29
control SiGnal & Mode
oPeration
total KW
Board action
W1 & Y/Y2
AUX HEAT
ON
5 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
10 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
15 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
20 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
OFF
Heat stages off instantly
Heat blower turns off after 40 second delay
W1, W2 & Y/Y2
AUX HEAT
ON
5 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
10 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
15 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 30 seconds delay
20 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
OFF
Heat stages off instantly
Heat blower turns off after 40 second delay
table 11. continued