background image

15

!

 WARNING:

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly
could result in serious injury, death or
property damage.

Never test for gas leaks with an open
flame. Use a commercially available soap
solution made specifically for the detection
of leaks to check all connections. A fire or
explosion may result causing property
damage, personal injury or loss of life.

Conversion
Conversion of this furnace to use LP/propane
gas must be made by qualified service
personnel, using only  approved parts.

!

 WARNING:

This furnace was equipped at the factory
for use with natural gas only.  A special
kit, supplied by the manufacturer, is
required to convert the furnace to operate
on LP/propane  gas.  Failure to use the
proper conversion kit can cause fire,
explosion, property damage, carbon
monoxide poisoning, personal injury, or
death.

HIGH ALTITUDE CONVERSION

High Altitude Application

Conversion of this furnace to replace the pressure
switch or to utilize LP/propane gas must be made
by qualified service personnel, using factory
authorized or approved parts. High altitude
application with this furnace can be field performed
by a simple adjustment of manifold pressure, and
if necessary changing the orifices and the pressure
switch. The changes required depend on the
installation altitude and the heating value of the
gas. The gas heating value based on sea level can
be obtained from your  local gas utility. The heating
value of gas at high altitude is always lower than
the sea level heating value. The heating values
used in Tables 5 & 6 are based on sea level values.

Pressure Switch Conversion for High
Altitude Applications
The pressure switch is factory equipped to oper-
ate between zero and 5000 feet above sea level.
For higher altitude applications, you may need to

replace the pressure switch. The approved high
altitude pressure switch kit is 903853.  The
directions to convert the furnace are given below:

1. READ ALL INSTRUCTIONS BEFORE

PROCEEDING WITH THE CONVERSION.

2. Disconnect all electrical power to the

furnace.

3. Remove the access door(s) from the front

of the unit.

4. Turn the gas valve knob to the OFF position.
5. Shut off the gas to the unit.
6. Disconnect the electrical leads to the

pressure switch (see Figure 14). It is not
necessary to mark the leads as polarity
does not matter across the switch.

7. Remove the hose from the pressure switch

and remove the fasteners that secure the
pressure switch to the burner box.

8. Discard the old pressure switch.
9. From the kit, install the new high altitude

pressure switch using the same fasteners
that were removed above.

10. Reattach the hose to the pressure switch

port in the same manner as it was removed.

11. Reattach the electrical leads to the

pressure switch.

12. Turn on the electrical power to the furnace.
13. Turn the gas valve knob to the ON position.
14. Follow the start-up procedure outlined later

in these installation instructions.  Verify that
the furnace is operating properly after the
conversion.

Natural Gas High Altitude Conversion

All factory shipped furnaces  are ready to operate
up to 4999 ft. above sea level.  For higher
altitudes (between 5000 and 10,000 ft. above
sea level), conversion can be achieved simply
by adjusting the furnace manifold pressure as
shown in Table 5.

LP/Propane Gas Sea Level and High
Altitude Conversion

IMPORTANT NOTE:

When converting a low NOx Furnace from
Natural gas to LP/Propane gas, it is necessary
to remove the NOx Baffles.

Conversion to LP/propane gas can be
accomplished by first replacing the natural gas
orifices with the appropriate LP/propane orifices
shown in Table 7 or 8.  Note: for installations
between zero and 5000 ft., refer to Table 7. For
installations above 5000 ft. above sea level,
refer to Table 8. After changing the orifices, use
Table 6 to determine the appropriate manifold
pressure for your installation.

Summary of Contents for RA 80+ series

Page 1: ...property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Donottrytolightan...

Page 2: ...ication 15 Pressure Switch Conversion for High Altitude Applications 15 Natural Gas High Altitude Conversion 15 LP Propane Gas Sea Level and High Altitude Conversion 15 Electrical Wiring 16 General 16...

Page 3: ...s as specified on Page 14 of these instructions 6 Always install furnace to operate within the furnace s intended temperature rise range with a duct system which has an external static pressure within...

Page 4: ...52 1240 54 1175 57 1210 55 1195 55 1180 56 1160 57 1135 59 1100 60 1060 63 1010 66 2375 28 2320 29 2280 30 2215 30 2150 31 2085 32 2015 33 1940 34 1975 33 1955 34 1920 35 1895 35 1850 36 1800 37 1740...

Page 5: ...acetobemovedtotheinstallation point The furnace must be installed so that all electrical components are protected from water The furnace must be installed upstream from a refrigeration system This fur...

Page 6: ...a Platform Upflow and Horizontal Furnaces UPFLOWAPPLICATION RIGHT SIDE BOTTOM TOP LEFT SIDE TOP BOTTOM SIDE SIDE HORIZONTAL APPLICATION Allow 24 minimum clearance for servicing Therecommendedclearanc...

Page 7: ...forB ventusethe recommended clearance Do not place combustiblematerials includinggasoline and any other flammable vapors and liquids in the vicinity of the furnace requirements ForCanadianinstallatio...

Page 8: ...y to provide outside air to ensure adequate combustion and venting even though the furnace is located in an unconfined space Installation In A Confined Space A confined space is an area with volume le...

Page 9: ...per 2 000 Btuh of total appliance input If the unit is installed in an area with an exhaust fan provide sufficient ventilation to prevent negative pressures from occurring in the room The combustion...

Page 10: ...icalstorage areas Exposure to the following substances in the combustion air supply may also require Outdoor Air for combustion Permanent wave solutions Chlorinated waxes and cleaners Chlorine based s...

Page 11: ...A B149 1 Natural Gas and Propane Installation Codes and these instructions Determine that there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condi...

Page 12: ...irculatedintotheliving space and create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death The return air ductwork may be connected to a...

Page 13: ...ce must be properly labeled by the installer in case emergency shutdown is required Leak Check After the gas piping to the furnace is complete all connections must be tested for gas leaks To check for...

Page 14: ...to 10000 Manifold Pressure Setting in WC 3 5 3 5 3 5 3 5 3 0 For a Natural Gas Sea Level Heating Value of 900 to 999 Btu cu ft Elevation feet above sea level zero to 1999 2000 to 4999 5000 to 5999 600...

Page 15: ...witch kit is 903853 The directions to convert the furnace are given below 1 READ ALL INSTRUCTIONS BEFORE PROCEEDING WITH THE CONVERSION 2 Disconnect all electrical power to the furnace 3 Remove the ac...

Page 16: ...o the furnace must be suppliedfromadedicatedbranchcircuitcontaining the correct fuse or circuit breaker for the furnace See Table 9 An electrical disconnect must be installedtobereadilyaccessiblefroma...

Page 17: ...board must be connected to the thermostat for proper cooling mode operation COOL Figure 10 Line Voltage Field Wiring Field Supplied Disconnect Within Sight of Furnace Field Supplied Panel Connector F...

Page 18: ...in water column 0 36 psig and is not less than 4 5 in water column 0 16 psig for natural gas For LP gas the line service pressure must not exceed 14 in water column 0 51 psig and must not be less than...

Page 19: ...ow room temperature and verify steps 9 through 11 of the Sequence of Operation Verifying and Adjusting Firing Rate The firing rate must be verified for each installation to prevent over firing the fur...

Page 20: ...Factory Wiring Low Voltage High Voltage Power On Limit Circuit Open or External Load On W Pressure Switch is Open with Inducer On Pressure Switch is Closed with Inducer Off Ignition Failure Check Gro...

Page 21: ...t systems the temperature rise will fall within the range specified on the rating plate with the blower speed at the factory recommended setting If the temperature rise measured is outside the range s...

Page 22: ...Exhaust Adapter 9 Low Voltage Transformer 10 Burner Assembly 11 Supply Air Limit Switch 12 Blower Assembly 13 Induced Draft Blower 14 Vent Transition 1 Igniter 2 Flame Sensor Not Shown 3 Gas Valve 4 F...

Page 23: ...rove that flame has carried over from the igniter to the opposite end burner If no flame is sensed the furnace will shut down within 7 seconds Flame Roll Out Switch The flame roll out switch verifies...

Page 24: ...s are found Failure to prevent products of combustion from being circulated into the living space can create potentially hazardousconditionsincludingcarbon monoxidepoisoningthatcouldresultin personal...

Page 25: ...the wires from the gas valve igniter and flame sensor 6 Using wrenches separate the ground joint union in the gas supply piping at the furnace 7 Remove the piping between the gas valve and the ground...

Page 26: ...xed at this level In general whenever ignition failure occurs the warm up interval is increased by 3 seconds on the next try And if successful it remains there Minimum and maximum warm up time limits...

Page 27: ...or plugged 8 Is the flame sensor coated Remove and clean with steel wool If the furnace locks out after 5 attempts for ignition it will try again every hour if a call for heat remains If the inducer a...

Page 28: ...s Piping Connections leak tested ______________________ Gas Line Pressure __________________ in water column with furnace operating Manifold Pressure __________________ in water column with furnace op...

Reviews: