7.
Pull the batteries out. Start with battery No. 3.
8.
When pulling out battery No. 2, remove the battery temperature
sensor if installed.
9.2
I
NSTALLING
B
ATTERIES
Install the battery blocks on the shelves. Start with battery block no. 1 at
the position most to the left on the shelf.
Fit the temperature sensor into the temperature sensor holder and install
battery block no. 2.
Install battery block no. 4 most to the right on the shelf.
Install battery block no. 3.
The distances between the battery blocks are normally given by the inter
connections and the spacers.
To ensure necessary air circulation around the battery blocks it is
important to keep a minimum distance of 7 mm between the battery
blocks.
The distance between the wall and the outer battery block will be approx.
35 mm in Cabinets without EQ Zone 4 reinforcement and approx. 30 mm
in EQ Zone 4 Cabinets.
Figure 16 Placement of Batteries