background image

25

brush attached to a length of high grade
stainless steel cable, such as drain
cleanout cable. Attach variable speed
reversible drill to the other end of the spring
cable. Slowly rotate the cable with the drill
and insert it into  the top portion of the heat
exchanger. While reversing the drill, work
the cable in and out several times to obtain
sufficient cleaning. Repeat this sequence
for each heat exchanger tubes.

14. When all heat exchanger tubes have been

cleaned, any debris inside the  tubes can be
removed with the nozzle of a vacuum
cleaner.

15. With a light, check the condition of the

upper and lower sections of the heat
exchanger tube.

16. Inspect the burners and clean them (if

necessary) with a soft wire brush and/or
the nozzle of a vacuum cleaner.  BE
EXTREMELY CAREFUL NOT TO
DAMAGE THE IGNITER WHILE
CLEANING THE BURNER.

17. Replace all the parts in reverse order from

which they were removed.

18. Follow the lighting instructions found on

the  furnace door to return the furnace to
operation. Verify proper operation after
servicing.

Cleaning of Burners
 If the burners must be cleaned, follow the steps
below.  See Figure 14  for component location
and identification.

1.

Shut off the gas supply to the furnace
either at the meter or at a manual  valve in
the supply piping.

2.

Turn off all power to the furnace and set the
thermostat to the lowest  temperature
setting.

3.

Remove the upper louvered door from the
furnace.

4.

Turn the gas control lever to the OFF
position.

5.

Disconnect the wires from the gas valve,
igniter, and flame sensor.

6.

Using wrenches, separate the ground-

joint union in the gas supply piping at the
furnace.

7.

Remove the piping between the gas valve
and the ground-joint union, if  necessary.

8.

Remove the screws that hold the burner
assembly in place and remove  the burner
assembly.  BE EXTREMELY CAREFUL
NOT TO DAMAGE THE IGNITER WHILE
REMOVING THE BURNER ASSEMBLY.

9.

Inspect the burners and clean them (if
necessary) with a soft wire brush and/or
the nozzle of a vacuum cleaner.  BE
EXTREMELY CAREFUL NOT TO
DAMAGE THE IGNITER WHILE
CLEANING THE BURNER.

10. Replace all the parts in reverse order from

which they were removed.

11. Follow the lighting instructions found on

the  furnace door to return the furnace to
operation. Verify proper operation after
servicing.

SYSTEM OPERATION INFORMATION

General
Proper maintenance is most important to
achieve the best performance from a furnace.
Follow these instructions for years of safe,
trouble free operation.

1.

Do not place combustible materials on or
against  the  furnace cabinet or within 6
inches of the vent pipe (or for B-vent use
the recommended clearance).

2.

Do not store gasoline or any other flammable
vapors and liquids in the vicinity of the
furnace.

3.

Change or replace the air filters monthly
during any period when the circulating
blower is operating regularly.

4.

Always replace the doors on the furnace
after servicing or cleaning/changing the
filters.  Do not operate the furnace without
all doors and covers in place.

5.

Avoid operating the furnace when windows
and doors are open.

6.

Be sure that the thermostat is properly
installed and is not being  affected by
drafts or heat from lamps or other
appliances.

Summary of Contents for RA 80+ series

Page 1: ...property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Donottrytolightan...

Page 2: ...ication 15 Pressure Switch Conversion for High Altitude Applications 15 Natural Gas High Altitude Conversion 15 LP Propane Gas Sea Level and High Altitude Conversion 15 Electrical Wiring 16 General 16...

Page 3: ...s as specified on Page 14 of these instructions 6 Always install furnace to operate within the furnace s intended temperature rise range with a duct system which has an external static pressure within...

Page 4: ...52 1240 54 1175 57 1210 55 1195 55 1180 56 1160 57 1135 59 1100 60 1060 63 1010 66 2375 28 2320 29 2280 30 2215 30 2150 31 2085 32 2015 33 1940 34 1975 33 1955 34 1920 35 1895 35 1850 36 1800 37 1740...

Page 5: ...acetobemovedtotheinstallation point The furnace must be installed so that all electrical components are protected from water The furnace must be installed upstream from a refrigeration system This fur...

Page 6: ...a Platform Upflow and Horizontal Furnaces UPFLOWAPPLICATION RIGHT SIDE BOTTOM TOP LEFT SIDE TOP BOTTOM SIDE SIDE HORIZONTAL APPLICATION Allow 24 minimum clearance for servicing Therecommendedclearanc...

Page 7: ...forB ventusethe recommended clearance Do not place combustiblematerials includinggasoline and any other flammable vapors and liquids in the vicinity of the furnace requirements ForCanadianinstallatio...

Page 8: ...y to provide outside air to ensure adequate combustion and venting even though the furnace is located in an unconfined space Installation In A Confined Space A confined space is an area with volume le...

Page 9: ...per 2 000 Btuh of total appliance input If the unit is installed in an area with an exhaust fan provide sufficient ventilation to prevent negative pressures from occurring in the room The combustion...

Page 10: ...icalstorage areas Exposure to the following substances in the combustion air supply may also require Outdoor Air for combustion Permanent wave solutions Chlorinated waxes and cleaners Chlorine based s...

Page 11: ...A B149 1 Natural Gas and Propane Installation Codes and these instructions Determine that there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condi...

Page 12: ...irculatedintotheliving space and create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death The return air ductwork may be connected to a...

Page 13: ...ce must be properly labeled by the installer in case emergency shutdown is required Leak Check After the gas piping to the furnace is complete all connections must be tested for gas leaks To check for...

Page 14: ...to 10000 Manifold Pressure Setting in WC 3 5 3 5 3 5 3 5 3 0 For a Natural Gas Sea Level Heating Value of 900 to 999 Btu cu ft Elevation feet above sea level zero to 1999 2000 to 4999 5000 to 5999 600...

Page 15: ...witch kit is 903853 The directions to convert the furnace are given below 1 READ ALL INSTRUCTIONS BEFORE PROCEEDING WITH THE CONVERSION 2 Disconnect all electrical power to the furnace 3 Remove the ac...

Page 16: ...o the furnace must be suppliedfromadedicatedbranchcircuitcontaining the correct fuse or circuit breaker for the furnace See Table 9 An electrical disconnect must be installedtobereadilyaccessiblefroma...

Page 17: ...board must be connected to the thermostat for proper cooling mode operation COOL Figure 10 Line Voltage Field Wiring Field Supplied Disconnect Within Sight of Furnace Field Supplied Panel Connector F...

Page 18: ...in water column 0 36 psig and is not less than 4 5 in water column 0 16 psig for natural gas For LP gas the line service pressure must not exceed 14 in water column 0 51 psig and must not be less than...

Page 19: ...ow room temperature and verify steps 9 through 11 of the Sequence of Operation Verifying and Adjusting Firing Rate The firing rate must be verified for each installation to prevent over firing the fur...

Page 20: ...Factory Wiring Low Voltage High Voltage Power On Limit Circuit Open or External Load On W Pressure Switch is Open with Inducer On Pressure Switch is Closed with Inducer Off Ignition Failure Check Gro...

Page 21: ...t systems the temperature rise will fall within the range specified on the rating plate with the blower speed at the factory recommended setting If the temperature rise measured is outside the range s...

Page 22: ...Exhaust Adapter 9 Low Voltage Transformer 10 Burner Assembly 11 Supply Air Limit Switch 12 Blower Assembly 13 Induced Draft Blower 14 Vent Transition 1 Igniter 2 Flame Sensor Not Shown 3 Gas Valve 4 F...

Page 23: ...rove that flame has carried over from the igniter to the opposite end burner If no flame is sensed the furnace will shut down within 7 seconds Flame Roll Out Switch The flame roll out switch verifies...

Page 24: ...s are found Failure to prevent products of combustion from being circulated into the living space can create potentially hazardousconditionsincludingcarbon monoxidepoisoningthatcouldresultin personal...

Page 25: ...the wires from the gas valve igniter and flame sensor 6 Using wrenches separate the ground joint union in the gas supply piping at the furnace 7 Remove the piping between the gas valve and the ground...

Page 26: ...xed at this level In general whenever ignition failure occurs the warm up interval is increased by 3 seconds on the next try And if successful it remains there Minimum and maximum warm up time limits...

Page 27: ...or plugged 8 Is the flame sensor coated Remove and clean with steel wool If the furnace locks out after 5 attempts for ignition it will try again every hour if a call for heat remains If the inducer a...

Page 28: ...s Piping Connections leak tested ______________________ Gas Line Pressure __________________ in water column with furnace operating Manifold Pressure __________________ in water column with furnace op...

Reviews: