8

Blower Speed

For optimum system performance and comfort, it may be 

necessary to change the factory speed setting. See 

Table 3, 

(page 11)

 for factory settings.

 WARNING:

To avoid electric shock, personal injury, or death, 

turn off the electric power at the disconnect or the 

main service panel before making any electrical 

connections.

 CAUTION:

Label all wires prior to disconnection when 

servicing controls. Wiring errors can cause 

improper and dangerous operation. Verify proper 

operation after servicing.

 CAUTION:

To avoid personal injury or property damage, 

make certain that the motor leads cannot come 

into contact with any metal components of the 

unit.

1. Disconnect all electrical power to the unit and remove the 

service panel.

2. Locate the orange and red wires terminated to the blower 

motor. 

NOTE: 

The orange wire controls cooling operation 

and the red wire controls the heating operation.

3. Verify the required speed from the airflow data found in 

Table 

3, (page 11)

. Place appropriate wire on the appropriate 

motor speed tap for the required airflow.

4. Check all factory wiring as shown in the wiring diagram and 

inspect the connections to make sure none of them loosened 

during shipping or installation.

START UP & ADJUSTMENTS

Pre-Start Checklist

The following check list should be observed prior to starting 

the unit.

  Verify the unit is level and allows proper condensate drainage.

 Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/control 

panels are in place. Unit must be installed with the proper 

clearances shown in 

Figure 1 (page 4)

.

  Verify that the duct work is sealed to prevent air leakage.

  Verify that the line voltage power leads are securely connected 

and the unit is properly grounded. Check the condenser fan 

to make sure it turns freely.

  Verify the thermostat is wired correctly and installed in a 

proper location. Make sure the low voltage wires are securely 

connected to the correct leads on the low voltage terminal 

strip.

 Verify that the power supply branch circuit overcurrent 

protection is sized properly.

  To achieve rated capacity and efficiency the compressor must 

be exposed to refrigerant for at least 24 hours prior to running. 

After unit startup, the compressor must run for a minimum of 

12 hours.

Start-Up Procedure

 CAUTION:

If the unit is equipped with a crankcase heater, 

allow 24 hours prior to continuing the start up 

procedures to allow for heating of the refrigerant 

compressor crankcase. Failure to comply may 

result in damage and could cause premature 

failure of the system. This warning should be 

followed at initial start up and any time the power 

has been removed for 12 hours or longer.

The control circuit thermostat may consist of an anti-short cycle 

timer that will not let the compressor re-start before 5 minutes 

have elapsed.

1. Set the system mode to OFF and the temperature mode to 

its highest setting.

2. Turn power on at the disconnect switch.

3. Set the system mode to ON or COOL.

4. Set the temperature mode below room temperature. Verify 

that the indoor blower, outdoor fan, and compressor energize 

and the cooling function starts.

5. Verify the discharge air grilles are adjusted and the system 

air is balanced.

6. Verify the duct work has no air leaks.

7. Verify the condensate drain is installed correctly and functions 

properly.

8. Set the temperature mode above room temperature. The unit 

should stop.

9. Instruct the homeowner on unit and thermostat operation and 

filter servicing.

Air Circulation

Leave the thermostat system mode on OFF, and set the fan 

mode to ON. Blower should run continuously. Check the air 

delivery at the supply registers and adjust register openings for 

balanced air distribution. Examine ducts for leaks or obstruction 

if insufficient air is detected.
Set the thermostat fan mode to AUTO. The blower should stop 

running.

System Cooling

Set the thermostat’s system mode to COOL and the fan mode 

to AUTO. Lower the thermostat temperature selector below the 

existing room temperature. Allow the cooling system to operate 

for several minutes and check for the discharge of cool air at 

the supply registers.

System Heating

(Available only when Electric heat is supplied) Set the 

thermostat’s system mode to HEAT and the fan mode to either 

AUTO (intermittent air) or to ON (continuous air). Raise the 

thermostat’s temperature selector above the existing room 

temperature and check the following:
1. The compressor and outdoor fan should not run.

2. The blower will run according to the thermostat’s fan mode 

setting.

Summary of Contents for P94RD Series

Page 1: ...plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings co...

Page 2: ...te a degree or level of seriousness and should not be ignored WARNING indicates a potentially hazardous situation that if not avoided could result in personal injury or death CAUTION indicates a poten...

Page 3: ...om the airflow data found in Table 3 page 11 Place appropriate wire on the appropriate motor speed tap for the required airflow GENERAL INFORMATION This packaged air conditioner is designed only for o...

Page 4: ...visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of America ACCA The supply duct system including the number and type of registers...

Page 5: ...an open area equal to or greater than a 12 x 20 grille The return air grille can be placed in the wall of a closet and the air ducted into the filter box through a boxed in area at the closet floor le...

Page 6: ...w safety warnings exactly could resultinseriousinjury deathorpropertydamage Improper servicing could result in dangerous operation serious injury death or property damage Beforeservicing disconnectall...

Page 7: ...of the NEC ANSI NFPA 70 and with applicable localcodeshavingjurisdiction Thermostatconnectionsshould Low Voltage Line Voltage be made in accordance with the instructions supplied with the thermostat...

Page 8: ...t 24 hours prior to running After unit startup the compressor must run for a minimum of 12 hours Start Up Procedure CAUTION If the unit is equipped with a crankcase heater allow 24 hours prior to cont...

Page 9: ...rical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The unit may have more than one electrical supply Proper maintenance is im...

Page 10: ...3 Ton 2 B 5 5 3 Opening for 12 Diameter Supply Duct Opening for 12 Diameter Return Duct A 17 50 8 9 1 B 8 A 5 5 3 17 50 9 2 9 1 Opening for 14 Diameter Return Duct Opening for 12 Diameter Supply Duct...

Page 11: ...252 25 1210 26 1161 27 1120 28 1071 30 1013 31 954 33 Tap T3 1460 22 1 415 22 1385 23 1335 24 1275 25 1 225 26 1 170 27 1120 28 Tap T4 1618 20 1 580 20 1543 20 1508 21 1478 21 1 443 22 1 388 23 1 345...

Page 12: ...EQUALIZATION VALVE 24V C R E Y2 Y1 W2 O G 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre F...

Page 13: ...C T STAT TERMINAL 24V GREEN 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LE...

Page 14: ...14...

Page 15: ...15...

Page 16: ...O Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO Rated Voltage __________________________________________________...

Reviews: