background image

6

AIR HANDLER INSTALLATION

The B4VM-E Series Air Handler is shipped ready for 
vertical upflow installation and is approved for attic, 
basement, alcove/closet or crawlspace installation with 
zero clearance to combustibles. See Figure 1 (page 4) 
for required installation clearances. This appliance is 
only for indoor use.

•  The unit must be leveled at installation and attached to 

a properly installed duct system.

•  The surface that the air handler is mounted on must 

provide sound physical support of the unit.

•  The air handler must be installed so that all electrical 

components are protected from water.

•  If a louvered door is installed across the front of this 

unit, the appliance must be mounted flush or behind 
front edge of finished wall.

Packaging Removal
Remove the shipping crate and User’s Manual from the 
equipment. When removing the crate, use extra care so 
tubing connectios are not damaged.

Mounting Applications
Vertical only air handlers are factory ready for upflow 
applications. These units may be applied in downflow 
or horizontal left and right discharge applications when 
applied with the appropriate field kit.

Factory ready horizontal air handlers may be applied in 
upflow or horizontal-left and -right discharge applications. 
These units may also be applied in downflow discharge 
when applied with the appropriate field kit as specified in 
the units Technical Specifications.

Through-the-floor installations require a 1/4” thick 
noncombustible resilient gasket to be used whenever the 
supply or return air ducts pass through the floor. The gasket 
should be positioned between the duct, unit, and floor.

Upflow Installations
All air handlers are factory shipped, ready for upflow 
installation. The horizontal drain pan should be removed 
from the air handler when installing the unit in an upflow 
configuration. All return air must enter from the bottom of 
the unit. A typical upflow unit is shown in Figure 2.

Downflow Installations
The downflow accessory kit (See Technical Specifications) 
is required for downflow applications. Instructions for 
installing the downflow accessory kit are included with the 
kit. It is recommended that the accessory be installed prior 
to installing the unit. All return air in downflow applications 
must enter through the top of the unit. A typical installation 
of the unit in a downflow application is shown in Figure 3.

Figure 2. Upflow Installation

Horizontal

Drain Pan

Return

Air

Figure 3. Downflow Installation

Tube

Close-off 

Plate

Coil

Cabinet

Adaptor Kit

noise eminating from the air handler. These treatments 
can produce a quieter installation, particularly in the 
heated space. However, they can increase the pressure 
drop in the duct system. Care must be taken to maintain 
the proper maximum pressure differential across the 
air handler, temperature rise and flow rate. This may 
mean increasing the duct size and/or reducing the 
blower speed. These treatments must be constructed 
and installed in accordance with NFPA and SMACNA 
construction standards. Consult with local codes for 
special requirements. For best sound performance, be 
sure to install all the needed gaskets and grommets 
around penetrations into the air handler, such as for 
electrical wiring.

Summary of Contents for B4VM-E

Page 1: ...type of equipment Improper installation service adjustment or maintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage...

Page 2: ...before servicing this equipment Pay attention to all safety warnings and any other special notes highlighted in the manual Safety markings are used frequently throughout this manual to designate a deg...

Page 3: ...operations Installthisunitonlyinalocationandpositionasspecified on pages 4 5 This unit is designed only for Indoor installations and should be located with consideration of minimizing the length of t...

Page 4: ...r service access and noise The dimensions of the room or alcove must be able to accommodate the overall size of the unit and the installation clearances listed in Figure 1 Physical dimensions for this...

Page 5: ...cated in the bottom of the unit Accessing the filter does not require tools and can be removed from the front of the unit by removing the filter door See Unit Maintenance page 13 for filter sizes and...

Page 6: ...never the supplyorreturnairductspassthroughthefloor Thegasket should be positioned between the duct unit and floor Upflow Installations All air handlers are factory shipped ready for upflow installati...

Page 7: ...horizontal drain pan IMPORTANT If the webbing is not removed the condensate will not drain properly and ceiling damage may occur 3 Insert the plug from horizontal drain pan into the open and unused d...

Page 8: ...r that minimizes the length of tubing and the number of bends in the tubing It should be supported in a manner that prevents it from vibrating or abrading during system operation Tubing should be kept...

Page 9: ...runionwithasmallpaintbrush If bubblingisobserved theconnectionisnotadequately sealed 11 Replace all grommets and properly dispose of all removed parts Condensate Drainage CAUTION The air handler must...

Page 10: ...occur Do not use gas piping as an electrical ground This unit must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA...

Page 11: ...MOP Circuit A Circuit B Circuit C 240 NONE 5 8 15 5 8 15 005H 30 8 40 30 8 40 008H 44 8 50 44 8 50 010H 55 8 60 55 8 60 015H 80 8 90 55 8 60 25 0 30 020H 105 8 125 55 8 60 50 0 60 025H 130 8 150 55 8...

Page 12: ...t user manual Dehumidification The iQ Drive system may provide some dehumidification by lowering the airflow to increase the amount of humidity that is removed from the circulating air during cooling...

Page 13: ...in place Verify that the thermostat is properly installed and is not being affected by drafts or heat from lamps or other appliances Toachievethebestperformanceandminimizeequipment failure it is reco...

Page 14: ...D B 43 5 16 19 11 16 18 1 4 No Tall B 49 5 16 19 11 16 18 1 4 No C 55 15 16 22 7 16 21 Yes 3 4 3 4 3 4 13 1 1 4 1 5 8 1 7 8 1 1 4 3 1 4 2 5 8 11 8 K O Typ 1 3 4 K O Typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1...

Page 15: ...tor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Control Board Filter Door Upper Door Assembly Lower Door Assembl...

Page 16: ...EXV Control Board R R 410A 1 2 3 4 5 6 7 8 ON OFF R 22 THERM THERM PRESS C Y COMM EXV C R G Y Y2 O W1 W2 Y1 24VAC COM FUSE P2 P3 X13 COM X13 HEAT X13 COOL XFMR L1 VSPOWER L1 L2COM L2 L2 Figure 10 X13...

Page 17: ...COM 24 VAC COM L1 L1 XFMR W2 W1 O Y Y2 HEATER PLUG KIT G R C RED YELLOW WHITE GREEN BLACK RED GREEN BLACK WHITE RED RED RED GRAY YELLOW WHITE BLACK TO OUTDOOR UNIT BLACK WIRES EXV 6 WIRE CABLE CABLE C...

Page 18: ...18...

Page 19: ...19...

Page 20: ...sareprimarilyintendedtoassistqualifiedindividuals experienced in the proper installation of this appliance Some local codes require licensed installation service personnel for this type of equipment P...

Reviews: