CP6, CP7, or CP8: Series Programmable Controller
Version 1.0
Page 43
Analog outputs
Maximum number and type
2 x 0/10Vdc optically-isolated outputs (Y1, Y2),
and 2 PWM phase cutting outputs (Y3, Y4), with
5V impulse of programmable duration
Power supply
external 24Vac/Vdc
Precision
1%
Resolution
0.5 %
Analogue outputs Y1 and Y2 settling time (s)
2
Maximum load
1 kW (10mA) for 0/10V and 470. (10mA) for
PWM
Digital outputs
maximum no.
8, 13 on the SMALL, MEDIUM boards
respectively
type
electromechanical relays
Groups
1, 2, 3, 4, 5, 6, 7, 8 (alarm relay) 9, 10, 11, 12,
13
NO Contacts
all with 250Vac varistor protection
Changeover contacts
3 with 250Vac varistor protection on both
contacts
Commutable power and related electrical parameters
2000VA, 250Vac, 8A resistive, 2A FLA, 12A
LRA, according to UL873 (30,000 cycles) 2A
resistive, 2A inductive, cos.=0.4, 2(2) A,
according to EN 60730-1 (100,000 cycles)
SSR outputs
2 in alternative to relays 7 and 8 (SMALL), 4 in
alternative to relays 7, 8, 12 and 13 (MEDIUM);
24Vac/Vdc, Pmax= 10W
Connection to the user terminal
type
asynchronous half duplex, 2 dedicated wires
terminal connector
6 way telephone plug
pLAN connector
removable 3 way connector
driver
CMR 7 V balanced differential (RS485)
Controller plastic case
Can be mounted on DIN rail according to DIN 43880 and EN 50022 standards
Material: technopolymer
Self-extinguishing V0 (according to UL94) and 960°C (according to IEC 695)
Marble test: 125°C
Resistance to creeping current: = 250V
Colour: grey RAL7035
Cooling vent