background image

8

• 

B6VMAI Series air handlers are charged through service 
valves on the end of the liquid tube for each circuit. 
These must be removed before brazing the line sets. 

Refrigerant Line Connections

 WARNING:

The coil in the air handler is factory shipped with 
a nitrogen charge. Avoid direct face exposure 
or contact with valve when gas is escaping. 
Always ensure adequate ventilation is present 
during the depressurization process. Address 
any uncertainties before proceeding. Failure 
to comply with this warning could result in 
equipment damage, personal injury, or death.

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

 CAUTION:

This unit uses R-410A refrigerant. DO NOT use 
any other refrigerant in this unit. Use of another 
refrigerant will damage the unit.

•  The installer should make every effort to ensure the 

field installed refrigerant containing components of the 
system have been installed in accordance with these 
instructions and sound installation practices for reliable 
system operation and longevity.

•  The air handler coil does not contain a refrigerant charge. 

Refer to the installation instructions supplied with the 
outdoor unit for refrigerant charge information.

•  Always refer to the installation instructions supplied with 

the outdoor unit for piping requirements. The suction 
and liquid lines must be sized in accordance with the 
condensing unit specifications. See Figure 6 (page 13) 
for liquid and suction line locations.

•  When  connecting  refrigerant  linesets  together,  it  is 

recommended that dry nitrogen be flowing through the 
joints during brazing. This will prevent internal oxidation 
and scaling from occurring.

•  Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends 
in the tubing. It should be supported in a manner that 
prevents it from vibrating or abrading during system 
operation. Tubing should be kept clean of foreign debris 
during installation.

•  If precise forming of refrigerant lines is required, a copper 

tubing bender is recommended. Avoid sharp bends and 
contact of the refrigerant lines with metal surfaces.

•  Refrigerant  lines  should  be  wrapped  with  pressure 

sensitive neoprene or other suitable material where 
they pass against sharp sheet metal edges.

Connecting the Linesets

1. Remove grommets from line set holes.

 CAUTION:

To protect the Thermistor and EXV, it is 
recommended that a wet rag be wrapped 
around the suction line in front of the close 
off plate before applying heat. Failure to keep 

components cool during brazing may result 

in structural damage, premature equipment 
failure, or possible personal injury.

2. Unbraze and remove the cap on the suction line.
3. Route and cut both lineset tubes to proper length in 

accordance with the outdoor unit specifications. Verify 
the ends are round, clean, and free of any burrs.

4. Position grommet on line set with sufficient distance away 

from brazing area. Brazing processes can permanently 
damage grommets.

5. Connect the suction and liquid lineset tubes.

 CAUTION:

To protect the Thermistor and EXV, it is 
recommended that a wet rag be wrapped 
around the suction line in front of the close 
off plate before applying heat. Failure to keep 

components cool during brazing may result 

in structural damage, premature equipment 
failure, or possible personal injury.

6. Braze the individual connections with dry nitrogen 

flowing through the joints. 

NOTE:

 This will prevent 

internal oxidation and scaling from occurring.

7. Wrap the refrigerant lines with pressure sensitive 

neoprene or other suitable material especially where 
the lines enter the opening in the sheet metal.

8. Evacuate the system of moisture and non-condensables 

to prevent low efficiency operation or damage to the 
unit. The suggested range of evacuation is 350 - 500 
microns.

9. Charge the system with refrigerant. Refer to the 

outdoor unit installation manual for additional charging 
instructions.

10. Check the system for leaks, including the lineset and 

the brazed joints.

11. Replace all grommets and properly dispose of all 

removed parts.

Summary of Contents for B6VMAI

Page 1: ...type of equipment Improper installation service adjustment or maintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage...

Page 2: ...t SAFETY INFORMATION INSTALLER Please read all instructions before servicing this equipment Pay attention to all safety warnings and any other special notes highlighted in the manual Safety markings a...

Page 3: ...operations The information listed below is for reference purposes only and does not necessarily have jurisdiction over local or state codes Always consult with local authorities before installing any...

Page 4: ...ons Applicable building codes may require additional clearance to equipment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums...

Page 5: ...must be properly insulated to minimize duct losses and prevent condensation Use insulation with an outer vapor barrier Refer to local codes for insulation material requirements Air Filters B6VMAI Ser...

Page 6: ...and floor Upflow Installations All air handlers are factory shipped ready for upflow installation The horizontal drain pan may be removed from the air handler when installing the unit in an upflow con...

Page 7: ...he horizontal drain pan IMPORTANT If the webbing is not removed the condensate will not drain properly and ceiling damage may occur 3 Insert the plug from horizontal drain pan into the open and unused...

Page 8: ...during installation Ifpreciseformingofrefrigerantlinesisrequired acopper tubing bender is recommended Avoid sharp bends and contact of the refrigerant lines with metal surfaces Refrigerant lines shou...

Page 9: ...ng or pvc pipe and adequately trapped Both drain tubes must have a minimum diameter of 3 4 and be trapped separately IMPORTANT Failure to install a trap may resultincondensationoverflowingthedrainpan...

Page 10: ...operation maybeadverselyaffectedbyradiantheatfromfireplaces sunlight or lighting fixtures and convective heat from warm air registers or electrical appliances Refer to the thermostat manufacturer s i...

Page 11: ...SeeiQDrivethermostat user manual Dehumidification The iQ Drive system may provide some dehumidification by lowering the airflow to increase the amount of humidity that is removed from the circulating...

Page 12: ...s on the air handler after servicingorcleaning changingthefilters Donotoperate the air handler without all doors and covers in place Verify that the thermostat is properly installed and is not being a...

Page 13: ...D B 43 5 16 19 11 16 18 1 4 No Tall B 49 5 16 19 11 16 18 1 4 No C 55 15 16 22 7 16 21 Yes 3 4 3 4 3 4 13 1 1 4 1 5 8 1 7 8 1 1 4 3 1 4 2 5 8 11 8 K O Typ 1 3 4 K O Typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1...

Page 14: ...tor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Control Board Filter Door Upper Door Assembly Lower Door Assembl...

Page 15: ...15 79 1 80 54 1 60 25 0 25 69 0 70 47 4 50 21 6 25 20 104 1 125 54 1 60 50 0 50 90 7 100 47 4 50 43 3 50 25 N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A 30 N A N A N A N A N A N A...

Page 16: ...R W2 W H OD UNIT BLOWER COIL THERMISTOR Figure 10 B6VMAI EXV Control Board R R 410A 1 2 3 4 5 6 7 8 ON OFF R 22 THERM THERM PRESS C Y COMM EXV Figure 11 B6VMAI Interface Control Board LED 1 BLWDTC BLW...

Page 17: ...TOR R4 SW Y EXV R C ID BLWR R DX DX GND R C R C W2 W H Y DX DX GND THERMISTOR EXV 6 WIRE CABLE SUCTION TEMP SENSOR CABLE N O I T C U S E R U S S E R P R O S N E S HARNESS THRU CORE RING THRU CORE RING...

Page 18: ...18...

Page 19: ...19...

Page 20: ...oteshighlightedinthemanual Improper installation of the air handler or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedto...

Reviews: