background image

80-9369-0120-020 (09-08)

• U.L. labeled fire or smoke barrier door assemblies require that
the 120VAC (60Hz) power input to the PowerMatic™ door
operator be supplied through normally closed alarm contacts of
the alarm system/alarm panel.

• Power input to PowerMatic door operator must be 120 VAC

(60Hz) to terminals HOT and COM at terminal strip T1. Terminal
GND is earth ground.

• All wiring must conform to standard wiring practice in

accordance with national and local wiring codes.

• Note: Unless otherwise noted, all dimensions are given in

inches (millimeters).

• Minimum frame face 2" (51mm).

• Minimum ceiling clearance 4-1/8” (105mm).

• Minimum suggested and required material thickness for hollow

metal frames (skin plus reinforcement) is charted on page 3.

• For wiring refer to Wiring Instruction 80-9369-0901-020.

• Hand of unit and hand of door must be the same. Hand of unit is

not reversible.

• Door must be hung on butt hinges [5" (127mm) max. width] or

3/4" (19mm) offset pivots. A separate door and frame
preparation template will be supplied for other conditions.

• Door thickness must be 1-3/4" (44mm) minimum, 2-1/4" (57mm)

maximum.

• Door must swing freely through the entire opening and closing

cycle before beginning the installation.

• Use of a supplemental door stop is always recommended.

Requirements

2

SC

SC

XX

XX

XX

PAS

DN

T2

T1

Sw3
ELS

Dip

Switches

Pinion Timing

Pulley

Timing Belt

ELS Board w/

ELS Board Pulley

ELS Board

LED

JP2

Terminal

Strip

Rotary Switches / Timer Pots

See Pages 2 and 4 of

Wiring Instructions
80-9369-0901-020

1

2

3

4

OFF

ON

Sw1

Dip

Switches

Main Board

Bracket for

Input Power

Terminal Strip

T1

Jp1

Terminal

Strip

Jp4

Terminal

Strip

Jp5

Terminal

Strip

Jp3

Terminal

Strip

(Sc) Speed

Control Valve

Solenoid

Door Calibrate

Close Position

Door Calibrate

Open Postion

11/16” Power

Adjustment Nut

Hand

Marking

(B)

Backcheck

Valve

(S)

Sweep

Speed Valve

(L)

Latch

Speed Valve

Selector Mode

Switch

“OFF” “ON” “H/O”

(P)

Backcheck

Position Valve

(PA)

Pressure

Adjustment Valve

11/16" Power

Adjustment Nut

S

L

PA

Summary of Contents for 6900 PowerMatic

Page 1: ...ceed all of the requirements for the Power Assist Door POR Function is designed to meet or exceed all of the requirements for the Low Energy Power Operated Door C US UL 6900 PowerMatic Low Energy Power Operator Installation Instructions Activation Modes Modes are configured during installation Selectively Activated Mode Automatically Activated Mode Functions Functions are configured during install...

Page 2: ...ng on butt hinges 5 127mm max width or 3 4 19mm offset pivots A separate door and frame preparation template will be supplied for other conditions Door thickness must be 1 3 4 44mm minimum 2 1 4 57mm maximum Door must swing freely through the entire opening and closing cycle before beginning the installation Use of a supplemental door stop is always recommended Requirements 2 SC SC XX XXXX PAS DN ...

Page 3: ...ameter x 1 3 4 45mm long sex nut WARNING Make sure that 120V 60Hz input power is turned off before proceeding with installation 1 2 13 5 16 8 7 1 4 184 1 11 16 43 1 7 16 37 5 8 16 3 8 10 4 0 102 A 11 1 2 292 17 5 16 440 23 7 8 606 26 0 660 3 8 10 1 1 4 32 Notes Do not scale drawing Left hand door shown All dimensions are given in inches mm Thickness recommended for reinforcements in hollow metal d...

Page 4: ...ven 7 two 2 ConcealedWired Units Only Surface Wired Units Only NOTE before Installation Sequence Fasten arm slide and shoe assembly to the door with the long end of arm shoe away from the hinge Slide the main arm onto the pinion shaft of the door control unit at a 90 angle to the door control unit and frame Align arm mark S with the flat corner of the pinion shaft square see illustration above rig...

Page 5: ...Backcheck B valve as necessary for hydraulic resistance to door opening in the backcheck range See illustration on Page 2 1 8 Hex Key Slower Closing Faster Closing Closing Cycle Closed 10 L a t c h R a n g e S weep Range 1 8 Hex Key Increase Cushion Decrease Cushion Opening Cycle Backcheck O p e n i n g Length of Time Seconds Setting 0 2 5 10 15 20 25 30 0 1 2 3 4 5 6 7 If desired install No 668 S...

Page 6: ... power cycle starts 3 Read the EXSOL DLY rotary switch timer pot to determine how long solenoid should be energized or de energized depending upon function required 4 Read th SW1 2 A D dip switch to determine how long solenoid should be energized 5 Read the M DLY rotary switch timer pot to determine how long before the pump motor and solenoid valve tu n on 6 When ELS board reaches upper taught lim...

Page 7: ...AD STEPS COMPLETELY BEFORE PROCEEDING The ELS board is calibrated Timed to appropriate starting zone at the factory During a normal installation this procedure is not required If for any reason the ELS Board was removed or the ELS Board Pulley is turned without the pinion turning it is likely the ELS board will need to be re calibrated timed The ELS board may be timed while unit is mounted to the ...

Page 8: ...eck SC Speed Control Valve setting Door may be opening too slowly Turn SC valve clockwise to increase speed 4 There may be wind or some other positive pressure present Adjust Obstruction Sensitivity to a longer time setting See page 7 PowerMatic Motor turns on and re activates door before it reaches jam or closed position a This could be caused by the unit sensing an obstruction on Closing 1 Check...

Reviews: