5
Downflow Applications:
Position the blower over the duct and
secure together with sheet metal screws.
Return Air Connections
The return air must be delivered to the blower by duct(s) secured
to the casing, running full size and without interruption. Tape or
seal all seams if required by local code.
Upflow & Horizontal Applications:
Position the blower over the
duct and secure together with sheet metal screws.
Downflow Applications:
To attach the supply air duct, bend
the furnace flanges outward 90° with a pair of wide duct pliers.
Position the duct on top of the cased coil and secure together
with sheet metal screws.
Acoustical Duct Work
• Certain installations may require the use of acoustical lining
inside the supply duct work. Acoustical insulation must be in
accordance with the current revision of the Sheet Metal and
Air Conditioning Contractors National Association (SMACNA)
application standard for duct liners. Duct lining must be UL
classified batts or blankets with a fire hazard classification of
FHC-25/50 or less.
• Fiber duct work may be used in place of internal duct liners if
the fiber duct work is in accordance with the current revision
of the SMACNA construction standard on fibrous glass ducts.
Fibrous duct work and internal acoustical lining must be NFPA
Class 1 air ducts when tested per UL Standard 181 for Class
1 ducts.
• Damping ducts, flexible vibration isolators, or pleated media-
style filters on the return air inlet of the air handler may be
used to reduce the transmission of equipment noise eminating
from the air handler. These treatments can produce a quieter
installation, particularly in the heated space. However, they
can increase the pressure drop in the duct system. Care
must be taken to maintain the proper maximum pressure rise
across the air handler, temperature rise and flow rate. This
may mean increasing the duct size and/or reducing the blower
speed. These treatments must be constructed and installed in
accordance with NFPA and SMACNA construction standards.
Consult with local codes for special requirements. For best
sound performance, be sure to install all the needed gaskets
and grommets around penetrations into the air handler, such
as for electrical wiring.
Air Filters
WARNING:
Never operate the air handler without a filter
or with doors removed. Dust and lint can build
up on internal components, resulting in loss of
efficiency, equipment damage, and possible fire.
MB7 Series air handlers are not equipped with a filter rack;
however, it is strongly recommended that a filter be located in
the return air duct system. Installing the filter and replacing it
every 3 months will increase air quality throughout the home.
Unconditioned Spaces
All duct work passing through unconditioned space must
be properly insulated to minimize duct losses and prevent
condensation. Use insulation with an outer vapor barrier. Consult
your Distributor for the recommended type and thickness of
insulation for your area as required by local codes.
Condensate Drainage
CAUTION:
The air handler must be level to ensure proper
condensate drainage. An unlevel installation may
result in structural damage, premature equipment
failure, or possible personal injury.
• To ensure proper condensate drainage, the unit must be
installed in a level position within 1/4 inch over the height,
width, and depth of the unit. The best system performance will
be obtained if the unit is located in a centralized position with
respect to the air distribution system. Refer to the Installation
Instructions supplied with the Cased Coil for proper condensate
drain connections.
• If the air handler is located in or above a living space where
damage may result from condensate overflow, an auxiliary
drain pan should be installed under the unit. A separate drain
line should extend from the pan to a conspicuous point and
serve as an alarm indicating that the primary drain is restricted.
As an alternative to a separate drain line, an approved water
level indicator or float switch device should be used to shut
down the unit in the event water is detected in the auxiliary
pan.
• During system checkout, inspect the drain line and connections
to verify proper condensate drainage.
• Methods for disposing of condensate vary according to local
codes. Refer to local codes or authority having jurisidiction for
restrictions and proper condensate disposal requirements.
AIR HANDLER INSTALLATION
The MB7 Series air handler is shipped ready for vertical upflow
installation and is approved for attic, basement, alcove/closet
or crawlspace installation with zero clearance to combustibles.
They may also be applied in downflow or horizontal left and right
discharge applications. See
for required
installation clearances.
This appliance is approved only for
indoor use.
NOTE:
For shipping purposes, the front and rear joining brackets
are located in the unit’s heater box. Remove these two items
from the heater box before beginning.
• The unit must be leveled at installation and attached to a
properly installed duct system.
• The surface that the air handler is mounted on must provide
sound physical support of the unit.
• The air handler must be installed so that all electrical
components are protected from water.
• If a louvered door is installed across the front of this unit, the
appliance must be mounted flush or behind front edge of
finished wall.
• Modular air handlers are intended to be mated with specific
C6 & C7 cased coils. Reference the Technical Specifications
for coil mating combinations.
Upflow Installation
MB7 series air handlers are shipped from the factory ready for
upflow configuration as shown in
. Return
air must must enter from the bottom of the unit.
1. Remove the bracket above the door of the cased coil. Retain
the screws for later use.
NOTE:
Before mating the modular
unit with the cased coil, clean the mating surfaces on both
Summary of Contents for MB7EM 3-PHASE Series
Page 23: ...23...