background image

InstallatIon GuIde

Page 2

uG_PPR Issue01

Mounting

the reader has been designed to fit into a standard door entry panel with an aperture of 
approximately 40mm x 40mm.  It must be mounted behind a polycarbonate window.  

avoid mounting readers directly beside each other or back to back; we recommend a 
separation of approximately 0.5 metres where possible for best performance. 

the mounting holes of the reader are 48mm apart.  use M3 nuts with appropriate fixings.

Connections should be made either directly to the host controller or in a suitable terminal 
box inside the building.

Wiring

Core colour

Function

Red

+VDC

Black

Ground

Yellow

LED input

Green

Wiegand Data 0 / Data

White

Wiegand Data 1 / Clock

Brown

Not used

Orange

Format select (see below)

Blue

Serial Data Output

Format Select:

The output format is selected by connecting ‘Format Select’ to either Ground or +VDC as follows:

Models

Connect to Ground

Connect to +VDC

PP1-EM1

PP1-HT1

PP1-HT2

10-Digit Clock & Data

26-Bit Wiegand

PP1-DP1

26-Bit Wiegand

44-Bit Wiegand

 

Reader Operation

The LED lights red when power is connected. 
When a token or card is presented, the LED blinks green briefly.
The LED changes to green while the LED input line (yellow) is pulled low (typically indicates that the 

door is unlocked). 

NOTE:

  

the output lines of the reader are fed by an open collector transistor – a biasing resistor 
may be required on some host controllers for correct operation.  Please refer to the 
controller reference documentation.