Standard Duty Double Lever Arm Application for Frame Reveals to 6-7/8” (175mm)
Stop (Push) Side of Door Installation For Handed (Not Reversible) Units
Door Openings 85° to 110° Use Series 6920 / 6921
Door Openings 111° to 180° Use Series 6930 / 6931
80-9369-0120-020 (09-08 )
Right Hand Door
Left Hand Door
80-9369-0120-020 (09-08)
WARNING
120 VOLT POTENTIAL PRESENT. MAKE SURE
POWER IS TURNED OFF DURING
INSTALLATION PROCEDURE.
An incorrectly installed or improperly
adjusted door operator can cause property
damage or personal injury. These
instructions should be followed to avoid the
possibility of misapplication or
misadjustment.
CAUTION
CAUTION
AmericansWith Disabilities Act (A.D.A.)
ANSI Standards
ANSI A117.1
providing
accessibility and usability for physically
handicapped people"
• ANSI A156.19
"for power assist and low energy power
operated doors"
U.L. Listing
Underwriters Laboratories, Inc. listed for use on
fire and smoke barrier door assemblies when the
120VAC (60Hz) power input is supplied through
the normally closed alarm contacts of a
compatible U.L. Listed alarm system or alarm
panel.
These door operators can be installed and adjusted to conform with
A.D.A. regulations.
– These door operators permit door
assemblies to conform to the requirements of this
specification "for buildings and facilities –
.
– These products are designed to conform to this
specification
.
– "PAS" Function is designed to meet or exceed all of the
requirements for the "Power Assist Door".
– "POR" Function is designed to meet or exceed all of the
requirements for the "Low Energy Power Operated Door".
C
US
UL
®
6900 PowerMatic
®
Low Energy Power Operator
Installation Instructions
Activation Modes (Modes are configured during installation.)
• Selectively Activated Mode -
• Automatically Activated Mode -
Functions (Functions are configured during installation.)
• Power Assist function (PAS)
unit depends upon external
switches or scanners for activation of functions.
unit will operate
utilizing on-board
ELS switching that automatically activates the functions. External
switches or scanners may also be used for activation.
– The unit operates as a standard
door closer unless activated via one of the Modes listed above.
Upon activation the door opening resistance is reduced, for a
selected period of time, well below A.D.A. guidelines. When the
time period expires, the door closes under normal door closer
spring power.
with a slight
movement of the door toward the open position
– The unit performs as a low
energy power door operator. Field settings allow for following two
functions:
1. Selectively Activated Mode (See Above).
2. Automatically Activated Mode (See Above).
• Power Operator function (POR)
NOTE: The
are factory set in the
as a
ELS Board Dip Switches
Selectively Activated Mode
Power Operator Function.
Basic Requirements
Parts Identification
Installation Template
Installation Sequence
Regulation & Adjustment
General Product Information
Function and Operation Sequence
ELS “Timing” Calibration
ELS Reset Instructions
Troubleshooting
2
2
3
4
5
6
6
7
8
8