Trouble locating and clearing procedures (continued) 1-91
DMS-100 Family NA100 Trouble Locating and Clearing Procedures Volume 2 of 2 LET0015 and up
Replacing a 3.5 in. disk drive unit
NTFX32BA
(continued)
At the MAP terminal
20
To manually busy the DDU, type
>BSY
and press Enter.
Example of a MAP display:
21
To start the DDU, type
>START
and press Enter.
Example of a MAP response:
22
To test the DDU, type
>TST
and press Enter.
Example of a MAP display:
23
To perform volume allocation tests, follow the procedure
Allocating test
volumes on 8-in., 5.25-in., or 3.5 in. DDUs in Routine Maintenance
Procedures. When the procedure is complete, return to this point.
24
To perform interference and file transfer tests, follow the procedure
Performing DDU interference and file transfer tests in Routine Maintenance
Procedures. When the procedure is complete, return to this point.
25
To access the CI level of the MAP display, type
>QUIT ALL
and press Enter.
If the BSY command
Do
passed
step 21
failed
step 38
If the TST command
Do
passed
step 23
failed
step 38
bsy
OK
Disk start successful
Process may take up to 3 minutes.
Test OK