10
Product Overview
2582302_C_EN_1611
Nortec EL
Option
Application
Remote blower pack power
kit
When a remote blower pack is being installed with the humidifier, this option provides a
transformer, fusing, and a terminal block inside the humidifier to provide power to the remote
blower pack. Without this option, a separate 110-120V supply must be provided for the
remote blower pack.
4.5
Accessories
Table 3
shows the list of accessories for the Nortec EL steam humidifier. Contact your Nortec representative
for details. To install and operate the accessories, refer to the instructions supplied with the accessories.
Table 3: Nortec EL Accessories
Accessory
Application
Steam distributor
Steam distribution system for use in an air duct.
SAM-e steam distribution
manifold
Steam distribution system for use in an air duct where reduced absorption distance is re
-
quired.
Blower pack, built-on or
remote
For direct room humidification or use in conditioned spaces without a built-in air distribution
system. The EL Space model has a blower pack mounted directly, the EL RMBP model has
power for a remote-mounted blower pack (blower pack ordered as an accessory).
Digital or analog control
humidistat with either On/Off
or modulating operation
Input device used to meter the output of the humidifier based on the sensed relative humidity.
The humidistat can be installed in the conditioned space that is being humidified, or within
the duct.
Digital RH transducer
Input device used to communicate the relative humidity in a conditioned space or a duct to
the humidifier.
Digital or analog high limit
humidistat with either On/Off
or modulating operation
Input device used to limit the output of the humidifier by either shutting it down or throttling it
down when the humidity in the duct approaches the high limit.
Air proving switch
Input device to ensure that humidification only occurs when air is moving through the duct.
Outdoor temperature sensor
Input device used to communicate the outdoor temperature to the humidistat so that it can
lower the setpoint value during cold weather to prevent condensation on exterior windows/
surfaces.