background image

10

Line Voltage

• 

An electrical disconnect must be located within 
sight of and readily accessible to the unit

. This switch 

shall be capable of electrically de-energizing the unit. 
See unit data label for proper incoming field wiring. Any 
other wiring methods must be acceptable to authority 
having jurisdiction.

•  It is recommended that the line voltage to the unit be 

supplied from a dedicated branch circuit containing the 
correct fuse or circuit breaker for the unit.

•  Overcurrent protection must be provided at the branch 

circuit distribution panel and sized as shown on the unit 
rating label and according to applicable local codes. See 
the unit rating plate and Table 4 (page 15) for maximum 
circuit ampacity & maximum overcurrent protection limits.

•  The  installer  should  become  familiar  with  the  wiring 

diagram/schematic before making any electrical 
connections to the unit. See the unit wiring label or 
Figure 12 (page 17).

•  Use only copper wire for the line voltage power supply 

to this unit. Use proper code agency listed conduit and 
a conduit connector for connecting the supply wires to 
the unit. Aluminum supply wire may be used if a heater 
kit is installed.

•  If replacing any of the original wires supplied with the 

unit, the replacement wire must be copper wire consisting 
of the same gauge and temperature rating.

•  Provide power supply for the unit in accordance with the 

unit wiring diagram, and the unit rating plate. Use UL 
listed conduit and conduit connectors for connecting the 
supply wires to the unit and for proper grounding. Field 
supplied bushings for the power supply cables must be 
added to support and protect the power supply cables. 

•  All 208/230 Volt units are shipped from the factory wired 

for 240 volt operation. For 208V operation, remove the 
lead from the transformer terminal marked 240V and 
connect it to the terminal marked 208V.

Thermostat Connections

•  Thermostat connections shall be in accordance with the 

instructions supplied with the thermostat. The thermostat 
used with this equipment must operate in conjunction 
with any installed accessories. Typical AC and air handler 
hookups are shown in Figure 8 (page 15).

•  The thermostat should be mounted about 5 feet above the 

floor on an inside wall. DO NOT install the thermostat on 
an outside wall or any other location where its operation 
may be adversely affected by radiant heat from fireplaces, 
sunlight, or lighting fixtures, and convective heat from 
warm air registers or electrical appliances. Refer to the 
thermostat manufacturer’s instruction sheet for detailed 
mounting and installation information.

•  Install the grommet, which is packed with the unit, in 

the hole for low-voltage wires. Properly connect the 
low-voltage wiring between the thermostat, outdoor 
unit, and control board. 

NOTE: 

When the low voltage 

wires are positioned in this grommet, the grommet will 
prevent chafing and/or shorting of the low voltage leads.

Control Board

The control board in the air handler controls the timing 

sequence of the elements.

 

NOTE:

 Variable speed air 

handlers cannot be twinned.

Heater Kits

When electric heat packages with circuit breakers are 

field-installed, the circuit breaker may be used as a 

disconnecting means in most applications. Reference 

the NEC and local codes for disconnect requirements.

If a heater kit is installed:

The B6 air handler is shipped from the factory without an 

electric heater kit installed. If electric heat is desired, the 

H6HK heater kit may be purchased separately and field 

installed. Determine the correct size heater kit for your 

unit by referring to the list below or the units rating label. 

B Cabinet ....................................................... 20Kw max
C Cabinet ....................................................... 30Kw max

1. Connect the 2 wire plug of the air handler to the mating 

2 wire plug of the heater kit.

2. Connect the line voltage leads to the circuit breaker or 

terminal block provided.

3. Connect the heater kit plug with the mating receptacle 

on the air handler control board.

If a heater kit is not installed:
1. Remove the 2 wire plug of the air handler by cutting 

the wires and discarding the plug.

2. Strip the ends of the 2 air handler wires and connect 

to the line-voltage leads with the 2 wire nuts provided. 

Electronic Air Cleaner (EAC)

The unit has an output to power an electronic air cleaner 

when the blower is running. This output is rated to 1.0 

amp at 208/240V.

Grounding

 WARNING:

The unit cabinet must have an uninterrupted 
or unbroken electrical ground to minimize 
personal injury if an electrical fault should occur. 
Do not use gas piping as an electrical ground!

This unit must be electrically grounded in accordance 

with local codes or, in the absence of local codes, with 

the National Electrical Code (ANSI/NFPA 70) or the CSA 

C22.1 Electrical Code. Use the grounding lug provided in 

the control box for grounding the unit.

Summary of Contents for B6VMAI

Page 1: ...type of equipment Improper installation service adjustment or maintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage...

Page 2: ...t SAFETY INFORMATION INSTALLER Please read all instructions before servicing this equipment Pay attention to all safety warnings and any other special notes highlighted in the manual Safety markings a...

Page 3: ...operations The information listed below is for reference purposes only and does not necessarily have jurisdiction over local or state codes Always consult with local authorities before installing any...

Page 4: ...ons Applicable building codes may require additional clearance to equipment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums...

Page 5: ...must be properly insulated to minimize duct losses and prevent condensation Use insulation with an outer vapor barrier Refer to local codes for insulation material requirements Air Filters B6VMAI Ser...

Page 6: ...and floor Upflow Installations All air handlers are factory shipped ready for upflow installation The horizontal drain pan may be removed from the air handler when installing the unit in an upflow con...

Page 7: ...he horizontal drain pan IMPORTANT If the webbing is not removed the condensate will not drain properly and ceiling damage may occur 3 Insert the plug from horizontal drain pan into the open and unused...

Page 8: ...during installation Ifpreciseformingofrefrigerantlinesisrequired acopper tubing bender is recommended Avoid sharp bends and contact of the refrigerant lines with metal surfaces Refrigerant lines shou...

Page 9: ...ng or pvc pipe and adequately trapped Both drain tubes must have a minimum diameter of 3 4 and be trapped separately IMPORTANT Failure to install a trap may resultincondensationoverflowingthedrainpan...

Page 10: ...operation maybeadverselyaffectedbyradiantheatfromfireplaces sunlight or lighting fixtures and convective heat from warm air registers or electrical appliances Refer to the thermostat manufacturer s i...

Page 11: ...SeeiQDrivethermostat user manual Dehumidification The iQ Drive system may provide some dehumidification by lowering the airflow to increase the amount of humidity that is removed from the circulating...

Page 12: ...s on the air handler after servicingorcleaning changingthefilters Donotoperate the air handler without all doors and covers in place Verify that the thermostat is properly installed and is not being a...

Page 13: ...D B 43 5 16 19 11 16 18 1 4 No Tall B 49 5 16 19 11 16 18 1 4 No C 55 15 16 22 7 16 21 Yes 3 4 3 4 3 4 13 1 1 4 1 5 8 1 7 8 1 1 4 3 1 4 2 5 8 11 8 K O Typ 1 3 4 K O Typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1...

Page 14: ...tor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Control Board Filter Door Upper Door Assembly Lower Door Assembl...

Page 15: ...15 79 1 80 54 1 60 25 0 25 69 0 70 47 4 50 21 6 25 20 104 1 125 54 1 60 50 0 50 90 7 100 47 4 50 43 3 50 25 N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A 30 N A N A N A N A N A N A...

Page 16: ...R W2 W H OD UNIT BLOWER COIL THERMISTOR Figure 10 B6VMAI EXV Control Board R R 410A 1 2 3 4 5 6 7 8 ON OFF R 22 THERM THERM PRESS C Y COMM EXV Figure 11 B6VMAI Interface Control Board LED 1 BLWDTC BLW...

Page 17: ...TOR R4 SW Y EXV R C ID BLWR R DX DX GND R C R C W2 W H Y DX DX GND THERMISTOR EXV 6 WIRE CABLE SUCTION TEMP SENSOR CABLE N O I T C U S E R U S S E R P R O S N E S HARNESS THRU CORE RING THRU CORE RING...

Page 18: ...18...

Page 19: ...19...

Page 20: ...oteshighlightedinthemanual Improper installation of the air handler or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedto...

Reviews: