72
Media Application Server platform
IBM eServer BladeCenter power requirements
Table 19 "IBM eServer BladeCenter power, heat cooling and sound
specifications" (page 72)
lists the power, heat, and cooling specifications
that apply to this platform.
Table 19
IBM eServer BladeCenter power, heat, cooling, and sound specifications
Specification
Values
Electrical Input
Input voltage
minimum 200 volt AC and maximum
240 volt AC
Power supply
1200 watts or greater
Sine-wave
50-60 Hz single phase
Heat emissions
Minimum
configuration
1365 BTU/hour (400 watts)
Maximum
configuration
9622 BTU/hour (2820 watts)
Cooling
Redundant
cooling
Two variable-speed hot-swappable
blowers
Sound emissions
without acoustic
module option
Sound power, idle: 7.4 bels maximum.
Sound power, operating: 7.4 bels
maximum
with acoustic
module option
Sound power, idle: 6.9 bels maximum.
Sound power, operating: 6.9 bels
maximum
IBM eServer BladeCenter T power requirements
This table shows the
Table 20 "IBM eServer BladeCenter T power, heat,
cooling, and sound specifications" (page 72)
that apply to the BladeCenter
T platform.
Table 20
IBM eServer BladeCenter T power, heat, cooling, and sound specifications
Specification
Values
Input voltage
minimum 200 volt AC and maximum 240 volt
AC
Power supply
1300 watts or greater
Electrical Input
Sine-wave
50-60 Hz or greater
Minimum configuration
673 BTU/hour (197 watts)
Heat emissions
Maximum configuration
12640 BTU/hour (3707 watts)
Cooling
Redundant cooling
Four variable-speed hot-swappable blowers
Sound emissions
Normal operations
Sound power, upper limit: 7.8 bels maximum
Nortel Media Application Server
Media Application Server Planning and Engineering
NN42020-201
01.04
Standard
4.0
27 July 2007
Copyright © 2007, Nortel Networks
.