Chapter 10 – Installing the system ground
Page 87 of 536
Option 11C Compact
Planning, Installation, Fault Clearing and CCBR Guide
3
Install a #6 AWG ground wire from the remaining ground lug in
the main cabinet to a suitable ground source (the ground bus in
the AC power service panel).
4
Place a DO NOT DISCONNECT tag on the ground wire at the
service panel.
—————————— End of Procedure ——————————
Figure 17
Ground lugs in the NTMW08 cabinet
WARNING
The connection in the AC power service panel should be performed by
a qualified technician or electrician.
Ground Lugs