background image

4

Minimum Clearance Requirements

Sufficient clearance for unobstructed airflow through the outdoor 
coil must be maintained in order to provide room for proper 
servicing and achieve rated performance. See 

Figure 1

 for 

minimum clearances to obstructions.
Service Access Clearance:

Blower and electrical control access panels .............. 24”

Compressor compartment access panel ................... 24”

Clearance from top of unit  ........................................ 72”

Clearance around condenser coil area to

Wall or shrubs (excludes duct panel side) ................. 12”

Clearances to Combustibles:

Combustible base - wood or Class A, B, or C

roof covering material ................................................ 0”

Supply & return air ducts ........................................... 0”

Duct connection side ................................................. 0”

Air Duct System

Air ducts must be installed in accordance with the standards of 

the National Fire Protection Association “Standard for Installation 

of Air Conditioning and Ventilation Systems” (NFPA 90A), 

“Standard for Installation of Residence Type Warm Air Heating 

and Air Conditioning Systems” (NFPA 90B), these instructions, 

and all applicable codes. NFPA publications are available by 

writing to: National Fire Protection Association, Batterymarch 

Park, Quincy, ME 02269 or visit www.NFPA.org on the web.

•  Design the duct work according to methods described by the 

Air Conditioning Contractors of America (ACCA).

•  The supply duct system, including the number and type of 

registers, will have much more effect on the performance of 

the system than any other factor. The duct must be sufficiently 

large to conduct an adequate amount of air to each register. 

See 

Figure 2

.

•  Duct work should be attached directly to the unit flanges for 

horizontal applications.

Figure 2. Single & Multiple Duct Applications

MULTIPLE DUCT APPLICATION

SINGLE DUCT APPLICATION

•  For highly resistive duct systems it may be necessary to add 

an additional return air duct and or supply to achieve maximum 

performance and prevent coil icing and refrigerant flood back.

•  The air conditioning output of the system will not cool 

the home if air is lost to the outside through leaks in the 

duct system. Ducts that are collapsed or restricted by 

foreign objects will also prevent adequate air flow.

•  All duct work passing through unconditioned space must 

be properly insulated to minimize duct losses and prevent 

condensation. Use insulation with an outer vapor barrier. 

Refer to local codes for insulation material requirements.

24"

12"

24"

TO

P OF UNIT

TO

 BE

UNOBSTR

UCTED

0"

Figure 1. Minimum Unit Clearances

Summary of Contents for P94RD Series

Page 1: ...plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings co...

Page 2: ...te a degree or level of seriousness and should not be ignored WARNING indicates a potentially hazardous situation that if not avoided could result in personal injury or death CAUTION indicates a poten...

Page 3: ...om the airflow data found in Table 3 page 11 Place appropriate wire on the appropriate motor speed tap for the required airflow GENERAL INFORMATION This packaged air conditioner is designed only for o...

Page 4: ...visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of America ACCA The supply duct system including the number and type of registers...

Page 5: ...an open area equal to or greater than a 12 x 20 grille The return air grille can be placed in the wall of a closet and the air ducted into the filter box through a boxed in area at the closet floor le...

Page 6: ...w safety warnings exactly could resultinseriousinjury deathorpropertydamage Improper servicing could result in dangerous operation serious injury death or property damage Beforeservicing disconnectall...

Page 7: ...of the NEC ANSI NFPA 70 and with applicable localcodeshavingjurisdiction Thermostatconnectionsshould Low Voltage Line Voltage be made in accordance with the instructions supplied with the thermostat...

Page 8: ...t 24 hours prior to running After unit startup the compressor must run for a minimum of 12 hours Start Up Procedure CAUTION If the unit is equipped with a crankcase heater allow 24 hours prior to cont...

Page 9: ...rical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The unit may have more than one electrical supply Proper maintenance is im...

Page 10: ...3 Ton 2 B 5 5 3 Opening for 12 Diameter Supply Duct Opening for 12 Diameter Return Duct A 17 50 8 9 1 B 8 A 5 5 3 17 50 9 2 9 1 Opening for 14 Diameter Return Duct Opening for 12 Diameter Supply Duct...

Page 11: ...252 25 1210 26 1161 27 1120 28 1071 30 1013 31 954 33 Tap T3 1460 22 1 415 22 1385 23 1335 24 1275 25 1 225 26 1 170 27 1120 28 Tap T4 1618 20 1 580 20 1543 20 1508 21 1478 21 1 443 22 1 388 23 1 345...

Page 12: ...EQUALIZATION VALVE 24V C R E Y2 Y1 W2 O G 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre F...

Page 13: ...C T STAT TERMINAL 24V GREEN 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LE...

Page 14: ...14...

Page 15: ...15...

Page 16: ...O Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO Rated Voltage __________________________________________________...

Reviews: