57
Installation
Nortec EL
2582302_C_EN_1611
Table 14: Maximum External Fusing, Nortec EL Space 3-Phase
Model
*
208V/3~
220-240V/3~
380-415V/3~
440-480V/3~
550-600V/3~
Maximum Output (kW)
Maximum Current (A)
Maximum External Disconnect (A)
Maximum Output (kW)
Maximum Current (A)
Maximum External Disconnect (A)
Maximum Output (kW)
Maximum Current (A)
Maximum External Disconnect (A)
Maximum Output (kW)
Maximum Current (A)
Maximum External Disconnect (A)
Maximum Output (kW)
Maximum Current (A)
Maximum External Disconnect (A)
EL Space 005
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
EL Space 010
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
EL Space 020
7.7
21.5
30
7.7
18.6
25
7.7
10.8
15
7.7
9.3
15
7.7
7.4
15
EL Space 030
11.5 31.9
40
11.5 27.6
35
11.5 16.0
20
11.5 13.8
20
11.5 11.0
15
EL Space 050
19.0 52.6
70
19.0 45.6
60
19.0 26.4
35
19.0 22.8
30
19.0 18.2
25
EL Space 075
28.3 78.6
100
28.3 68.1
90
28.3 39.4
50
28.3 34.1
45
28.3 27.2
35
EL Space 100
33.9 94.2
125
37.7 90.6
125
37.7 52.4
70
37.7 45.3
60
37.7 36.2
50
* Space or RMBP (remote blower pack powered by the humidifier) configuration
5.8.6 Electrical Connections Checklist
Check the following to ensure that the electrical connections for the humidifier have been installed correctly:
Power supply meet the voltage and current requirements shown on the specification label (
Figure 3
on page 9
)?
Power supply have an external dedicated fused disconnect?
All wiring done according to the wiring diagram and instructions in this manual?
All cables fastened securely?
All cables free of tension and pass through cable glands or grommets?
Electrical installation meet the applicable national and local codes?
All door panels closed and fastened securely?