10-40
Page 9
2006-09-15
Probable Cause
Corrective Action
1. Is the contactor closed but not energized?
2. Does the processor board display capacity output but
contactor is open?
1. Replace the contactor.
2. Replace the driver board.
1. Back pressure?
2. Organics present in water?
3. Insufficient drain or over concentration.
1. Verify drain is functioning and clean.
2. Verify steam line installation.
3. Check optional inline filter.
1. Back pressure?
2. Organics present in water?
3. Insufficient drain or over concentration.
1. Verify drain is functioning and clean.
2. Verify steam line installation.
3. Check optional inline filter.
The cylinder must be replaced with the same type and
model.
When ordering a new cylinder, quote the model number of
cylinder presently installed in the humidifier or serial
number of humidifier.
The cylinder must be replaced with the same type and
model.
When ordering a new cylinder, quote the model number
presently installed in the humidifier.
1. Is the drain leaking?
2. Adjust drain factor.
3. Check the system backpressure.
4. Is salt required?
1. Clean the drain valve.
2. Set drain factor to 0.7.
3. Install a fill cup extension kit if required.
4. Add one teaspoon of table salt.
1. Is the sensor powered?
2. Is the sensor wiring correct?
3. Is the sensor defective?
4. Is the RH less than 5%?
1. Use a multimeter to check that the sensor is powered.
2. Verify wiring is correct as per wiring instructions.
3. Replace the sensor.
4. RH values under 5% are interpreted as a broken
sensor.
1. Is the sensor powered?
2. Is the sensor wiring correct?
3. Is the sensor defective?
4. Is the RH less than 5%?
1. Use a multimeter to check that the sensor is powered.
2. Verify wiring is correct as per wiring instructions.
3. Replace the sensor.
4. RH values under 5% are interpreted as a broken
sensor.
1. Is the sensor powered?
2. Is the sensor wiring correct?
3. Is the sensor defective?
4. Is the RH less than 5%?
1. Use a multimeter to check that the sensor is powered.
2. Verify wiring is correct as per wiring instructions.
3. Replace the sensor.
4. RH values under 5% are interpreted as a broken
sensor.
1. Is the sensor powered?
2. Is the sensor wiring correct?
3. Is the sensor defective?
4. Is the RH is less than 5%?
1. Use a multimeter to check that the sensor is powered.
2. Verify wiring is correct as per wiring instructions.
3. Replace the sensor.
4. RH values under 5% are interpreted as a broken
sensor.
---
To disable this feature, consult the programming manual
shipped with the humidifier.
---
To disable this feature, consult the programming manual
shipped with the humidifier.
Summary of Contents for NH Series
Page 1: ...Manual No H 101 2006 09 15 NH Series ELECTRODE STEAM HUMIDIFIER Installation Manual TM ...
Page 9: ...10 00 Page 1 2006 09 15 10 00 INTRODUCTION ...
Page 10: ...10 00 Page 2 2006 09 15 Figure 1 NHTC ...
Page 14: ...10 00 Page 6 2006 09 15 Figure 6 Typical NHTC Installation Sheet 1 of 2 ...
Page 15: ...10 00 Page 7 2006 09 15 Figure 6 Typical NHTC Installation Sheet 2 of 2 ...
Page 16: ...10 00 Page 8 2006 09 15 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 17: ...10 10 Page 1 2006 09 15 10 10 INSTALLATION PROCEDURES ...
Page 20: ...10 10 Page 4 2006 09 15 Figure 3 Water Drain and Supply Connection ...
Page 41: ...10 10 Page 25 2006 09 15 Figure 24 Typical SAM e Duct Installation ...
Page 45: ...10 10 Page 29 2006 09 15 Figure 27 Drain Water Cooler Option Installation with SAM e ...
Page 48: ...10 10 Page 32 2006 09 15 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 49: ...10 20 Page 1 2006 09 15 10 20 OPERATION ...
Page 54: ...10 20 Page 6 2006 09 15 Figure 6 Basic Steam Production Method ...
Page 56: ...10 20 Page 8 2006 09 15 Figure 7 Software Flow Chart Sheet 1 of 7 ...
Page 57: ...10 20 Page 9 2006 09 15 Figure 7 Software Flow Chart Sheet 2 of 7 ...
Page 58: ...10 20 Page 10 2006 09 15 Figure 7 Software Flow Chart Sheet 3 of 7 ...
Page 59: ...10 20 Page 11 2006 09 15 Figure 7 Software Flow Chart Sheet 4 of 7 ...
Page 60: ...10 20 Page 12 2006 09 15 Figure 7 Software Flow Chart Sheet 5 of 7 ...
Page 61: ...10 20 Page 13 2006 09 15 Figure 7 Software Flow Chart Sheet 6 of 7 ...
Page 62: ...10 20 Page 14 2006 09 15 Figure 7 Software Flow Chart Sheet 7 of 7 ...
Page 72: ...10 20 Page 24 2006 09 15 Figure 14 NORTEC OnLine Status Page ...
Page 73: ...10 30 Page 1 2006 09 15 10 30 MAINTENANCE PROCEDURES ...
Page 79: ...10 40 Page 1 2006 09 15 10 40 TROUBLESHOOTING ...
Page 91: ...10 50 Page 1 2006 09 15 10 50 TECHNICAL ...
Page 95: ...10 50 Page 5 2006 09 15 Figure 4 NHTC NHPC Wiring Diagram ...
Page 108: ...10 50 Page 18 2006 09 15 THIS PAGE INTENTIONALLY LEFT BLANK ...