background image

6

Proper maintenance is important to achieve optimum performance from the furnace. This equipment should be inspected annually by a 
licensed HVAC technician. 

Table 1, (page 7)

 contains suggested inspections and frequency of maintenance. Routine maintenance 

should include the following:

BLOWER & FILTER

•  Never operate the furnace without a filter in place. Dust and lint 

can build up on internal components, resulting in loss of efficiency, 

equipment damage, and possible fire.

•  Keep air filters cleaned. Filters should be changed or cleaned 

monthly during the heating/cooling season. Clean or replace filter 

to maintain proper airflow and achieve maximum efficiency. Newly 

built or renovated homes may require more frequent changing 

until the construction dust has minimized. Filters designed to 

remove smaller particles such as pollen, may require additional 

maintenance.

•  It is recommended that the blower compartment be cleaned of 

dirt or lint that may have accumulated in the compartment or on 

the blower and motor as part of the annual inspection.

CONDENSATE DRAINAGE

•  This furnace produces liquid condensate which is slightly acidic. 

The vent pipe must be sloped upwards away from the furnace 

to properly drain the water back into the condensate disposal 

system.

•  Condensate drain tubes must maintain a downward slope to 

ensure proper drainage. Periodically inspect the condensate 

drain tube for proper drainage. Also, do not place heavy objects 

on the tubing that restricts the flow of condensate.

FURNACE & AIR DUCTS

•  Homeowners should perform frequent visual inspections of the 

furnace for obvious signs of deterioration. The furnace should be 

sound without sagging, cracks gaps, etc around the base. The 

return air duct connection(s) is secured and sealed to the furnace 

cabinet and terminates outside the area containing the furnace. 

Any signs of damage or loose connections should be repaired 

by a qualified HVAC technician.

•  Furniture and drapery should be arranged so that the supply air 

registers and return grilles are not obstructed.

VENTING SYSTEM

•  For proper and safe operation, the furnace needs air for combustion 

and ventilation. 

Do Not

 block or obstruct air openings on the 

furnace, or any air openings where the furnace may be installed, 

including any surrounding spaces.

•  Direct vent furnaces pull combustion air from the outdoors and 

vent combustion products back outside. Combustion air coming 

from the outside needs to be clean of chemicals that can cause 

corrosion, such as pool chlorinating products.

•  Vent pipe must slope upwards and be physically sound without 

holes or corrosion. Any corroded section of vent pipe must be 

replaced, and any obstruction or blockage must be removed by 

a licensed HVAC technician.

•  Flue passageways, the vent system, and the burners should be 

inspected and cleaned (if required) by a licensed HVAC technician 

annually to ensure continued safe operation.

If the furnace fails to operate check the following:

1.  Is the thermostat setting correct?

2.  Is the On / OFF switch (inside the blower compartment) turned 

on? See 

Figure 3, (page 8)

.

3.  Is the circuit breaker tripped?

4.  Is the gas turned on at the manual shutoff?

5.  Is the filter dirty or clogged?
If the furnace still doesn’t operate, contact a licensed HVAC 

technician.

MAINTENANCE INFORMATION

TROUBLESHOOTING

Summary of Contents for MG2R

Page 1: ...store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical sw...

Page 2: ...INFORMATION 5 ABOUT THE FURNACE 5 AIR FILTERS 5 THERMOSTAT 5 FURNACE IN A SMALL ROOM OR CLOSET 5 SOURCES OF CORROSION 5 WARRANTY INFORMATION 5 MAINTENANCE INFORMATION 6 BLOWER FILTER 6 CONDENSATE DRAI...

Page 3: ...CAUTION indicates a potentially hazardous situation that if not avoided may result in minor or moderate injury or property damage WARNING To avoid possible equipment damage fire or personal injury the...

Page 4: ...t scell es de mani re emp cher l infiltration de produits de combustion dans le b timent Veiller ce que la ou les sorties de l vent de l appareil de chauffage et la prise d air ne soient en aucune fa...

Page 5: ...ith applicable local codes having jurisdiction Thermostat connections should be made according to the instructions supplied with the thermostat and the indoor equipment The thermostat should be mounte...

Page 6: ...nt visual inspections of the furnace for obvious signs of deterioration The furnace should be sound without sagging cracks gaps etc around the base The return air duct connection s is secured and seal...

Page 7: ...valve outside the furnace 3 Turn electric to the furnace off 4 Open the door to the burner compartment 5 Set the gas valve ON OFF knob switch to the OFF position See Figure 2 for gas valve type and kn...

Page 8: ...served FURNACE COMPONENTS Figure 3 MG2R MG2S Furnace Components Blower Assembly Inducer Assembly Single Stage Gas Valve Gas Manifold Burner Assembly ON OFF Switch Control Board Limit Switch Inline Dra...

Reviews: