11
humidistat (see
). During normal operation, the
motor will gradually change speeds during start-up, shut
down, when thermostat inputs change, and when the duct
static pressure changes (vents closed or opened, filter
clogging, etc.). The air handler is configured by setting
the selector switches on the control board.
Selecting Basic Heating Airflow
The fixed speed motor control board (
) contains a set of dip switches for setting the blower
speed. Use pins 1 to 4 to set the blower speed for heating
and pins 5 to 8 to set the speed for cooling. To determine
the appropriate switch settings for your installation, see
NotE:
The minimum electric heat airflow setting may be
set higher, but must never be set lower than the setting
shown in
.
Selecting Basic Cooling / Heat Pump Airflow
The basic cooling/heat-pump airflow is controlled by setting
switches 5 - 8 on the thermostat input board (mounted
on the blower). All airflows for other modes of operation
(except electric heat) are determined by this basic setting.
FAN ONLY would deliver 50% of the selected cooling
airflow.
lists the basic airflow values
versus the airflow selector switch settings and ranges of
basic air flow settings.
• When operating in the heat pump mode, a higher
basic airflow setting will increase the energy efficiency
and capacity but will also decrease the supply air
temperature.
• For maximum capacity and energy efficiency, select an
airflow at or near the top of the range for that nominal
capacity.
• For maximum dehumidification, select an airflow near the
middle or bottom of the range for that nominal capacity.
Additional information on humidity control can be found
in the Humidistat and Delay Setting sections.
• For thermostats with a dehumidifier output, use a field
supplied wire to connect the thermostat’s dehumidifier
output to the terminal marked
DHUm
. The thermostat
should be set so that the
DHUm
output should be high
(positive) when dehumidification is needed. See also
Dehumidification Options section.
ImpoRtANt!
If coil icing is observed, the basic cooling/
heat-pump airflow selected may be too low. Verify the
setting selected is within the range shown in
and that the the system is properly charged.
Please refer to the instructions supplied with the outdoor
unit. If icing continues to occur, raise the selected airflow
one or two steps.
UNIt mAINtENANcE
Proper maintenance is most important to achieve the best
performance from a air handler. Some of the components
and their locations are shown in
any component of the air handler must be replaced, use
only factory authorized replacement parts specified in the
Replacement Parts List provided online.
WARNING:
ELEctRIcAL SHocK, FIRE oR
EXpLoSIoN HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical
power to the air handler.
• When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
• Verify proper operation after servicing.
• These maintenance instructions are primarily intended
to assist qualified technicians experienced in the proper
maintenance and operation of this appliance.
• Always reinstall the doors on the air handler after
servicing or cleaning/changing the filters. Do not operate
the air handler without all doors and covers in place.
• Verify that the thermostat is properly installed and is
not being affected by drafts or heat from lamps or other
appliances.
• To achieve the best performance and minimize
equipment failure, it is recommended that a yearly
maintenance checkup be performed. At a minimum,
this check should include the following items:
Air Filter(s)
WARNING:
Never operate the air handler without a filter in
place. Dust and lint in the return air can build
up on internal components, resulting in loss of
efficiency, equipment damage, and possible fire.
B6BV series air handlers are not supplied with a single air
filter when shipped from the factory. It is recommended
that the filter be cleaned or replaced monthly. Newly built
or recently renovated homes may require more frequent
changing until the construction dust has minimized. Filter
sizes shown in
are available at most local retailers.
Filters designed to remove smaller particles such as
pollen, may require additional maintenance.
cABINEt SIZE
FILtER SIZE
A
12
x
20
x
1
B
18
x
20
x
1
C
20
x
20
x
1
table 2. Filter Sizes
Summary of Contents for B6BV Series
Page 23: ...23...