| MH Installation Requirements
Control Location
The humidity controls, whether controller or transducer, must be installed in a location which
best represents the space that is being humidified. The preferred location for the humidity
control is in the return air duct.
Figure 27: Control Location
1
Air Proving Switch
Locate so that it can sense air flow or lack of it.
2
Humidity / Temperature Control
MHTC can be Modulating, On/Off, or a Humidity Sensor. MHB can be On/Off.
Can be located either in return air duct (preferred) or in room being humidified / cooled.
Mount in area representative of room humidity / temperature (draft, doorways, sunlight, or
overhang such as a shelf can affect reading). Avoid placing near discharge diffuser of
humidified / cooled air.
Note:
Regardless of selecting on/off or modulating control method, The MH must
have a closed circuit across its On/Off security loop control terminal to operate.
Nortec highly recommends the use of an air proving switch for this function.
Caution:
Failure to wire the MH in accordance with the wiring instructions could cause
permanent damage. Such errors will void the warranty.
1
2
Humidity/
Temperature
Control
(return air
duct or
in room)
Air
Proving
Switch