50
ML Flex - Direct room humidfication
2591584_EN_1706
ML Systems
7.2.2 Inserting the nozzle
WARNING!
Never unscrew a nozzle on a pressurised unit. Disconnect power to the pump station when working
on high-pressure system.
CAUTION!
Be careful! The threads on the nozzles break easily, the nozzle seals with an O-ring and hence
does not need to be tightened very hard, just a little more than you can do by hand.
Before inserting the nozzle, check that its threads and O-ring are intact.
, insert the nozzle into the Flex assembly
• Screw the nozzle in by hand, tighten.
• Use a set of polygrip pliers to tighten the nozzle (approx. 1/8 turn) (torque: 1.5 lbf ft. +/- 0.07 lbf ft.
(2.1 Nm +/- 0.1 Nm))
• Ensure that the nozzle itself is tightened by tightening on the tip of the nozzle.
Figure 23: Inserting the nozzle