3 DAY DRAIN
3 DAY DRAIN FUNCTION
SW3/7
Function Disabled
OFF
Function Enabled (Factory set)
ON
KEEP WARM
3 DAY DRAIN FUNCTION
SW5/7
Function Enabled
ON
Function Disabled (Factory set) - 3 day drain
OFF
MAINTENANCE (GSP)
MAINTENANCE INTERVAL (GSP)
SW3/8
500 hour (Factory set)
OFF
1000 hour
ON
ANALOG CHANNEL 1
Input Range
SW1/1
SW4/1
SW 4/2
0-10V input
OFF
OFF
OFF
0-5V input
OFF
ON
OFF
2-10V input
OFF
OFF
ON
1-5V input
OFF
ON
ON
0-20mA input
ON
OFF
OFF
0-10mA input
ON
ON
OFF
4-20mA input
ON
OFF
ON
2-10mA input
ON
ON
ON
ANALOG CHANNEL 2
Input Range
SW1/2
SW4/1
SW 4/2
0-10V input
OFF
OFF
OFF
0-5V input
OFF
ON
OFF
2-10V input
OFF
OFF
ON
1-5V input
OFF
ON
ON
0-20mA input
ON
OFF
OFF
0-10mA input
ON
ON
OFF
4-20mA input
ON
OFF
ON
2-10mA input
ON
ON
ON
- 39 -