49
Installation
Nortec EL
2582302_C_EN_1611
5.8.3.6 24V On/Off Humidistat
If a 24V On/Off humidistat is used, connect the signal cable to the terminal points "4" and "6" in the low
voltage terminal strip. Refer to
Figure 24 on page 41
and
Figure 31
.
The signal cable must lead into the control cabinet through a cable gland or grommet.
IMPORTANT!
When connecting a 24V On/Off humidistat, jumper JP1 on the driver board must
be set to 24V (so that terminal point "6" will output 24VDC), and Control Mode must be set to
"On/Off" in the control software. Refer to the Operation and Maintenance Manual.
Figure 31:
External
1
JP1
10V
24V
LV
8
7
6
5
4
3
2
9
1
24V On/Off Humidistat Connection
1 24V On/Off humidistat
5.8.3.7 External On/Off Input
The humidifier can also be controlled by an external On/Off input through connector X11 on the driver
board – refer to
Figure 24 on page 41
.
The signal cable must lead into the control cabinet through a cable gland or grommet
Enable Input must be set to "On" in the control software to use this input signal – refer to the Operation
and Maintenance Manual.