Installation
2582302_C_EN_1611
Nortec EL
5.8.3.5 Ohmic Humidity Controller (Passive)
If a passive 135-10kΩ ohmic humidity controller is used, connect the signal cable to the terminal points
3", "4" and "6" in the low voltage terminal strip. Refer to
Figure 24 on page 41
and
Figure 30
. The permis
-
sible control signal input values are shown in
Table 8 on page 39
.
The signal cable must lead into the control cabinet through a cable gland or grommet.
IMPORTANT!
When connecting an ohmic humidity controller, jumper JP1 on the driver board
must be set to 10V (so that output of terminal point "6" is 10V), and Signal Type must be set to
"0-10V" in the control software. Refer to the Operation and Maintenance Manual.
Figure 30:
External
1
JP1
10V
24V
LV
8
7
6
5
4
3
2
9
1
Ohmic Humidity Controller Connection
1
Ohmic humidity controller, 135-10kΩ