background image

 

 

2549736-D | 22 July 2014 

 

                                    Introduction |

 3

 

 

 

 

 

 

Table 4: Technical Specification 

Power Supply 

Operating Voltage 

24 V AC/DC ± 10 %, 50…60 Hz 

Power Consumption 

Max. 1.5 VA 

Electrical Connection 

Terminal Connectors,  
wire: AWG 24…12

 

Internal rectification:  
Signal ground = power ground 

Half wave rectified  
Isolation transformer required 

Signal Inputs 

Humidity Input:  
Range 
Accuracy 
 
Hysteresis 

Element: Polymer-Based Capacity Sensor 
0…100% r.H.  
10%...90% r.H. 

 5.0% 

0…10% and 90…100% 

 7.0% 

±1% r.H. 

Temperature Input 
Range 

External NTC (P/N: 2520263) 
-40…70°C (-40…158°F) 

Accuracy 

-40…0°C (-40…32°F): 0.5 C 
0…50°C (32…122°F): 0.2 C 
50…70°C (122…158°F): 0.5 C 

Signal Outputs 

Digital Switching Outputs 
Switching type 
AC Switching power 

DO1…DO2 
Relays 
2 x 1.0 A, 24 Vac max. 

Environment 

Operation 
Climatic Conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 
0…50 °C (32…122 °F) 
<95 % r.H. non-condensing 

Transport & Storage 
Climatic Conditions 
Temperature 
Humidity 
Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-25…70 °C (-13…158 °F) 
<95 % r.H. non-condensing 
class 2M2 

Standards 

Product standards 
Automatic electrical controls for household and 
similar use 

EN 60 730 –1 
EN 60 730 – 2 – 9 

Degree of Protection 

IP30 to EN 60 529 

Safety Class 

III (IEC 60536) 

Housing 

Cover, back part 
Mounting Plate 

Polycarbonate PC (UL94 class V-0) 
PTFE coated 1μm pores 

General 

Dimensions (H x W x D):  
Front part: 
Power case: 

 
112 x 73 x 15 mm (4.4” x 2.9” x 0.6”) 
ø 58 x 32 mm (ø 2.3” x 1.3”) 

Weight (including package) 

220g 

Power Failure

 

Upon power-interruption, all parameters and setpoints are memorized in non-volatile memory and therefore do not have to be re-entered again. 

 

 

Table 5: Error messages and Troubleshooting Guide 

Display 

Cause 

Symptoms 

Corrective Action 

 
Err1 

 
Humidity sensor faulty. The humidity 
sensor is damaged. 
 

 
The LCD screen will report the message 
Err1.  
 

 
Check that the humidity 
sensing element is not loose  

 
Err2 
 

 
External input for temperature setback 
missing or damaged. 

 
The LCD screen will report the message 
Err2.  
 

 
Check that the temperature 
sensor is connected to the 
humidistat. If the sensor is 
connected and the error 
message persists a 
replacement sensor should 
be ordered. 

 
NOTE: If at any time this troubleshooting guide fails to provide the information needed Nortec’s Technical Support Department can be reached at 1-866-
NORTEC-1 to provide assistance. 

 

 