Chapter 3 — System and site requirements
Page 35 of 536
Option 11C Compact
Planning, Installation, Fault Clearing and CCBR Guide
Auxiliary equipment power
Terminals, printers, modems, and other data units used in conjunction with
the Option 11C Compact system require special wiring considerations.
Power for system equipment in the switch room must:
•
be powered from the same panel or transformer as the Option 11C
Compact system
•
be grounded to the same panel or transformer as the Option 11C Compact
system
•
be tagged at the panel to prevent unauthorized interruption
•
not be controlled by a switch between the breaker and the equipment.
Service receptacles for the system and associated equipment should be:
•
of the isolated ground type, such as NEMA IG5-15
•
rated for 120 or 240 V, 15 or 20A, 50-60 Hz, 3-pole, 3-wire, grounded
•
grounded to the same location so as to form a Single Point Ground.
Summary of Contents for Meridian Meridian 1
Page 3: ...553 3121 210 Standard 3 0 January 1999 ...
Page 17: ...xiv Contents 553 3121 210 Standard 3 0 January 1999 ...
Page 97: ...Page 78 of 536 Chapter 8 Installing a new system 553 3121 210 Standard 3 0 January 1999 ...
Page 107: ...Page 88 of 536 Chapter 10 Installing the system ground 553 3121 210 Standard 3 0 January 1999 ...
Page 113: ...Page 94 of 536 Chapter 11 Installing the power supply 553 3121 210 Standard 3 0 January 1999 ...
Page 125: ...Page 106 of 536 Chapter 12 Adding an expansion cabinet 553 3121 210 Standard 3 0 January 1999 ...
Page 209: ...Page 190 of 536 Chapter 18 Connecting the trunks 553 3121 210 Standard 3 0 January 1999 ...
Page 323: ...Page 304 of 536 Chapter 21 Installing Hospitality 553 3121 210 Standard 3 0 January 1999 ...
Page 419: ...Page 400 of 536 Chapter 23 Pre programmed data 553 3121 210 Standard 3 0 January 1999 ...
Page 555: ...Page 536 of 536 Chapter 25 Fault locating and clearing 553 3121 210 Standard 3 0 January 1999 ...