLUG HARNESS BLACK WHITE GRAY RED BLACK RED WHITE BLACK MOTOR 6 PIN PLUG HARNESS WHITE BLACK BLUE GREEN YELLOW ORANGE RED BROWN BLUE GREEN ORANGE RED BROWN YE...

Page 26: ...R BLACK WHITE 6 PIN PLUG 6 PIN PLUG BLACK WHITE BLACK WHITE GRAY RED BLACK HARNESS HARNESS GREEN BROWN RED ORANGE YELLOW GREEN BLUE BROWN RED ORANGE YELLOW GREEN BLUE RED CUT WIRES TO REMOVE PLUG HOU...

Page 27: ...delay W Y AUX HEAT On 5 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 10 KW Stage 1 Heat on instantly Cool blower on after 3 second delay Stage 2 Heat on after 5 seconds delay 15 KW...

Page 28: ...ly Blower off after 15 second delay W1 W2 EHEAT On 5 KW Stage 1 Heat on instantly Heat blower on after 3 second delay 10 KW Stage 1 Heat on instantly Heat blower on after 3 second delay Stage 2 Heat o...

Page 29: ...off instantly Heat blower turns off after 40 second delay W1 W2 Y Y2 AUX HEAT On 5 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 10 KW Stage 1 Heat on instantly Cool blower on afte...

Page 30: ...30...

Page 31: ...31...

Page 32: ...Replaces 7091750 ATTENTION INSTALLERS It is your responsibility to know this product better than your customer This includes being able to install the product according to strict safety guidelines and...

Reviews: