16
coNtRoL SIGNAL & moDE
opERAtIoN
totAL KW
BoARD ActIoN
w1 & w2
eheAt
O
n
5 Kw
Stage 1 Heat on instantly
Heat blower on after 3 second delay
10 Kw
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
15 Kw
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
20 Kw
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
25 Kw
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
Stage 5 Heat on after 20 seconds delay
30 Kw
Stage 1Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
Stage 5 Heat on after 20 seconds delay
Stage 6 Heat on after 25 seconds delay
O
FF
Heat stages off instantly
Blower off after 15 second delay
w1 & Y/Y2
Aux heAt
O
n
5 Kw
Stage 1 Heat on instantly
Cool blower on after 3 second delay
10 Kw
Stage 1 Heat on instantly
Cool blower on after 3 second delay
15 Kw
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
20 Kw
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
25 Kw
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
30 Kw
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
O
FF
Heat stages off instantly
Heat blower turns off after 40 second delay
table 8. Heating Element Logic - continued