6
NotE:
Downflow installations require the use of a plenum
connector (or its equivalent) if the supply air ducts pass
through the floor of the structure. This factory supplied
accessory must be installed in the floor cavity and attached
to the supply air duct before the downflow unit is installed.
Available plenum connectors for all B6BV air Handlers are
listed in
applications must enter through the top of the unit.
Position the air handler on top of the plenum connector and
secure together with sheet metal screws. The screws must
penetrate the sheet metal cabinet and plenum connector.
Tape or seal all seams if required by local code.
Plenum Connector Installation
The plenum connector is designed for use with trunk ducts
having a minimum width of 12”. If sufficient space is not
available to adequately bend and secure duct tabs it may
be necessary to attach the connector to the duct using
sheet-metal fasteners and seal with an approved foil tape.
The connector may be field constructed but must meet
requirements as listed in the unit installation instructions.
1. Measure and mark the outline of the cut-out on the
floor. See
for cutout dimensions.
ImpoRtANt!
Cut-outs in the floor and ductwork must
be carefully located to avoid misalignment of the air
handler and supply / return air ducts.
2. Cut out the floor opening.
NotE:
To allow some clearance for installing the plenum
connector, cut the opening 1/16” larger than the actual
cutout drawn.
3. Center the plenum connector in the floor opening with
bottom tabs resting on top of the supply air duct.
4. Mark the cut-out area on the supply air duct by tracing
around the connector tabs of the plenum connector.
Figure 2. Installation configurations
Return
Air
Return
Air
UPFLOW
DOWNFLOW
AIR HANDLER INStALLAtIoN
These Installation procedures are suggested for typical
air handler installations. Since all installations are different
from each other, the sequence of these steps may
differ from the actual installation.
only qualified HVAc
technicians should install this air handler
.
The B6BV series air handler is shipped ready for vertical
upflow installation and is approved for attic, basement,
alcove/closet or crawlspace installation with zero clearance
to combustibles. See
for required
installation clearances.
this appliance is approved only
for indoor use.
• remove the shipping carton and user’s manual from
the equipment.
• The unit must be leveled at installation and attached to
a properly installed duct system.
• The surface that the air handler is mounted on must
provide sound physical support of the unit.
• The air handler must be installed so that all electrical
components are protected from water.
• If a louvered door is installed across the front of this
unit, the appliance must be mounted flush or behind
front edge of finished wall.
Upflow Installations
All air handlers are factory shipped, ready for upflow
installation. All return air must enter from the bottom of the
unit when installed in the upflow configuration. A typical
upflow unit is shown in
Position the air handler on top of the return air duct and
secure together with sheet metal screws. The screws
must penetrate the sheet metal cabinet and duct. Tape
or seal all seams if required by local code.
To attach the supply air duct to the air handler, bend the
perforated flanges (
with a pair of wide duct pliers. Position the duct on top
of the air handler and secure together with sheet metal
screws. Make sure the screws penetrate the sheet metal
casing and flanges. Tape or seal all seams if required by
local code.
NotE:
If an upflow pedestal mounting stand is fabricated
in the field, the stand must be constructed strong
enough to support the unit with all accessories installed
(approximately 130 lbs. for B-cabinet models and 200 lbs.
for C-cabinet models). The construction of the pedestal
stand must also allow for at least 235 in
2
free opening
(300 in
2
for C-cabinet models) in the application. Field
fabricated upflow pedestal mounting stands must be
constructed of noncombustible materials. Position the air
handler on top of the mounting stand and secure together
with sheet metal screws. The screws must penetrate the
sheet metal cabinet and duct. Tape or seal all seams if
required by local code.
Downflow Installations
B6BV air handlers can be converted to downflow operation
by flipping an upflow unit 180°. A typical installation of
the unit in a downflow application is shown in
.
Summary of Contents for B6BV Series
Page 23: ...23...