Userguide CableTroll 210 March 2020 

01021000/11/12/13

 

8. Test and Reset 

 

8.1 Test-Reset Button: 

The function of the Test-/Reset button is dependent of operating mode (idle- or indication mode) and of 
how long the Test-/Reset button is pressed. 
 

When EFI in Idle Mode: 
 
Less than 1 sec press:  

 

Alternating Amber/Red and Green LED: Indicate battery status OK. 

 

Only Amber/Red LED: Indicate battery status below 20%. 

 

Press between 1 sec and 5 sec: 
Press the test/Reset button less than 1 sec:

 

The indicator shows status of Auto Reset signal from the CT/sensor:  

 

Auto Reset from sensor Inactive: Fault LED flashes rapidly in burst

 

 

 

Auto Reset from sensor Active: Fault LED illuminates constant.   

 

Press longer than 5 sec: 

Simulated fault indication with both relays closed for 15 min. 
SCADA reset possible. Manual reset with button also possible. 
Auto Reset (230 VAC- or Sensor-Reset) not possible. 

 

When EFI in Indication Mode: 

If the EFI is in indication mode (after a fault), a press on the Test-/Reset button will reset indication and 
EFI will go back to idle mode. 

 

8.2 Remote reset 

Reset is immediately after 2 sec pulse of 9-110VDC supervisory reset from a SCADA RTU.  
 

8.3 Auto reset 

Automatic reset by voltage (230VAC) or from Rogowski coil/CT (imbalance 

˃ 3A) if dip 8 is enabled. 

Reset time is 15 seconds. 
  

 

 

Summary of Contents for 01021000

Page 1: ...Userguide CableTroll 210 March 2020 010121000 11 12 13 CableTroll 210 User Guide for product nr 01021000 11 12 13...

Page 2: ...updated 6 20 09 19 Programming table updated 7 25 09 19 Technical drawing with dimensions updated 8 15 09 19 Updated with Rogowski coil sensor 9 28 01 20 Pictures updated with black Rogowski coil 10...

Page 3: ...6 3 2 CAPACITIVE DISCHARGE CURRENTS 6 3 3 EARTH FAULT DETECTION 7 4 APPLICATION MOUNTING 8 4 1 SENSOR MOUNTING 8 5 BATTERY STATUS 8 5 1 LOW BATTERY LITHIUM BATTERY 8 5 2 TO REPLACE THE BATTERY 9 5 3 R...

Page 4: ...and suitable for use in tropical weather conditions with high humidity of 65 to 95 The CableTroll 210 will indicate earth faults locally by a flashing diode and remotely through a relay contact 1 1 De...

Page 5: ...closed NC Pulse relay may be available from factory on request 2 4 Rogowski coil Current Transformer CT Earth fault element The indicator uses one direct type Rogowski coil for detection of earth faul...

Page 6: ...rough the sensor element seen from the feeder The capacitive discharge current from behind the Rogowski coil CT earth fault element must not exceed the trip level setting of the indicator The capaciti...

Page 7: ...e met Ic It where Ic capacitive current down stream of the indicator It CableTroll 210 programmed trip level sensitivity To estimate the capacitive discharge current at any line point you must calcula...

Page 8: ...e indicator erroneously Product number 01021000 11 12 13 Rogowski Coil Current Transformer Mounting 5 Battery Status 5 1 Low battery Lithium battery When there is less than 20 remaining capacity on th...

Page 9: ...en replaced the battery counter must be reset This is done by pushing the Test Reset button and hold it pressed for more than 30 seconds Observe the following sequence Push the Test Reset button and h...

Page 10: ...ion diagram CT210 Terminal from left 1 Mains reset 220 240VAC 2 Mains reset 220 240VAC 3 SCADA reset 9 110VDC Hot 4 SCADA reset 9 110VDC Ground 5 LED 6 Red 6 LED 6 Black 7 Earth fault Relay 1 NC1 8 Ea...

Page 11: ...fixed trip level 0 0 1 160A fixed trip level 1 0 1 240A fixed trip level Table 1 Switch setting overview trip level NOTE NORTROLLs Earth Fault Indicator and Earth Fault Element are tuned in to consti...

Page 12: ...urs 0 1 16 hours 1 1 32 hours Table 3 Switch overview reset time settings 7 4 Setting Auto reset Select Auto Reset with switch number 8 0 OFF 1 ON 8 Auto reset 0 Auto reset Disabled 1 Auto reset Enabl...

Page 13: ...the CT sensor Auto Reset from sensor Inactive Fault LED flashes rapidly in burst Auto Reset from sensor Active Fault LED illuminates constant Press longer than 5 sec Simulated fault indication with bo...

Page 14: ...r CT Timer 4 8 16 or 32 hours DIP Switch Manual Reset button Remote SCADA supervisory reset 9 110VDC Indication Red High intensity LED s for earth fault Red Amber and Green LED for battery status Exte...

Page 15: ...1 12 13 11 Dimensions 11 1 Housing Overall dimensions 85 x 94 x 51 6 mm 4 x 4 2mm Mounting holes on 74 x 74 mm centres as shown below 11 2 Split core Rogowski coil CT Overall dimensions 40x45x28 mm sh...

Page 16: ...tion Prod no 01021000 CT210 with Lithium battery CT 3m cable and short coil Prod no 01021011 CT210 with Lithium battery CT 16m cable and short coil Prod no 01021012 CT210 with Lithium battery CT 3m ca...

Reviews: