6. DO NOT mount humidifier on hot surfaces.
7. DO NOT mount humidifiers in an area where
freezing may occur.
8. DO NOT mount humidifiers on a vibrating surface.
10. DO NOT mount the humidifier to a duct or plenum.
STEAM DISTRIBUTOR NOZZLE (in duct location)
1. When installing the steam distribution nozzle of
the RESDELUX humidifier it must be located in
the supply duct at least 4 feet from any
obstructions such as bends, fans, filters, etc. to
prevent wetting (see figure #4).
2. The steam distribution nozzle can be mounted in
the bottom wall or on the vertical walls of the duct.
If the duct wall is more than 3/4" (20 mm) thick, the
nozzle will have to be mounted from the inside of
the duct. Remove internal insulation material if
necessary. (See Figure #5).
3.
When the steam distribution nozzle is located
above the top surface of the humidifier:
The
nozzle must be at least 1 ft (305 mm) above the
top surface of the humidifier. Locate the steam
hose so that it slopes at an angle of at least 20°
(Figure #6).
4.
Steam distribution nozzle below top surface of
humidifier:
The steam hose must first rise to the
minimum height of 1 ft (305 mm) above the top
surface of the humidifier and thereafter slope a
minimum 5
°
in a uniform manner toward the
nozzle. A separate drain line must be provided for
condensate that collects at the steam distribution
nozzle (Figure #7).
- 2 -
Min. 12”
Figure #4
Steam Distributor Nozzle in Duct Location
Figure #5
Steam Distribution Nozzle Mounting Arrangement
Figure #3
Wall Mounting Detail
Wall
Fasten HumidifierTo
Wall Using Screws 2” long
(2) supplied by other
0.6”
(1.6 cm)
A
12.1” (30.7cm)
NHB, NHP, NHMC,
RESDELUX ONLY
To be 2” (50mm) longer
then duct static pressure
or minimum.
12”
min.
(300
mm)
6” min
(150
mm)
12”
(300
mm)
Rmin
.
12”
(300
mm)
min. 2º
min. 10º
min. 10º
Nortec
Humidifier
Figure #6
Steam Plumbing Arrangement Above Humidifier