INPUT CHANNEL
DUAL CHANNEL FUNCTION
SW4/5
One Channel Input
OFF
Dual Channel Inputs
ON
TIME PROPORTIONING
TIME PROPORTIONING
SW4/7
Disabled (Factory set)
OFF
Enabled
ON
BLOWDOWN (GSP)
BLOWDOWN
SW5/1
SW 5/2
SW5/3
5%
ON
OFF
OFF
10%
OFF
ON
OFF
15%
ON
ON
OFF
20%
OFF
OFF
ON
25% (Factory set)
ON
OFF
ON
30%
OFF
ON
ON
35%
ON
ON
ON
MAINTENANCE SHUTDOWN
MAINTENANCE SHUTDOWN FUNCTION
SW5/4
Unit will shutdown 72 hours after service time expired, by gen-
erating an error.
OFF
Unit will display warning but continues to operate. (Factory set)
ON
FULL TANK BLOWDOWN
FULL TANK BLOWDOWN FUNCTION
SW5/8
Disabled
OFF
Enabled (Factory set)
ON
- 40 -
Summary of Contents for GS 100
Page 76: ......