background image

VGZ-003 / 20120327.0  

 

PB65XL / 

Page 5

36"

CORNER CLEARANCES

36"

LOCATING STOVE

Proper clearances must be maintained for ad-
equate air circulation. Adequate ventilation must be  
provided while operating this stove.
1.  The stove must be placed on solid con-

crete, solid masonry, or when installed on a  
combustible floor a solid surface floor protector 
listed to UL1618 Type 2 with a minimum of 1˝ thick 
and a R-value of 3.0 or greater, such as Hy-C or 
Imperial Model UL 5463BK must be used. (NOTE: 
To calculate R-values of equivalent alternative 
materials, see page 15). The base must extend 
at least 18” beyond the front, rear and sides of 
the stove, and 

must  extend underneath and 2˝ 

beyond each side of horizontal connector pipe if it 
is elbowed towards a wall (see figure 5 and consult 
local building codes and fire protection ordinances.)

2.  The stove must have its own flue. 

DO NOT CON-

NECT THIS UNIT TO A CHIMNEY FLUE SERVING 
OTHER APPLIANCES.

3.  After observing the clearances to combus-

tible materials (figure 2 – 4), locate your floor  
protector accordingly (figure 2) and careful-
ly place the stove in your selected location.   
Install stove pipe, elbows, and thimble as  
required, utilizing either a recently cleaned and 
inspected 6˝/152mm masonry chimney or a 

FLOOR

PROTECTOR

DASHED LINE SHOWS

HORIZONTAL CHIMNEY

CONNECTOR AND

ADDITIONAL FLOOR

PROTECTION REQUIRED

BACKWALL

54"

(TOP VIEW)

36"

18"

18"

18"

36"

63"

18"

SIDEWALL

COMBUSTIBLE

CONSTRUCTION 

ACCORDING TO

NFPA 211

COMBUSTIBLE

CONSTRUCTION 

ACCORDING TO

NFPA 211

6˝/152mm i.d. ma nu fa cured chimney system listed 
to UL 103 HT. Maximum 64 square inches.

4.  Use 6˝/152mm diameter minimum 24 MSG Black  

or 26 MSG Blue round stove pipe. DO NOT USE 
GALVANIZED duct pipe. Secure pipe sections with 
three (3) sheet metal screws in each stove pipe 
and/or elbow joint to firmly hold the pipe sections 
together.  Screws may be no more than a maxi-
mum of 3˝/76mm apart. 

DO NOT CONNECT THIS 

STOVE TO ANY AIR DISTRIBUTION OR DUCT 
SYSTEM.

5.  R e c h e c k   c l e a r a n c e s   f r o m   t h e   s t o v e ,  

connector stove pipe, and corner clearances 
using the illustrations (figure 2, 3 & 4) and  
your local building codes or fire protection  
ordinances.  

 

NOTE: Drywall faced with brick or stone MUST be 
considered a combustible surface.

6. 

DO NOT INSTALL THIS STOVE IN A MOBILE 
HOME,  MANUFACTURED HOME, TENT OR 
TRAILER. (NO EXCEPTIONS)

7.  T h e   c l e a ra n c e s   p r ov i d e d   a r e   m i n i mu m  

dimensions. Installation of this stove must  
comply with your local building code rulings.

8.  This stove is NOT a UL listed stove.

Continued on next page

Fig. 2      Minimum Clearance Dimensions from Combustible Surfaces      Fig. 3

MINIMUM CLEARANCES

TO COMBUSTIBLE SURFACES

Unit to Sidewall .......................................................36 inches
Unit to Backwall ......................................................36 inches
Unit Corner to Wall .................................................36 inches
Pipe Connector to Backwall ..................................38 inches
Pipe Connector to Ceiling ......................................18 inches

Fig. 4 – Top View

 Minimum Corner Clearances from  

Combustible Surfaces

Call us at 1-866-667-8454 

NorthlineExpress.com

www.NorthlineExpress.com

Summary of Contents for RAILROAD POTBELLY PB65XL

Page 1: ...T A UL LISTED STOVE NOTE IT IS RECOMMENDED INSTALLATION BE COMPLETED BY A QUALIFIED HEATING EQUIPMENT INSTALLER DO NOT INSTALL IN A MOBILE HOME REFER TO MARKINGS ON STOVE LABELS FOR ADDITIONAL INFORMATION SAFETY NOTICE IF THIS STOVE IS NOT PROPERLY INSTALLED A HOUSE BUILDING FIRE MAY RESULT FOR YOUR SAFETY CONTACT LOCAL OR MUNICIPAL BUILDING OR FIRE OFFICIALS ABOUT PERMITS RESTRICTIONS AND INSTALL...

Page 2: ...g Heating Appli ance Chimney Use a 6 152mm diameter chim ney that is high enough to give a good draft See specifics in Chimney Connections instructions 11 Be sure that your chimney is safely constructed and in good repair Have the chimney inspected by the fire department or a qualified inspector Your insurance company should be able to recommend a qualified inspector Chimney connector pipe must be...

Page 3: ...LTED IF YOU HAVE QUESTIONS REGARDING THE INSTALLATION OF THIS SOLID FUEL BURNING APPLIANCE 18 This stove has a painted surface which is durable but it will not stand rough handling or abuse When installing your stove use care in handling 19 Clean exterior with soap and warm water when stove is not hot Do not use any acids or scouring soap as these solvents wear and dull the finish 20 CLEAN STOVE F...

Page 4: ...efore the stove is used a Drill two 1 4 holes centered on either side of the pipe section 6 from the top end of the pipe figure 1 b Remove the handle from the damper then slide the damper into the pipe c Align the damper with the holes drilled in step 9a and insert the handle through the holes and the damper NOTE THIS DAMPER IS NECESSARY FORTHE PROPER OPERATION OF THE STOVE AND TO MEET EPA EMISSIO...

Page 5: ...KWALL 54 TOP VIEW 36 18 18 18 36 63 18 SIDEWALL COMBUSTIBLE CONSTRUCTION ACCORDING TO NFPA 211 COMBUSTIBLE CONSTRUCTION ACCORDING TO NFPA 211 6 152mm i d ma nu fa cured chimney system listed to UL 103 HT Maximum 64 square inches 4 Use 6 152mm diameter minimum 24 MSG Black or 26 MSG Blue round stove pipe DO NOT USE GALVANIZED duct pipe Secure pipe sections with three 3 sheet metal screws in each st...

Page 6: ...vepipe in stallation The use of more than two 90 degree bends may decrease the amount of draw and possibly cause smoke spillage Where pos sible use only corrugated nonadjustable elbows These provide a better seal 7 The connector pipe must not pass through an attic or roof space trusses closet or any concealed space or floor ceiling wall or com bustible construction See Chimney Connector NOTE CONNE...

Page 7: ...ve an adverse effect on the draft The manufacturer cannot be held responsible for external factors leading to less than optimal drafting Should you have a problem with inadequate draft you should contact a licensed heating and cooling contractor for assistance in solving the problem IMPORTANT Installation Points 1 Size chimney flue to stove collar This stove requires a 6 diameter flue 2 Never conn...

Page 8: ...or www mtlfab com VENTING TO EXISTING FIREPLACE In some instances people desire to convert an ex isting fireplace for stove use Usually safe connection to an existing masonry chimney requires more work than using a prefabricated chimney The existing fireplace must be closed and sealed at the damper with high temperature caulk ceramic wool or furnace cement Prior to installation clean and inspect t...

Page 9: ...nto the chimney 24 below the ceiling should insure proper clearance for a 6 stovepipe 2 Install a metal or fire clay 5 8 minimum thickness thimble Make sure the thimble is flush with the inner surface of the chimney liner and does not protrude into the flue see figure 8 on page 6 3 Secure the thimble with refractory mortar The thimble should be surrounded by 12 of solid unit masonry brickwork or 2...

Page 10: ...2mm of glass fiber insulation Opening shall be covered and thimble supported with a sheet steel support minimum 24 gauge in thickness D Chimney Section Pass through Solid insulated listed factory built chimney length with an inside diameter 2 51mm larger than the chimney connector and having 1 25 4mm or more of insulation serving as a pass through for a single wall sheet steel chimney connector of...

Page 11: ... 16 should be air dried sea soned for a minimum of 6 months Logs greater than 6 in diameter should be split Wood should be stored in a dry well ventilated area The humidity content for usable firewood must be less than 20 of the weight of the log Attempts to use wet or unseasoned wood will cause ignition problems rapid creosote build up with possible chimney fire incomplete combustion low heat yie...

Page 12: ...s 14 page 2 CHIMNEY DRAFT Draft is a function of the chim ney not the stove do not expect the stove to draw Smoke spillage into the house or excessive buildup of condensation or creosote in the chimney are warnings that the chimney is NOT functioning properly Correct the problem before using the stove Following are some possible causes for improper draft 1 The connector stovepipe may be pushed int...

Page 13: ...E HOUSE 3 CALL THE FIRE DEPARTMENT SOOT Formation need for Removal CAUTION RISK OF FIRE When coal is burned the products of combustion combine with moisture to form a soot residue which accumu lates in the flue lining When ignited this soot makes an extremely hot fire The chimney connector and chimney should be inspected at least once every two months during the heating season to determine if a so...

Page 14: ... parts Part No Description Qty 1 Cook Lid 1 2 Lid Lifter 1 3 Collar Top 1 4 Top Plate 1 5 Upper Chamber 1 6 Feed Chamber 1 7 Feed Door 1 8 Spin Draft 1 9 Spring Handle 1 10 Burn Chamber 1 11 Shaker Door 1 Part No Description Qty 12 Shaker Grate 1 13 Lower Chamber 1 14 Base 1 15 Leg 4 16 Ash Door 1 17 Slide Draft 1 18 Slide Draft Knob 1 19 Ash Drawer 1 20 Draft Damper for pipe installation 1 21 Har...

Page 15: ...lculate R value of proposed material s b For multiple layers add R values of each layer to determine overall R value 3 If the overall R value of the floor protector system is equal to or greater than the floor protector specifications given the alternate is acceptable Definitions Thermal conductance C BTU W hr ft2 F m2 K Thermal conductivity k Btu inch W Btu hr ft2 F m K hr ft F Thermal resistance...

Page 16: ...n good health Respectfully yours Proprietor Vogelzang International Corporation 400 West 17th Street Holland Michigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 COMPANY TESTIMONY FOR GOD SO LOVED THE WORLD THAT HE GAVE HIS ONLY BEGOTTEN SON THAT WHOEVER BELIEVES IN HIM SHALL NOT PERISH BUT HAVE ETERNAL LIFE JOHN 3 16 MADE IN CHINA DO NOT INSTALL THIS STOVE IN A MOBILE HOME MAN...

Reviews: