background image

 

 

 

Side 6 of 16 

Userguide CableTroll 210 March 2020 

01021000/11/12/13

 

3. Functional description 

3.1 Fault currents in cable network 

The short circuit current magnitude is mainly given by voltage level, type of transformer, primary feeding 
network and the distance from the feeding transformer to the fault location.  
 
A cable short circuit will normally cause a fault current in the kA-range. When short circuit appears near 
the end of a long line, the fault current is most likely to be of a significantly lesser value. 
 
In  networks  with  directly  earthed  neutral  an  earth  fault  is  equivalent  to  a  phase-to-earth  short  circuit. 
The  current  magnitude  will  in  this  case  be  almost  equal  to  the  fault  current  of a  phase-to-phase  short 
circuit.  
 
For  networks  that  do  not  have  a  directly  earthed  neutral,  the  magnitude  of  the  singular  earth  fault 
current is  determined by  the size  of the  galvanically  interconnected network, the voltage level, type of 
cable and the neutral equipment.  
 
The  magnitude  of  a  fault  current  during  a  dual  earth  fault  will  be  almost  equal  to  a  short  circuit  in 
networks that do not have a directly earthed neutral. 
 
IMPORTANT: 

 

As the sensor principle is of the threshold type, correct use of the indicator is subject to calculations of 
earth  fault  currents  and  capacitive  discharge  currents  through  the  sensor  element  (seen  from  the 
feeder).  
 
The capacitive discharge current from behind the Rogowski coil/CT/earth fault element must not exceed 
the trip level setting of the indicator.  
 
The capacitive  discharge current will vary between the different types of cable, and the cable supplier 
should be consulted about the data for your specific type in order to make the correct calculations.  
 
In compensated networks, the earth fault detection may not be possible in certain locations depending 
on the degree of compensation. 
 

3.2 Capacitive Discharge Currents 

The CableTroll 210 series indicators is not directional, (see CableTroll 3500 for directional) it therefore 
detects  current  without  discriminating  its  direction.  In  case  of  an  earth  fault,  the  network  capacitive 
energy discharges in the fault point.  
 
It should be checked that the capacitive discharge current downstream the indicator is below pre-set trip 
level  in  order  to  avoid  the  indicator  erroneously  activating  upon  earth  faults.  If  the  total  capacitive 
current  exceeds  the  trip  level,  it  is  advisable  to  change  the  trip  level  or  install  the  indicators  in  the 
branching points instead of in the main line.  
 
The capacitive discharge of a  branching point is limited by  its own capacitance,  while  in the main line 
the capacitive current of all the branches downstream the indicator is added.  
 
Underground  cables  have  larger  capacitance  than  overhead  lines.  This  must  be  considered  when  an 
overhead line feeds an underground cable and vice versa.  
 

Summary of Contents for 01021000

Page 1: ...Userguide CableTroll 210 March 2020 010121000 11 12 13 CableTroll 210 User Guide for product nr 01021000 11 12 13...

Page 2: ...updated 6 20 09 19 Programming table updated 7 25 09 19 Technical drawing with dimensions updated 8 15 09 19 Updated with Rogowski coil sensor 9 28 01 20 Pictures updated with black Rogowski coil 10...

Page 3: ...6 3 2 CAPACITIVE DISCHARGE CURRENTS 6 3 3 EARTH FAULT DETECTION 7 4 APPLICATION MOUNTING 8 4 1 SENSOR MOUNTING 8 5 BATTERY STATUS 8 5 1 LOW BATTERY LITHIUM BATTERY 8 5 2 TO REPLACE THE BATTERY 9 5 3 R...

Page 4: ...and suitable for use in tropical weather conditions with high humidity of 65 to 95 The CableTroll 210 will indicate earth faults locally by a flashing diode and remotely through a relay contact 1 1 De...

Page 5: ...closed NC Pulse relay may be available from factory on request 2 4 Rogowski coil Current Transformer CT Earth fault element The indicator uses one direct type Rogowski coil for detection of earth faul...

Page 6: ...rough the sensor element seen from the feeder The capacitive discharge current from behind the Rogowski coil CT earth fault element must not exceed the trip level setting of the indicator The capaciti...

Page 7: ...e met Ic It where Ic capacitive current down stream of the indicator It CableTroll 210 programmed trip level sensitivity To estimate the capacitive discharge current at any line point you must calcula...

Page 8: ...e indicator erroneously Product number 01021000 11 12 13 Rogowski Coil Current Transformer Mounting 5 Battery Status 5 1 Low battery Lithium battery When there is less than 20 remaining capacity on th...

Page 9: ...en replaced the battery counter must be reset This is done by pushing the Test Reset button and hold it pressed for more than 30 seconds Observe the following sequence Push the Test Reset button and h...

Page 10: ...ion diagram CT210 Terminal from left 1 Mains reset 220 240VAC 2 Mains reset 220 240VAC 3 SCADA reset 9 110VDC Hot 4 SCADA reset 9 110VDC Ground 5 LED 6 Red 6 LED 6 Black 7 Earth fault Relay 1 NC1 8 Ea...

Page 11: ...fixed trip level 0 0 1 160A fixed trip level 1 0 1 240A fixed trip level Table 1 Switch setting overview trip level NOTE NORTROLLs Earth Fault Indicator and Earth Fault Element are tuned in to consti...

Page 12: ...urs 0 1 16 hours 1 1 32 hours Table 3 Switch overview reset time settings 7 4 Setting Auto reset Select Auto Reset with switch number 8 0 OFF 1 ON 8 Auto reset 0 Auto reset Disabled 1 Auto reset Enabl...

Page 13: ...the CT sensor Auto Reset from sensor Inactive Fault LED flashes rapidly in burst Auto Reset from sensor Active Fault LED illuminates constant Press longer than 5 sec Simulated fault indication with bo...

Page 14: ...r CT Timer 4 8 16 or 32 hours DIP Switch Manual Reset button Remote SCADA supervisory reset 9 110VDC Indication Red High intensity LED s for earth fault Red Amber and Green LED for battery status Exte...

Page 15: ...1 12 13 11 Dimensions 11 1 Housing Overall dimensions 85 x 94 x 51 6 mm 4 x 4 2mm Mounting holes on 74 x 74 mm centres as shown below 11 2 Split core Rogowski coil CT Overall dimensions 40x45x28 mm sh...

Page 16: ...tion Prod no 01021000 CT210 with Lithium battery CT 3m cable and short coil Prod no 01021011 CT210 with Lithium battery CT 16m cable and short coil Prod no 01021012 CT210 with Lithium battery CT 3m ca...

Reviews: