CP6, CP7, or CP8: Series Programmable Controller
Version 1.0
Page 14
Real time defrost schedule. The RTC defrost is enabled on Setup Screen 6 in the Factory Setup
Screens. Selecting the (RTC) will allow for real time based defrosting, instead of run time defrost
when the SYS Option is selected. The system may be programmed for 4 defrost cycles every 24
hour period.
CONFIG 5
Press the ENTER key to move the cursor to the set point data field. Use the Up or Down Arrow
key to toggle between Centigrade and Fahrenheit. When the correct value is displayed press the
ENTER key to enter the set point, the cursor will move to the next data field. Press the ENTER
key to move the cursor to the upper left hand corner and the Up or Down Arrow key to scroll to the
next set point screen or press the MENU key to return to the System Status screen.
Note: If the user changes temperature units, all set points and bands
must be verified in terms of the new unit. If the parameters have
changed, then they must be re-entered.
CONFIG 6
Press the ENTER key to move the cursor to the set point data field. Use the Up or Down Arrow
key to toggle between DISABLED or ENABLED. When the correct value is displayed press the
ENTER key to enter the set point, the cursor will move to the next data field. Press the ENTER
key to move the cursor to the upper left hand corner and the Up or Down Arrow key to scroll to the
next set point screen or press the MENU key to return to the System Status screen.
Communications set-up.
Protocol: NLSUP RS485,NLSUP RS232,MODBUS
Baud Rate: 1200,2400,4800,9600,19200
Ident Number: 0 to 200
System Setup 5
Units>Centigrade
Change set points
To Fahrenheit
System Setup 6
Protocol>
NLSUP RS485
BAUD RATE> 1200
INDENT NUMBER> 000