background image

5

Requirements for sealing ducts vary from region to 

region. Consult with local codes for requirements specific 

to your area.

Return Air connections

For each application in the USA, the home manufacturer 

shall comply with all of the following conditions to have 

acceptable return air systems for closet installed forced 

air heating appliances:

•  regardless of the location, the return air opening into the 

closet shall not be less than specified in the appliance’s 

listing.

•  means shall be provided to prevent inadvertent closure 

by a flat object placed over the return air opening when 

it is located in the floor of the closet (versus the vertical 

front or side wall).

•  The  cross-sectional  area  of  the  return  duct  system 

leading into the closet shall not be less than 390 in

2

.

•  The total free area of openings in the floor or ceiling 

registers serving the return air duct system must be at 

least 352 in

2

. At least one register should be located 

where it is not likely to be covered by carpeting, boxes 

and other objects.

•  materials located in the return duct system must have a 

flame spread classification of 200 or less. This includes 

a closet door if the air handler is in a closet.

•  Test the negative pressure in the closet with the air-

circulating fan operating at high speed and the closet 

closed. The negative pressure is to be no more negative 

than minus 0.05 inch water column.

•  For  floor  return  systems,  the  manufactured  home 

manufacturer shall affix a prominent marking on or 

near the appliance where it can be easily read when 

the closet door is open. The marking shall read:

 cAUtIoN:

ASpHYXIAtIoN HAZARD: Do not cover or restrict 

return air opening.

•  The return air opening can be located in a closet door or 

a sidewall. If the return air opening is directly adjacent 

to the side (or front) of the air handler, 6” minimum 

clearance must be provided between the side of the 

air handler and the return air opening. If no part of the 

return air opening is directly adjacent to the unit no 

clearance is required.

•  In  applications  where  the  supply  ducts  carry  heated 

air to areas outside the space where the air handler 

is installed, the return air must be delivered to the air 

handler by duct(s) secured to the casing, running full 

size and without interruption.

Supply Air connections

•  The supply duct system must be designed so that the 

static pressure measured external to the air handler 

does not exceed the listed static pressure shown on 

the rating plate. The supply air must be delivered to the 

heated space by duct(s) secured to the casing, running 

full length and without interruption.

Unconditioned Spaces

All duct work passing through unconditioned space must 

be properly insulated to minimize duct losses and prevent 

condensation. Use insulation with an outer vapor barrier. 

Refer to local codes for insulation material requirements.

Acoustical Duct Work

•  Certain installations may require the use of acoustical 

lining inside the supply duct work. Acoustical insulation 

must be in accordance with the current revision of the 

Sheet Metal and Air Conditioning Contractors National 

Association (SMACNA) application standard for duct 

liners. Duct lining must be UL classified batts or blankets 

with a fire hazard classification of FHC-25/50 or less.

•  Fiber duct work may be used in place of internal duct 

liners if the fiber duct work is in accordance with the 

current revision of the SMACNA construction standard 

on fibrous glass ducts. Fibrous duct work and internal 

acoustical lining must be NFPA Class 1 air ducts when 

tested per UL Standard 181 for Class 1 ducts.

•  Damping ducts, flexible vibration isolators, or pleated 

media-style filters on the return air inlet of the air 

handler may be used to reduce the transmission of 

equipment noise eminating from the air handler. These 

treatments can produce a quieter installation, particularly 

in the heated space. However, they can increase the 

pressure drop in the duct system. Care must be taken 

to maintain the proper maximum pressure rise across 

the air handler, temperature rise and flow rate. This 

may mean increasing the duct size and/or reducing the 

blower speed. These treatments must be constructed 

and installed in accordance with NFPA and SMACNA 

construction standards. Consult with local codes for 

special requirements. For best sound performance, be 

sure to install all the needed gaskets and grommets 

around penetrations into the air handler, such as for 
electrical wiring.

Air Filters

B6BV series air handlers are not supplied with an air filter 

when shipped from the factory. The installer must provide 

a high velocity filter that is appropriately sized to the return 

air duct opening or filter rack located in the bottom of the 

unit. Accessing the filter does not require tools and can 

be removed from the front of the unit by removing the 
filter door. See Unit Maintenance (

page  11

) for filter 

sizes and installation information.

 WARNING:

Never operate the air handler without a filter 

or with doors removed. Dust and lint can build 

up on internal components, resulting in loss of 

efficiency, equipment damage, and possible fire.

Summary of Contents for B6BV Series

Page 1: ...nt role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the appliance or failure to follow safety warnings could result in s...

Page 2: ...Blower Off 10 Blower Configurations 10 Determining Nominal System Capacity 10 Selecting Continuous Low Speed Fan Operation 10 Proper Blower Speed for Multi Speed Units 10 High Efficiency Fixed Speed U...

Page 3: ...ted in accordance with the Canadian Electric Code Part 1 CSA C 22 1 Installationofequipmentmayrequirebrazingoperations Installer must comply with safety codes and wear appropriate safety equipment saf...

Page 4: ...his may result in fire explosion carbon monoxide poisoning personal injury or property damage Plenums and air ducts should be installed in accordance with the standards of the National Fire Protection...

Page 5: ...ate The supply air must be delivered to the heated space by duct s secured to the casing running full length and without interruption Unconditioned Spaces All duct work passing through unconditioned s...

Page 6: ...r attic basement alcove closetorcrawlspaceinstallationwithzeroclearance to combustibles See Figure 1 page 4 for required installationclearances Thisapplianceisapprovedonly for indoor use Remove the sh...

Page 7: ...ant Requirements for sealing ductwork varyfromregiontoregion Consultwithlocalcodes for requirements specific to your area A C or H P Coil Installation Approved air conditioning and heat pump system co...

Page 8: ...isolating contacts to prevent inter connection of Class 2 outputs Where local codes require that the thermostat wiring must be routed through a conduit or raceway splices can be made inside the unit...

Page 9: ...y Theseoutdoorunitscomestandardwith24V power supply sufficient for powering both air handlers c Low voltage wiring should be connected as shown in Figure 10 page 18 d Wire all other low voltage thermo...

Page 10: ...BV series air handler is equipped with the option of continuous low speed fan operation When G is energized without Y Y2 the air handler will operate using the heating speed With G Y Y2 or Y Y2 energi...

Page 11: ...ithin the range shown in Table 6 page 14 and that the the system is properly charged Please refer to the instructions supplied with the outdoor unit If icing continues to occur raise the selected airf...

Page 12: ...s recommended that the blower compartment be cleaned of dirt or lint that may have accumulated in the compartment or on the blower and motor as part of the annual inspection Blower Fan Wheel Inspect t...

Page 13: ...4 13 1 7 8 K O 11 8 K O typ 11 4 15 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A Cabinet Size H W A D...

Page 14: ...10 960 925 875 830 745 1 0 1 0 1275 1220 1175 1120 1060 970 930 890 0 1 1 0 1365 1350 1255 1200 1150 1105 1060 1025 1 1 1 0 1480 1430 1370 1325 1265 1225 1185 1140 0 0 0 1 1560 1535 1485 1430 1375 133...

Page 15: ...blower on after 3 second delay Stage 2 Heat on after 5 second delay Stage 3 Heat on after 10 second delay Stage 4 Heat on after 15 second delay Off Heat stages off instantly Blower off after 15 second...

Page 16: ...5 seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay Stage 6 Heat on after 25 seconds delay Off Heat stages off instantl...

Page 17: ...s delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay 30 KW Stage 1Heat on instantly Cool blower on after 3 second delay Stage 2...

Page 18: ...Typical 2 Stage Heat Pump with 2 Stage Air Handler Y2 Y2 Y2 Y2 OUT W E R Air Conditioner Air Handler Air Conditioner Air Handler Heat Pump Air Handler Heat Pump O R C Y Air Handler Heat Pump NOTE Jump...

Page 19: ...AT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 Figure 11 Single Stage Control Board 3A Fuse EAC L 1 L 2 HUM L 1 L 2 8 1 2 3 4 5 6 7 8 ON HEAT COOL R C G W D Y EHEAT POWER ECM BLOWER Figure 12 Fixe...

Page 20: ...OWER MOTOR PLUG 6 5 4 3 2 1 1 COM 2 HIGH 3 MED HIGH 4 MED LOW 5 LOW 6 OPEN NOTES 1 The blower motor speed tap connection may not be as shown See the Installation Instructions 2 Disconnect all power be...

Page 21: ...have a dual voltage primary tap Match the tap position with the supply voltage used 4 If the internal wiring is replaced use only 105 C copper wire of the same gauge BLACK BLACK RED IF BOARD EQUIPPED...

Page 22: ...ir un robinet principal double tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac utilisez seulement un fil de cuivre 105 C du m me gabarit...

Page 23: ...23...

Page 24: ...r reproductive harm Specifications illustrationssubjecttochangewithoutnoticeorincurringobligations 10 16 O Fallon MO Nortek Global HVAC LLC 2016 All Rights Reserved INSTALLER NAME CITY STATE INSTALLAT...

Reviews: