background image

6

Location

The furnace must be installed on a level surface, 
and as close to the center of the air distribution 
system as possible. See Table 1 for overall di-
mensions to determine the required clearances 
in hallways, doorways, stairs, etc. to allow the 
furnace to be moved to the installation point. The 
furnace must be installed so that all electrical 
components are protected from water.

Minimum clearances to combustible materials 
are listed in Table 2. Access for positioning and 
servicing must be considered when locating the 
unit.  24 inches is the minimum required clearance 
for servicing the unit. 30 inches is the minimum 
required clearance for positioning the unit.  36 
inches is the recommended clearance from the 
front of the unit. Please note that a panel or door 
can be located such that the minimum clearance 
on the rating plate is satisfi ed, but that panel or 
door must be removable so as to allow the ap-
propriate clearance.

This furnace is certifi ed for use on wood fl ooring. 
The furnace must be installed on a solid surface 
and must be level front to back and side to side. 
This furnace must not be installed directly on 
carpeting, tile, or any combustible material other 
than wood fl ooring.

A gas-fi red furnace installed in a residential 
garage must be installed so that the bottom of 
the burners and igniter are located a minimum 
of 18” from the fl oor. The furnace must be lo-
cated or protected to avoid physical damage 
by vehicles.

HORIZONTAL INSTALLATIONS

The upfl ow model furnaces are approved for 
horizontal installation. Installation Kit #903568 
is available for horizontal applications. The 
parts may also be fi eld supplied. The parts that 
are fi eld supplied should conform to Figures 2 
and 3.

 CAUTION:

Damage to the product resulting 
from failure to follow instructions or 
use of unauthorized parts may void 
the manufacturer’s product warranty 
coverage.

The 90+ upfl ow furnace can be installed hori-
zontally in an attic, basement, crawl space or 
alcove. This furnace can be installed horizontally 
to the clearances listed in Table 6 on a platform 
or on the ceiling rafters. Note that the platform 
and the ceiling rafters must be able to support 
the weight of the furnace being installed. It can 
also be suspended from a ceiling in a basement 
or utility room in either a right to left airfl ow or 
left to right airfl ow.

When installed horizontally, the furnace must 
be raised above the surface to allow a drain 
trap to hang vertically below the furnace.  This 
will allow for proper drainage of the condensate 
from the furnace.

Conversion of the iQ Drive Upfl ow Furnace 
for a Horizontal Right Installation.

Refer to Figure 2.

1.  Remove the hard “J” tube drain trap as-

sembly.

2.  Place the 5/8” cap plug over the drain trap 

in the header box from which the “J” drain 
trap assembly was removed.

3.  Remove the piece of soft tubing running 

from the in-line drain assembly to the header 
box and place a ½” vinyl cap over the drain 
tap in the in-line drain assembly.

4.  Remove the gray tubing from the pressure 

tap on the header box. Remove the ¼” cap 
from the pressure tap on the right side of 
the header box and place it on the corre-
sponding pressure tap on the opposite of 
the header box.

5.  Place the gray tubing that was removed, 

to the corresponding pressure tap on the 
right side of the header box. (Refer to Figure 
2)

6.   If fi eld supplied parts are used, disconnect 

both soft tubes from the hard “J” tube drain 
trap after loosing 7/8” clamps. Shorten long 
side of the “J” trap by 8-1/2”. 

3.  A Product-approved vent terminal must 

be used, and if applicable, a Product-
approved air intake must be used. In-
stallation shall be in strict compliance 
with the manufacturer’s instructions. A 
copy of the installation instructions shall 
remain with the appliance or equipment 
at the completion of the installation.

Summary of Contents for TE Series 95

Page 1: ...or maintenance can cause injury or property damage Refer to this manual for assistance For additional information consult a qualified installer service agency or the gas supplier FOR YOUR SAFETY Do n...

Page 2: ...ort 15 Location of Outdoor Terminations 18 Horizontal Venting 18 Vertical Venting 19 Vent Freezing Protection 19 Concentric Vent Termination 20 Drainage of Condensate From Furnace 20 Gas Supply and Pi...

Page 3: ...s A B Combustion Air Vent 3 See Fig 15 for sizes 1 1 2 x 3 1 2 Dia Opening for Gas Connection 3 4 3 4 3 4 22 1 2 Exhaust Vent Combustion Air Inlet 1 1 2 x 3 1 2 Dia Opening for Gas Connection C 2 PVC...

Page 4: ...these instructions 10 The furnace is not to be used for temporary heating of buildings or structures under construction INSTALLATION REQUIREMENTS Requirements and Codes Thisfurnacemustbeinstalledinacc...

Page 5: ...oratory as recognized under 527 CMR 3 A Product approved vent terminal must be used and if applicable a Product approved air intake must be used In stallation shall be in strict compliance with the ma...

Page 6: ...use of unauthorized parts may void the manufacturer s product warranty coverage The 90 upflow furnace can be installed hori zontally in an attic basement crawl space or alcove This furnace can be inst...

Page 7: ...Tee Soft Tubing Looped to Provide a Drain Trap 3 to 2 Reducer Optional Drainage Port is Downward Reducer Bushing Alternative for Horizontal Vent Pressure Switch Pressure Switch Condensate Vinyl Cap Fi...

Page 8: ...be connected to any other heat producing device such as a fireplace insert stove etc CIRCULATING AIR SUPPLY Plenums and air ducts must be installed in ac cordance with the Standard for the Installatio...

Page 9: ...taminated with various household chemicals which can cause severe corrosion in the furnace combus tion system NOTE If the furnace is operated without ad equate air for combustion and ventilation it ma...

Page 10: ...y involves installation in a small room All such installations must have specific provisions for introduction of combustion and ventilation air Codes require that two openings be provided for this one...

Page 11: ...oved for use with these condensing furnaces Table 3 Vent Table table provided in this section applies to the total of vent and combustion air piping for either type of installation These condensing fu...

Page 12: ...Air Duct must be at least 1 sq in per 4 000 Btuh of total input rating Ducts must extend above attic insulation Air Duct must be at least 1 sq in per 4 000 Btuh of total input rating Ventilation Louve...

Page 13: ...ilding 4 Follow the lighting instructions Place the appliance being inspected in operation Adjust thermostat so appliance shall operate continuously 5 Turn on clothes dryers and any other appliance no...

Page 14: ...ion requires breakable connec tions in the piping Note that a maximum of two couplings per pipe are allowed Upflow Furnaces Combustion Air Pipe Exhaust Vent Cabinet 5 Support System on Vertical Rise B...

Page 15: ...longradiuselbow Therefore forour example we have three additional long radius elbowsforwhichwemustaddtoourpiping Each long radius elbow is equivalent to 2 5 feet so we must add 7 5 feet to our vent le...

Page 16: ...000 Btuh 3 kW and 100 00 Btuh 30 kW 6 inches 15 cm for appliances 10 000 Btuh 3 kW 9 inches 23 cm for appliances 10 000 Btuh 3 kW and 50 000 Btuh 15 kW C Clearance to permanently closed window D Vert...

Page 17: ...other appliance 6 inches 15 cm for appliances 10 000 Btuh 3 kW 12 inches 30 cm for appliances 10 000 Btuh 3 kW and 100 00 Btuh 30 kW 36 inches 91 cm for appliances 100 00 Btuh 30 kW 4 feet 1 2 m belo...

Page 18: ...eCanadianFuelGasCodetakes precedence over these instructions Specifi cally allminimumdistancerequirementswith respecttoterminationoftheventpipinglisted below items 1 through 8 The following list is a...

Page 19: ...or pulled through the wall 4 Insure the combustion air inlet pipe for a 2 pipeinstallation hasa90degreetermination elbow as shown in Figures 16 and 17 Note A combustion air intake must be provided wi...

Page 20: ...4 Route the tubing out of the hole located 8 inches up from the bottom furnace The condensate should drain from the plastic collector box location A in Figure 18 as droplets or a small stream If you...

Page 21: ...J Drain Tube Clamp Loosen For Step 1 Retighten for Step 3 Route to floor drain OR Route to condensate pump Keep downward slope Collector Box A Rotate counter clockwise Step 2 Upflow Models the Nationa...

Page 22: ...jury or death Figure 19 Typical Gas Service Connection MANIFOLD PRESSURE ADJUSTMENT Manifold pressures for low and high stages are independently adjustable Adjustment tap locations on the valve are sh...

Page 23: ...500 440 400 370 350 1 1 2 1600 1100 890 760 670 610 560 530 For a Natural Gas Sea Level Heating Value of 800 to 899 Btu cu ft Elevation feet above sea level zero to 1999 2000 to 4999 5000 to 5999 600...

Page 24: ...nace to replace the pressure switch or to utilize LP propane gas must be made by qualified service personnel using factory authorized or approved parts High altitudeapplicationswiththisfurnacecanbefie...

Page 25: ...for the control system to operate correctly Verify that the incoming neutrallineisconnectedtothewhitewireand the incoming hot line is connected to the blackwireinthejunctionbox Thesefurnaces will not...

Page 26: ...ler The thermostat controller must not be installed on an outside wall or any other location where itsoperationmaybeadverselyaffected Adverse effects include radiant loading from fireplaces sunlight o...

Page 27: ...rocedures After all of the above checks have been made 1 Close the disconnect s to provide line volt age to the furnace 2 Setthermostatcontrollerusingtheinstaller s instructions also refer to Table 1...

Page 28: ...alue for instal lation see Table 1 Refer to either Table 6 for natural gas or Table 7 for LP propane gas to verify the manifold pressure setting required for yourparticularinstallation Toadjustthemani...

Page 29: ...f the supply air limit switch make sure that the blower door is in place and that there is power to the furnace Completely block the return airflow to the furnace by install ing a close off plate in p...

Page 30: ...e vent pressure switch reacts to blockage in the vent or combus tion air piping Supply Air Limit Switch The supply air limit switch prevents the air temperature leaving the furnace from exceeding the...

Page 31: ...N TEMP SENSOR SUCTION PRESS SENSOR GREEN BLACK WHITE RED RED EXV 6 WIRE CABLE CABLE WHITE GREEN GREEN BLACK 3 PIN PLUG 6 PIN PLUG WHITE BLACK FURNACE BOARD GREEN RED RED YELLOW GRAY RED YELLOW RED BLU...

Page 32: ...the bearings is required for the life of the motor Condensate Drain Assembly Be sure the condensate lines are free and open i e avoid kinking hoses Also make sure all hose clamps are tight to avoid dr...

Page 33: ...lower Door Switch 10 Vent Safety Switch 11 Low Voltage Transformer 12 Supply Air Limit Switch 3 4 12 18 14 7 9 11 23 5 6 22 10 16 13 15 21 8 17 20 2 1 13 Circulating Air Blower Assembly 14 Induced Dra...

Page 34: ...eignitionfeaturewhich varies the warm up period as follows If igni tion is successful the warm up is reduced by 3 seconds on each subsequent call for heat until ignition failure occurs Upon igni tion...

Page 35: ...ng 1 Is the thermostat operating properly 2 Are the blower compartment door s in place 3 Is the furnace disconnect closed 4 Has the circuit breaker tripped or the control board fuse burned open 5 Is t...

Page 36: ...k tested _______ Gas Line Pressure _____________________ in water column with furnace operating Manifold Pressure ______________________ in water column with furnace operating Is there adequate fresh...

Reviews: