After the sensor has been exposed to water and condensation, the sensor requires time during which
the relative humidity is less than 80% in order to measure correctly.
Do not bend the sensor as this would inflict permanent damage on the electronics of the sensor.
Dol-sensors reserve the right to change this document and the product herein described without further
notice.
LED/Light Protocoll
LED
Status
Green
Red
ON
Operation OK
Flash
Outside normal range
(below 10% RH or exceeding 95% RH)
ON
Connection error
Load < 500 Ω
Flash
Sensor defect
Over/under voltage alarm
(below 11 V or exceeding 32 V)
Overload
Output voltage
Figure 49: Mounting
Figure 50: Functional graph
Installation
For optimum mounting of the sensor, use mounting clips or mount it free-hanging in the cable.
The sensor element requires free air passage. See Fig. 1. Mount the sensor so it is not exposed to direct
sunlight, as this would affect the measurement.
REMEMBER TO PUT ON A PROTECTION CAP BEFORE MOUNTING THE CABLE.