background image

13

5. Inspect the unit rating plate for the proper type of 

refrigerant and quantity.

6. Weigh in the proper amount of new (or reclaimed) 

refrigerant.

Refrigerant Charging
The system refrigerant charge can be checked and 
adjusted through the service ports provided at the front 
panel of the outdoor unit. Use only gauge lines which have 
a Schrader depression device present to actuate the valve.

Air Circulation
Running the Blower Continuously
Set the thermostat’s system mode to OFF and the 
thermostat’s fan mode to ON. The blower motor should 
run continuously. Check for air delivery at the register(s). 
Ensure that there are no obstructions at the registers or 
in the ducts.

Turning the Blower Off
Set thermostat’s fan mode to AUTO, the blower will shut 
down immediately.

NOTE: If blower is turning opposite of arrow direction, shut 
off main power to the unit and switch any two field wires 
at the disconnect. DO NOT alter unit wiring.

Continuous low speed fan operation
(Standard Blower)
The air handler is equipped with an option of continuous 
low speed fan operation. When G is energized without Y/
Y2
, the air handler will operate using the heating speed. 
With  G & Y/Y1 or Y/Y2 energized, the air handler will 
operate in the selected cooling speed (including 40 sec 
blower-off delay).

System Cooling
1. Set the thermostat’s system mode to COOL and fan 

mode to AUTO. Lower the thermostat’s temperature 
mode below room temperature and observe that the 
blower energizes. Check the air being discharged at 
the register is cooler than room temperature. Verify 
unit refrigerant pressures are in order. Blower should 
be turning in direction indicated by arrow.

 NOTE: DO NOT alter unit wiring. Listen for any unusual 

noises. Locate the source and correct as needed.

2. Allow the unit to run for several minutes and then set 

the thermostat’s temperature above room temperature. 
Verify the blower cycles off with the thermostat.

System Heating
1. Set the thermostat’s system mode to HEAT and the fan 

mode to AUTO. Increase the thermostat’s temperature 
above room temperature and observe that the blower 
energizes. Check the air being discharged at the register 
is warmer than room temperature.

2. Allow the unit to run for several minutes and then set 

the thermostat’s temperature below room temperature. 
Verify the blower cycles off with the thermostat.

Minimum Electric Heat Airflow
The minimum electric heat airflow setting controls the 
minimum air flow that will be produced whenever electric 
heater kits are used. When the electric heater kit is 
energized along with a heat pump, the airflow may be 
higher depending on the basic cooling/heat-pump airflow 
setting. The minimum electric heat airflow is selected by 
the red blower wire on 3-speed models.

Blower Configurations
Determining Nominal System Capacity
To select the appropriate airflows for the air handler, the 
nominal system capacity must be known. The nominal 
system capacity is always the nominal capacity of the 
outdoor unit. However, in some situations the nominal 
system capacity may not be the same as the nominal 
capacity of the air handler. Always refer to the outdoor 
unit rating label to determine the nominal system capacity.

NOTE: The CFM values listed in Table 2 (page 17) are 
not dependent on duct static pressure. The VSHE motor 
automatically compensates for changes in duct static 
pressure (within the limits of the motor).

3-Speed Units
The blower speed is preset at the factory for operation 
at the same speed for heating and cooling, by using the 
jumping terminal on the blower motor and connecting it 
to the desired speed with both the red and black wires 
connected to the jumping terminal. NOTE: The control 
board is programmed with a 40 second off delay in the 
cooling mode for optimum system performance and 
efficiency.

 CAUTION:

To avoid personal injury or property damage, 
make sure the motor leads do not come into 
contact with any uninsulated metal components 
of the unit.

For optimum system performance and comfort, it may be 
necessary to change the factory set speed. See Table 2 
(page 17) for airflow data. To change the blower speed:
1. Disconnect all electrical power to the unit and remove 

the upper door.

2. Remove the black and red wires from the blower motor 

jumping terminal. Discard the blower motor jumping 
terminal.

3. Connect the heating speed wire (red) and the cooling 

speed wire (black) to the desired blower speed marked 
on the terminal block of the blower motor.

•  Terminal 4 = Hi speed
•  Terminal 5 = Med speed
•  Terminal 6 = Low speed

4. Replace the upper door and secure it to the unit.
5. Restore power to the unit..

Summary of Contents for B5BM

Page 1: ...ion service adjustment or maintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage Unless otherwise noted in these ins...

Page 2: ...ns 11 Control Board 12 Twinning 12 Heater Kits 12 Startup Adjustments 12 Before You Start the Unit 12 Refrigerant Charging 13 Air Circulation 13 Running the Blower Continuously 13 Continuous Low Speed...

Page 3: ...his unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equipment...

Page 4: ...ervice access and noise The dimensions of the room or alcove must be able to accommodate the overall size of the unit and the installation clearances listed in Figure 1 Physical dimensions for this ai...

Page 5: ...duct opening or filter rack located in the bottom of the unit Accessing the filter does not require tools and can be removed from the front of the unit by removing the filter door See Unit Maintenanc...

Page 6: ...hen installing the unit in an upflow configuration All return air must enter from the bottom of the unit A typical upflow unit is shown in Figure 2 Downflow Installations Thedownflowaccessorykit SeeTe...

Page 7: ...orizontal drain pan into the open and unused drain hole in the drain pan at the bottom of the unit to block bypass air 4 Remove the corresponding drain line knockout from the coil access door to allow...

Page 8: ...quid lines must be sized in accordance with the condensing unit specifications See Figure 11 page 16 for liquid and suction line locations When connecting refrigerant linesets together it is recommend...

Page 9: ...h lineset tubes to proper length in accordance with the outdoor unit specifications Verify the ends are round clean and free of any burrs 4 Positiongrommetonlinesetwithsufficientdistanceaway from braz...

Page 10: ...ccurring 7 Wrap the refrigerant lines with pressure sensitive neoprene or other suitable material especially where the lines enter the opening in the sheet metal 8 Evacuatethesystemofmoistureandnon co...

Page 11: ...the unit Use only copper wire for the line voltage power supply to this unit Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit Aluminum supply...

Page 12: ...vided 3 Connect the heater kit plug with the mating receptacle on the air handler control board If a heater kit is not installed 1 Remove the 2 wire plug of the air handler by cutting the wires and di...

Page 13: ...un for several minutes and then set the thermostat s temperature below room temperature Verify the blower cycles off with the thermostat Minimum Electric Heat Airflow The minimum electric heat airflow...

Page 14: ...he factory It is recommended that the filter be cleaned or replaced monthly Newly built or recently renovated homes may requiremorefrequentchanginguntiltheconstructiondust has minimized Filter sizes s...

Page 15: ...11 4 15 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A Cabinet Size H W A Detail D A 43 5 16 14 3 16 12...

Page 16: ...Motor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Control Board Filter Door Upper Door Assem...

Page 17: ...1270 1196 1113 1018 913 Corrected ESP1 0 00 0 00 0 00 0 09 0 23 0 36 0 50 0 64 42 48K B Cabinet Low 1324 1302 1271 1233 1187 1134 1072 1003 Corrected ESP1 0 00 0 06 0 17 0 27 0 38 0 49 0 61 0 72 Medi...

Page 18: ...Conditioner with Variable Speed Air Handler Typical 2 Stage Cooling Heat Pump with Optional Outdoor Thermostat Variable Speed Air Handler W2 W1 O Y Y2 G R C W2 W1 O Y Y2 G R C Y2 Y2 Y2 Y2 W1 W3 R Y1...

Page 19: ...19 C R G Y Y2 O W1 W2 Y1 24VAC COM FUSE P2 P3 X13 COM X13 HEAT X13 COOL XFMR L1 VSPOWER L1 L2COM L2 L2 Figure 13 Motor Control Board...

Page 20: ...8 9 10 11 12 13 14 15 16 G C O HUM Y1 W R HUM Y Y2 L2 COM 2 L2 L2COM L1 VS POWER XFMR COOL HEAT Y1 HEATER PLUG P3 1 2 3 4 5 6 7 8 YELLOW BLUE RED JUMPER SELECTOR SWITCHES NOTE 1 ON 0 OFF 710544D Repl...

Page 21: ...IELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE The blower motor speed tap connection may not be as shown See the Installation Instructions Disconnect all power before servicing Transformer may have a dua...

Page 22: ...ct all power before servicing 3 Transformer may have a dual voltage primary tap Match the tap position with the supply voltage used 4 If the Internal wiring is replaced use only 105 C copper wire of t...

Page 23: ...K GREY BLACK GREY BLUE ORANGE POWER PLUG LIMIT RED RED RED RED BLACK BLACK RED BLACK RELAY RELAY TERMINAL BLOCK for select models only CIRCUIT BREAKER Circuit breaker models only BLUE W2 W1 O Y Y2 G R...

Page 24: ...pply voltage used 4 If the Internal wiring is replaced use only 105 C copper wire of the same gauge W2 W1 O Y Y2 G R C 4 SPD MOTOR 1 2 3 5 6 4 TRANSFORMER 24V BLACK RED WHITE BLACK WHITE FUSE L2 COM 2...

Page 25: ...1 2 3 5 4 TRANSFORMER 24V BLACK RED WHITE BLACK WHITE FUSE BLOWER MOTOR PLUG C L G N N NEUTRAL G GROUND L LINE C COMMON L2 L2 L2 COM L1 L1 XFMR X13 COOL X13 HEAT 24 VAC RED COM GREY Y1 C L G N WHITE X...

Page 26: ...1 only On Stage 1 Heat on instantly Heat blower on after 3 second delay Stage 3 5 Heat on after 1 minute delay Stage 2 Heat on after 2 minute delay Stage 4 6 Heat on after 3 minute delay Off Heat stag...

Page 27: ...27...

Page 28: ...sareprimarilyintendedtoassistqualifiedindividuals experienced in the proper installation of this appliance Some local codes require licensed installation service personnel for this type of equipment P...

Reviews: